The required Hydrazine Detection System must conform to the specifications of the Drager X-am 5100 and Drager X-zone 5800 or equal models. The system must meet requirements for dimensions, weight, ambient conditions, alarms, ingress protection, operating time, data logging, and certifications.
The related federal contract opportunity is a Pre-Solicitation Request for Information (RFI) from the 162nd Wing Contracting Office for a Hydrazine Detection System. The anticipated NAICS code is 334519 with a 600 employee size standard. The anticipated PSC is 6665. Interested parties are requested to provide information about their qualifications by the date and time listed in SAM.gov. No solicitation or contract award will result from this RFI.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sources Sought- Hydrazine Detection System.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W50S6S24RFI0015
Hydrazine Detection System
MFG: Drager or equal
Model: Drager X-am 5100 & Drager X-zone 5800 or equal
Part number- 8326839 (Drager X-am 5100) , 8329040 (Drager X-zone 5800) or equal Conforming to the requirements below specifications:
(Drager X-am 5100) or equal
• Dimensions (W x H x D)- 48 x 130 x 61 mm; 1.89 x 5.12 x 2.4 inches
• Weight- 220 – 250 g; 7.8 – 8.8 oz.
• Ambient condi�ons Temperature - 20 to + 50 °C; - 4 to + 122 °F
• Pressure 700 to 1300 mbar; 20.7 to 38.4 inch Hg
• Rela�ve humidity 10 to 90 % RH
• Alarms Visual 360°
• Audible Mul�-tone > 90 dB at 30 cm; 1 �.
• Vibra�on
• Ingress Protec�on IP 54
• Opera�ng �mes
• ~150 h (alkaline batery), ~150 h (NiMH rechargeable batery), or
• ~180 h (NiMH high capacity rechargeable batery)
• Charging �mes < 4 h
• Data logger Retrievable using an infrared interface
• > 1000 h at a recording interval of 1 value per minute
• CE mark Electromagne�c compa�bility
• Guideline 2004/108/EC
• Explosion protec�on – Guideline 94/9/EC
(Drager X-zone 5800) or equal
• Dimensions (W x H x D)- 490 x 300 x 300 mm (20 x 12 x 12 in)
• Weight- 10 kg (22 lbs.) (24 Ah batery)
• Ambient condi�on
• Temperature max. +50 °C (+122 °F), depending on sensors used
• Pressure 700 to 1,300 hPa
• Humidity 10 to 95 % r.h.
• Ambient condi�ons
• Temperature as low as -50 °C (-58 °F), depending on sensors used
• Ingress Protec�on- IP67
Alarm
• Visual 360° LED (illuminated ring)
• Audible 360°; >108 dB in a distance of 1 m (3 �), 120 dB in a distance of 30 cm (1 �)
• Configurable alarm paterns, frequencies and volumes
Life signal
• Green status display (360°),
• illuminated ring (LED)
Opera�ng �me
• Approx. 120 h (24 Ah batery)
• Depending on sensor equipment / configura�on of the life signal, Extended run �me is possible with op�onal Power Supply Ex
Charging �me
• Approx. 14 h
• Flexible power supply: External 100 – 240 V charger (worldwide) or induc�ve wireless charger
Pump opera�on.
• Maximum hose length: 45 m (150 �); 30 m (98 �) for Zone 0
Alarm output.
• Poten�al-free alarm contact for intrinsically safe circuits (6-pole); <20 V to 0.25 A (0.15
A constant current); Resis�ng load.
Radio transmission
• Worldwide license-free ISM frequencies
• Digital radio, robust and interference-free transmission up to 100 m (328 �)
RF approvals
• 915 MHz (USA, Canada)
Approvals
• ATEX I M1 Ex ia I Ma, II 1G Ex ia IIC T4 Ga
• IECEx Ex ia I Ma, Ex ia IIC T4 Ga
• CSA (Canada and US) [Ex ia Ga] IIC, [AEx ia Ga] IIC