Requests for Information – Fire Alarm Repair 15 July 20

1. Specs call for repair or replacement if a device can't be fixed how are we to price this, i.e. will a mod be issued for the additional cost?

The bidder should price these items as repair. The contractor will be required to provide the Government with a change order request and cost proposal, to include supporting documentation, if items are unrepairable and must be replaced. This shall be accomplished once during contract performance and include all items that need to be replaced. The Government shall then make a determination on accepting the proposal and issuing a modification.

2. Please supply quantities needed for "Building 1225 Replace all obsolete or non-functioning heat detectors. 19 heat detectors Replace the smoke detectors in the sleeping quarters." 21 smoke detectors

3. "Monaco fire alarm panel has failed and needs to be replaced” What is the model number of the above? (Building 1406) Fire Lite MS-2 Fire Alarm Panel

4. "Replace all obsolete or non-functioning heat detectors" Please supply quantities. (Building 1406) 2 heat detectors

5. “Replace all heat detectors that are over 15 years old."

Please supply quantities (Buildings 1700-1708) 5 heat detectors

6. "Building 1804 Replace all heat detectors that are obsolete or non-functioning. 17 heat detectors

7. Building 1805 Replace all heat detectors that are obsolete or non-functioning.

Please supply quantities for the above. 5 heat detectors

8. Building 1806

Replace all heat detectors that are obsolete or non-functioning.
Supply quantities 3 heat detectors

9. “Building 1807/1808 igloo Replace all heat detectors that obsolete or non-functioning. 4 heat detectors

10. Inspect all horns and strobes, contractor shall replace or repair any horns and strobes found to be non-functioning." 2 horn strobes