ME010_LightingWorkbook.xlsx
XLSX spreadsheet 51 KB Posted
- Attached to
- Construction - Lighting Upgrade Federal contract opportunity
- Solicitation number
- W15QKN-21-Q-5126
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ME006 7829-126 Elec Sch sht 26.PDF | ||
| ME006 7829-123 Elec FP sht 23.PDF | ||
| ME001 29-06-71 Elec 1st FP sht 56.PDF | ||
| ME006_LightingWorkbook.xlsx | XLSX spreadsheet | |
| ME001_LightingWorkbook.xlsx | XLSX spreadsheet | |
| ME010 7828-339 E3 Lighting Plan sht 39 of 51.PDF | ||
| ME001 29-06-71 Elec 2nd FP sht 57.PDF | ||
| Inquiries Responses to W15QKN-21-Q-5126 Lighting Upgrade.pdf | ||
| Amendment 0001 Extending Sol Lighting Upgrade.pdf | ||
| W15QKN-21-Q-5126 Lighting Upgrade Posted to FBO.pdf | ||
| W15QKN-21-Q-5126 Lighting Upgrade Posted to FBO.pdf | ||
| Contractor Cost Breakdown Form.xls | XLS spreadsheet | |
| Attachment 6 DavisBacon ME20210019 Saco.pdf | ||
| Attachment 1 SOW Lighting Upgrade Auburn ME.pdf | ||
| Attachment 4 DavisBacon ME20210015 Auburn.pdf | ||
| Attachment 5 DavisBacon ME20210017 Dexter.pdf | ||
| Attachment 3 SOW Lighting Upgrade Saco ME.pdf | ||
| Attachment 2 SOW Lighting Upgrade Dexter ME.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lighting Fixture Schedule
| FROM AS-BUILT | REPLACEMENT SCHEDULE | |||||||||||||||
| Fixture Type | Manufacturer | Catalog Number | Volts | LAMP DATA | MOUNTING TYPE | DESCRIPTION | ||||||||||
| QTY | BALLAST | TYPE (Watts) | Fixture Style | Fixture Qty | Lamp Qty | Lamp Type | Qty | Wattage /lamp | Fixture Wattage | Total Wattage /type | ||||||
| A1 | 277 | 4 | T5HO | 54 | High Bay | 2x4 Fluorescent, 4-lamp instant start ballast | 27 | 108 | HIGH BAY EQ TO 4 T5 HO | 1 | 136 | 136 | 14688 | |||
| A2 | 277 | 1 | T8-D835 | 32 | Wrap Around | 1x4 Fluorescent, 1-lamp instant start ballast | 4 | 4 | T8 - TLED DIRECT FIT | 1 | 10 | 10 | 40 | |||
| A3 | 277 | 2 | T8-D835 | 32 | Wrap Around | 1x4 Fluorescent, 2-lamp instant start ballast | 40 | 80 | T8 - TLED DIRECT FIT | 2 | 10 | 20 | 800 | |||
| A4 | 277 | 2 | T8-D835 | 32 | Recessed | 2x4 Fluorescent, 2-lamp instant start ballast | 67 | 134 | T8 - TLED DIRECT FIT | 2 | 10 | 20 | 1340 | |||
| A5 | 277 | 3 | T8-D835 | 32 | Recessed | 2x4 Fluorescent, 3-lamp instant start ballast | 21 | 63 | T8 - TLED DIRECT FIT | 3 | 10 | 30 | 630 | |||
| A6 | 277 | 4 | T8-D836 | 32 | Recessed | 2x4 Fluorescent, 4-lamp instant start ballast | 10 | 1 | T8 - TLED DIRECT FIT | 4 | 10 | 40 | 10 | |||
| A7 | 277 | 1 | T8-D836 | 32 | Strip | 4 feet strip, 1-lamp instant star balast | 2 | 2 | T8 - TLED DIRECT FIT | 1 | 10 | 10 | 20 |
TOTAL 171 392
Lighting Savings
| MA022 - Lighting Workbook | ||||||||||||||||||||||||||||||||
| INTERIOR LIGHTING | ||||||||||||||||||||||||||||||||
| Building | Space Type | Fixture Qty | EXISTING | PROPOSED | PROPOSED CONTROLS | SAVINGS | ||||||||||||||||||||||||||
| Location | Existing Controls | Hours Reduction Factor | Fixture Code (from As-Built) | Type | Lamp Qty | Lamp Wattage | Lamp Type | Actual Fixture Wattage | Annual Runtime Hours | kWbase | kwh base | Lamp Qty | Lamp Type | Lamp Wattage | Fixture Wattage | kWee | kWh ee | Control Measure? | Control Type | Reduction Factor | CF | IF | Lamp kWh Savings | Lamp kW Savings | Controls kWh Savings | Controls kW Savings | TOTAL kWh Savings | TOTAL Demand Savings (kw) | Comments | |||
| Training Ctr | ROOM 101 | Office (Occupied) | --- | 0 | 15 | A1 | 4 | 54 | T5HO | 216 | 2600 | 3.24 | 8424 | 1 | HIGH BAY EQ TO 4 T5 HO | 136 | 136.0 | 2.04 | 5304 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 3120.00 | 0.82 | 1591.20 | 0.42 | 4711 | 1.23 | ||
| Training Ctr | ROOM 102 | Misc / Storage | --- | 0 | 2 | A2 | 1 | 32 | T8-D835 | 32 | 900 | 0.064 | 58 | T8 - TLED DIRECT FIT | 10 | 10.0 | 0.02 | 18 | Yes | Occupancy Sensor | 0.3 | 0.72 | 0 | 39.60 | 0.03 | 5.40 | 0.00 | 45 | 0.04 | |||
| Training Ctr | ROOM 103 | Misc / Storage | --- | 0 | 2 | A2 | 1 | 32 | T8-D835 | 32 | 900 | 0.064 | 58 | T8 - TLED DIRECT FIT | 10 | 10.0 | 0.02 | 18 | Yes | Occupancy Sensor | 0.3 | 0.72 | 0 | 39.60 | 0.03 | 5.40 | 0.00 | 45 | 0.04 | |||
| Training Ctr | ROOM 104 | Misc / Storage | --- | 0 | 8 | A3 | 2 | 32 | T8-D835 | 64 | 900 | 0.512 | 461 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.16 | 144 | Yes | Occupancy Sensor | 0.3 | 0.72 | 0 | 316.80 | 0.25 | 43.20 | 0.03 | 360 | 0.29 | |||
| Training Ctr | ROOM 105 | Misc / Storage | --- | 0 | 3 | A3 | 2 | 32 | T8-D835 | 64 | 900 | 0.192 | 173 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.06 | 54 | Yes | Occupancy Sensor | 0.3 | 0.72 | 0 | 118.80 | 0.10 | 16.20 | 0.01 | 135 | 0.11 | |||
| Training Ctr | ROOM 106 | Misc / Storage | --- | 0 | 6 | A3 | 2 | 32 | T8-D835 | 64 | 900 | 0.384 | 346 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.12 | 108 | Yes | Occupancy Sensor | 0.3 | 0.72 | 0 | 237.60 | 0.19 | 32.40 | 0.03 | 270 | 0.22 | |||
| Training Ctr | ROOM 107 | Office (Occupied) | --- | 0 | 5 | A3 | 2 | 32 | T8-D835 | 64 | 2600 | 0.32 | 832 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.1 | 260 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 572.00 | 0.15 | 78.00 | 0.02 | 650 | 0.17 | |||
| Training Ctr | ROOM 108 | Office (Occupied) | --- | 0 | 6 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.384 | 998 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.12 | 312 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 686.40 | 0.18 | 93.60 | 0.02 | 780 | 0.20 | |||
| Training Ctr | ROOM 109 | Misc / Storage | --- | 0 | 6 | A3 | 2 | 32 | T8-D835 | 64 | 900 | 0.384 | 346 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.12 | 108 | Yes | Occupancy Sensor | 0.3 | 0.72 | 0 | 237.60 | 0.19 | 32.40 | 0.03 | 270 | 0.22 | |||
| Training Ctr | ROOM 110 | Bathroom | --- | 0 | 4 | A3 | 2 | 32 | T8-D835 | 64 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.08 | 208 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 111 | Bathroom | --- | 0 | 8 | A3 | 2 | 32 | T8-D835 | 64 | 2600 | 0.512 | 1331 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.16 | 416 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 915.20 | 0.24 | 124.80 | 0.03 | 1040 | 0.27 | |||
| Training Ctr | ROOM 112 | Office (Occupied) | --- | 0 | 14 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.896 | 2330 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.28 | 728 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 1601.60 | 0.42 | 218.40 | 0.06 | 1820 | 0.48 | |||
| Training Ctr | ROOM 113 | Office (Occupied) | --- | 0 | 2 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.192 | 499 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.06 | 156 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 343.20 | 0.09 | 46.80 | 0.01 | 390 | 0.10 | |||
| Training Ctr | ROOM 114 | Office (Occupied) | --- | 0 | 2 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.192 | 499 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.06 | 156 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 343.20 | 0.09 | 46.80 | 0.01 | 390 | 0.10 | |||
| Training Ctr | ROOM 115 | Office (Occupied) | --- | 0 | 3 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.288 | 749 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.09 | 234 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 514.80 | 0.13 | 70.20 | 0.02 | 585 | 0.15 | |||
| Training Ctr | ROOM 116 | Office (Occupied) | --- | 0 | 2 | A6 | 4 | 32 | T8-D836 | 128 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 40.0 | 0.08 | 208 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 117 | Office (Occupied) | --- | 0 | 2 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.128 | 333 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.04 | 104 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 228.80 | 0.06 | 31.20 | 0.01 | 260 | 0.07 | |||
| Training Ctr | ROOM 118 | Office (Occupied) | --- | 0 | 2 | A6 | 4 | 32 | T8-D836 | 128 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 40.0 | 0.08 | 208 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 119 | Office (Occupied) | --- | 0 | 2 | A6 | 4 | 32 | T8-D836 | 128 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 40.0 | 0.08 | 208 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 120 | Office (Occupied) | --- | 0 | 4 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.08 | 208 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 121 | Bathroom | --- | 0 | 2 | A7 | 1 | 32 | T8-D836 | 32 | 2600 | 0.064 | 166 | T8 - TLED DIRECT FIT | 10 | 10.0 | 0.02 | 52 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 114.40 | 0.03 | 15.60 | 0.00 | 130 | 0.03 | |||
| Training Ctr | ROOM 122 | Bathroom | --- | 0 | 1 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.064 | 166 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.02 | 52 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 114.40 | 0.03 | 15.60 | 0.00 | 130 | 0.03 | |||
| Training Ctr | ROOM 123 | Office (Occupied) | --- | 0 | 6 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.384 | 998 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.12 | 312 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 686.40 | 0.18 | 93.60 | 0.02 | 780 | 0.20 | |||
| Training Ctr | ROOM 124 | Office (Occupied) | --- | 0 | 22 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 1.408 | 3661 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.44 | 1144 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 2516.80 | 0.66 | 343.20 | 0.09 | 2860 | 0.75 | |||
| Training Ctr | ROOM 125 | Office (Occupied) | --- | 0 | 2 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.192 | 499 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.06 | 156 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 343.20 | 0.09 | 46.80 | 0.01 | 390 | 0.10 | |||
| Training Ctr | ROOM 126 | Office (Occupied) | --- | 0 | 2 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.192 | 499 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.06 | 156 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 343.20 | 0.09 | 46.80 | 0.01 | 390 | 0.10 | |||
| Training Ctr | ROOM 127 | Office (Occupied) | --- | 0 | 2 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.192 | 499 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.06 | 156 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 343.20 | 0.09 | 46.80 | 0.01 | 390 | 0.10 | |||
| Training Ctr | ROOM 128 | Office (Occupied) | --- | 0 | 3 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.288 | 749 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.09 | 234 | Yes | Occupancy Sensor | 0.3 | 0.68 | 0 | 514.80 | 0.13 | 70.20 | 0.02 | 585 | 0.15 | |||
| Training Ctr | ROOM 129 | Office (Occupied) | --- | 0 | 2 | A6 | 4 | 32 | T8-D836 | 128 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 40.0 | 0.08 | 208 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 130 | Office (Occupied) | --- | 0 | 2 | A6 | 4 | 32 | T8-D836 | 128 | 2600 | 0.256 | 666 | T8 - TLED DIRECT FIT | 10 | 40.0 | 0.08 | 208 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 457.60 | 0.12 | 62.40 | 0.02 | 520 | 0.14 | |||
| Training Ctr | ROOM 136 | Office (Occupied) | --- | 0 | 3 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.288 | 749 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.09 | 234 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 514.80 | 0.13 | 70.20 | 0.02 | 585 | 0.15 | |||
| Training Ctr | ROOM 137 | Office (Occupied) | --- | 0 | 2 | A5 | 3 | 32 | T8-D835 | 96 | 2600 | 0.192 | 499 | T8 - TLED DIRECT FIT | 10 | 30.0 | 0.06 | 156 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 343.20 | 0.09 | 46.80 | 0.01 | 390 | 0.10 | |||
| Training Ctr | ROOM 138 | Office (Occupied) | --- | 0 | 12 | A4 | 2 | 32 | T8-D835 | 64 | 2600 | 0.768 | 1997 | T8 - TLED DIRECT FIT | 10 | 20.0 | 0.24 | 624 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 1372.80 | 0.36 | 187.20 | 0.05 | 1560 | 0.41 | |||
| OMS | MAINTENANCE BAY | OMS | --- | 0 | 12 | A1 | 4 | 54 | T5HO | 216 | 2600 | 2.592 | 6739 | 1 | HIGH BAY EQ TO 4 T5 HO | 136 | 136.0 | 1.632 | 4243 | No | Occupancy Sensor | 0.3 | 0.68 | 0 | 2496.00 | 0.65 | 1272.96 | 0.33 | 3769 | 0.99 |
TOTAL 39317 17095 TOTAL 22222 6 5129 1 27350 8
| EXTERIOR LIGHTS | |||||||||||||||||||||||||||||
| Building | Space Type | Fix Qty | EXISTING | PROPOSED | CONTROLS | CALCULATIONS | |||||||||||||||||||||||
| Location | Fixture Type (from As-Builts) | Type | Lamp Qty | Lamp Wattage | Lamp Type | Actual Fixture Wattage | Annual Runtime Hours | kWbase | kwh base | Lamp Type | Lamp Wattage | Fixture Wattage | kWee | kWh ee | Control Measure? | Control Type | Annual Runtime Hours after CM | CF | IF | Lamp kWh Savings | Lamp kW Savings | Controls kWh Savings | Controls kW Savings | TOTAL kWh Savings | TOTAL Demand Savings (kw) | Comments | |||
| ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | No | Existing Photocell | 0.0 | 1 | 0 | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | |||||||
| --- | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | 0 | ||||||||||||||||||||||||
| TOTAL | ERROR:#N/A | ERROR:#N/A | TOTAL | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A | ERROR:#N/A |
TOTAL (ALL LIGHTING) ERROR:#N/A ERROR:#N/A
| SUMMARY OF FIXTURE TYPES | Fixtures | Lamps |
| U | 0 | 0 |
TOTAL 0 0
| Space Type | Runtime Hours | Logic | CF | IF |
| --- | 0 | 1.00 | 0.00 | |
| 24hr Load | 8760 | 0.72 | 0 | |
| Corridors / Stairwells | 8760 | 0.72 | 0 | |
| Exterior | 4380 | 1.00 | 0.00 | |
| Misc / Storage | 900 | 0.72 | 0 | |
| Office (Occupied) | 2600 | 0.68 | 0 | |
| Office (Unused) | 900 | 0.68 | 0 | |
| Classroom | 2600 | 0.68 | 0 | |
| Bathroom | 2600 | 0.68 | 0 | |
| OMS | 2600 | 0.68 | 0 |
| Control Measure | Reduction | Logic | Y/N |
| --- | 0.0 | No Change | |
| Occupancy Sensor | 0.3 | NJ TRM | Yes |
| Daylight Dimming | 0 | NJ TRM | No |
| Existing Photocell | 0.0 | No Change |