Lighting Fixture Schedule

FROM AS-BUILTREPLACEMENT SCHEDULE
Fixture TypeManufacturerCatalog NumberVoltsLAMP DATAMOUNTING TYPEDESCRIPTION
QTYBALLASTTYPE (Watts)Fixture StyleFixture QtyLamp QtyLamp TypeQtyWattage /lampFixture WattageTotal Wattage /type
A12774T5HO54High Bay2x4 Fluorescent, 4-lamp instant start ballast27108HIGH BAY EQ TO 4 T5 HO113613614688
A22771T8-D83532Wrap Around1x4 Fluorescent, 1-lamp instant start ballast44T8 - TLED DIRECT FIT1101040
A32772T8-D83532Wrap Around1x4 Fluorescent, 2-lamp instant start ballast4080T8 - TLED DIRECT FIT21020800
A42772T8-D83532Recessed2x4 Fluorescent, 2-lamp instant start ballast67134T8 - TLED DIRECT FIT210201340
A52773T8-D83532Recessed2x4 Fluorescent, 3-lamp instant start ballast2163T8 - TLED DIRECT FIT31030630
A62774T8-D83632Recessed2x4 Fluorescent, 4-lamp instant start ballast101T8 - TLED DIRECT FIT4104010
A72771T8-D83632Strip4 feet strip, 1-lamp instant star balast22T8 - TLED DIRECT FIT1101020

TOTAL 171 392

Lighting Savings

MA022 - Lighting Workbook
INTERIOR LIGHTING
BuildingSpace TypeFixture QtyEXISTINGPROPOSEDPROPOSED CONTROLSSAVINGS
LocationExisting ControlsHours Reduction FactorFixture Code (from As-Built)TypeLamp QtyLamp WattageLamp TypeActual Fixture WattageAnnual Runtime HourskWbasekwh baseLamp QtyLamp TypeLamp WattageFixture WattagekWeekWh eeControl Measure?Control TypeReduction FactorCFIFLamp kWh SavingsLamp kW SavingsControls kWh SavingsControls kW SavingsTOTAL kWh SavingsTOTAL Demand Savings (kw)Comments
Training CtrROOM 101Office (Occupied)---015A1454T5HO21626003.2484241HIGH BAY EQ TO 4 T5 HO136136.02.045304NoOccupancy Sensor0.30.6803120.000.821591.200.4247111.23
Training CtrROOM 102Misc / Storage---02A2132T8-D835329000.06458T8 - TLED DIRECT FIT1010.00.0218YesOccupancy Sensor0.30.72039.600.035.400.00450.04
Training CtrROOM 103Misc / Storage---02A2132T8-D835329000.06458T8 - TLED DIRECT FIT1010.00.0218YesOccupancy Sensor0.30.72039.600.035.400.00450.04
Training CtrROOM 104Misc / Storage---08A3232T8-D835649000.512461T8 - TLED DIRECT FIT1020.00.16144YesOccupancy Sensor0.30.720316.800.2543.200.033600.29
Training CtrROOM 105Misc / Storage---03A3232T8-D835649000.192173T8 - TLED DIRECT FIT1020.00.0654YesOccupancy Sensor0.30.720118.800.1016.200.011350.11
Training CtrROOM 106Misc / Storage---06A3232T8-D835649000.384346T8 - TLED DIRECT FIT1020.00.12108YesOccupancy Sensor0.30.720237.600.1932.400.032700.22
Training CtrROOM 107Office (Occupied)---05A3232T8-D8356426000.32832T8 - TLED DIRECT FIT1020.00.1260YesOccupancy Sensor0.30.680572.000.1578.000.026500.17
Training CtrROOM 108Office (Occupied)---06A4232T8-D8356426000.384998T8 - TLED DIRECT FIT1020.00.12312YesOccupancy Sensor0.30.680686.400.1893.600.027800.20
Training CtrROOM 109Misc / Storage---06A3232T8-D835649000.384346T8 - TLED DIRECT FIT1020.00.12108YesOccupancy Sensor0.30.720237.600.1932.400.032700.22
Training CtrROOM 110Bathroom---04A3232T8-D8356426000.256666T8 - TLED DIRECT FIT1020.00.08208YesOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 111Bathroom---08A3232T8-D8356426000.5121331T8 - TLED DIRECT FIT1020.00.16416YesOccupancy Sensor0.30.680915.200.24124.800.0310400.27
Training CtrROOM 112Office (Occupied)---014A4232T8-D8356426000.8962330T8 - TLED DIRECT FIT1020.00.28728YesOccupancy Sensor0.30.6801601.600.42218.400.0618200.48
Training CtrROOM 113Office (Occupied)---02A5332T8-D8359626000.192499T8 - TLED DIRECT FIT1030.00.06156YesOccupancy Sensor0.30.680343.200.0946.800.013900.10
Training CtrROOM 114Office (Occupied)---02A5332T8-D8359626000.192499T8 - TLED DIRECT FIT1030.00.06156YesOccupancy Sensor0.30.680343.200.0946.800.013900.10
Training CtrROOM 115Office (Occupied)---03A5332T8-D8359626000.288749T8 - TLED DIRECT FIT1030.00.09234YesOccupancy Sensor0.30.680514.800.1370.200.025850.15
Training CtrROOM 116Office (Occupied)---02A6432T8-D83612826000.256666T8 - TLED DIRECT FIT1040.00.08208YesOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 117Office (Occupied)---02A4232T8-D8356426000.128333T8 - TLED DIRECT FIT1020.00.04104YesOccupancy Sensor0.30.680228.800.0631.200.012600.07
Training CtrROOM 118Office (Occupied)---02A6432T8-D83612826000.256666T8 - TLED DIRECT FIT1040.00.08208YesOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 119Office (Occupied)---02A6432T8-D83612826000.256666T8 - TLED DIRECT FIT1040.00.08208YesOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 120Office (Occupied)---04A4232T8-D8356426000.256666T8 - TLED DIRECT FIT1020.00.08208YesOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 121Bathroom---02A7132T8-D8363226000.064166T8 - TLED DIRECT FIT1010.00.0252YesOccupancy Sensor0.30.680114.400.0315.600.001300.03
Training CtrROOM 122Bathroom---01A4232T8-D8356426000.064166T8 - TLED DIRECT FIT1020.00.0252YesOccupancy Sensor0.30.680114.400.0315.600.001300.03
Training CtrROOM 123Office (Occupied)---06A4232T8-D8356426000.384998T8 - TLED DIRECT FIT1020.00.12312YesOccupancy Sensor0.30.680686.400.1893.600.027800.20
Training CtrROOM 124Office (Occupied)---022A4232T8-D8356426001.4083661T8 - TLED DIRECT FIT1020.00.441144YesOccupancy Sensor0.30.6802516.800.66343.200.0928600.75
Training CtrROOM 125Office (Occupied)---02A5332T8-D8359626000.192499T8 - TLED DIRECT FIT1030.00.06156YesOccupancy Sensor0.30.680343.200.0946.800.013900.10
Training CtrROOM 126Office (Occupied)---02A5332T8-D8359626000.192499T8 - TLED DIRECT FIT1030.00.06156YesOccupancy Sensor0.30.680343.200.0946.800.013900.10
Training CtrROOM 127Office (Occupied)---02A5332T8-D8359626000.192499T8 - TLED DIRECT FIT1030.00.06156YesOccupancy Sensor0.30.680343.200.0946.800.013900.10
Training CtrROOM 128Office (Occupied)---03A5332T8-D8359626000.288749T8 - TLED DIRECT FIT1030.00.09234YesOccupancy Sensor0.30.680514.800.1370.200.025850.15
Training CtrROOM 129Office (Occupied)---02A6432T8-D83612826000.256666T8 - TLED DIRECT FIT1040.00.08208NoOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 130Office (Occupied)---02A6432T8-D83612826000.256666T8 - TLED DIRECT FIT1040.00.08208NoOccupancy Sensor0.30.680457.600.1262.400.025200.14
Training CtrROOM 136Office (Occupied)---03A5332T8-D8359626000.288749T8 - TLED DIRECT FIT1030.00.09234NoOccupancy Sensor0.30.680514.800.1370.200.025850.15
Training CtrROOM 137Office (Occupied)---02A5332T8-D8359626000.192499T8 - TLED DIRECT FIT1030.00.06156NoOccupancy Sensor0.30.680343.200.0946.800.013900.10
Training CtrROOM 138Office (Occupied)---012A4232T8-D8356426000.7681997T8 - TLED DIRECT FIT1020.00.24624NoOccupancy Sensor0.30.6801372.800.36187.200.0515600.41
OMSMAINTENANCE BAYOMS---012A1454T5HO21626002.59267391HIGH BAY EQ TO 4 T5 HO136136.01.6324243NoOccupancy Sensor0.30.6802496.000.651272.960.3337690.99

TOTAL 39317 17095 TOTAL 22222 6 5129 1 27350 8

EXTERIOR LIGHTS
BuildingSpace TypeFix QtyEXISTINGPROPOSEDCONTROLSCALCULATIONS
LocationFixture Type (from As-Builts)TypeLamp QtyLamp WattageLamp TypeActual Fixture WattageAnnual Runtime HourskWbasekwh baseLamp TypeLamp WattageFixture WattagekWeekWh eeControl Measure?Control TypeAnnual Runtime Hours after CMCFIFLamp kWh SavingsLamp kW SavingsControls kWh SavingsControls kW SavingsTOTAL kWh SavingsTOTAL Demand Savings (kw)Comments
ERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/ANoExisting Photocell0.010ERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/A
---ERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/A0
TOTALERROR:#N/AERROR:#N/ATOTALERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/AERROR:#N/A

TOTAL (ALL LIGHTING) ERROR:#N/A ERROR:#N/A

SUMMARY OF FIXTURE TYPESFixturesLamps
U00

TOTAL 0 0

Space TypeRuntime HoursLogicCFIF
---01.000.00
24hr Load87600.720
Corridors / Stairwells87600.720
Exterior43801.000.00
Misc / Storage9000.720
Office (Occupied)26000.680
Office (Unused)9000.680
Classroom26000.680
Bathroom26000.680
OMS26000.680
Control MeasureReductionLogicY/N
---0.0No Change
Occupancy Sensor0.3NJ TRMYes
Daylight Dimming0NJ TRMNo
Existing Photocell0.0No Change