Velan Steam Valve Salients.xlsx
XLSX spreadsheet 6 MB Posted
- Attached to
- USS FRANK CABLE Steam Valves
- Solicitation number
- N4044626Q5004
About this file
This is a procurement specification document detailing Velan steam valve requirements for the USS FRANK CABLE (T-ALT AS 39 19018) steam valve replacement project. The document specifies four valve assemblies required for a naval steam system, organized by service application with detailed technical salient characteristics and construction standards.
The procurement covers four Velan globe-style steam valves in quantities of two each: (1) Superheater Steam Stop Valve with Motor-Operated Valve (MOV) actuator, 6-inch, 705 psig, 875°F, CR-MO construction per A217 Gr. WC6 standard; (2) Desuperheater Outlet Steam Stop Valve with MOV actuator, 5-inch, 705 psig, 725°F, carbon steel construction per A216 Gr. WCB standard; (3) Desuperheater Steam to Soot Blowers Valve (manual), 2.5-inch, 705 psig, 725°F, carbon steel construction per A216 Gr. WCB standard; and (4) Main Feed Water Stop/Check Valve to Economizer and Boiler (manual), 4-inch, 920 psig, 263°F, carbon steel construction per A216 Gr. WCB standard. All valves feature 600LB pressure class ratings, butt weld end connections, bolted bonnets, CR-13 stems, and hard-faced/Stellite seats and discs per ASME B16.10 and B16.34 standards. Motor-operated valves require 440V, 60Hz, three-phase power with 15-second cycle times, dual contactors for push-button closure, and single contactor indicator light controls for open/close operations. The specification includes Velan drawing references, bypass valve configurations for two valves, and photographic documentation of valve actuators and installations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment N4044626Q50040001 SF 30.pdf | ||
| Solicitation - N4044626Q5004.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AS
| Design Data | Construction | Motor Operator | ||||||||||||||||||||||||
| Class | Service | Velan Dwg. | Reference Dwg. | Ref Dwg Valve | Qty./Ship | Type | Bypass | Size | Sys. Pipe SCH | Pressure (psig) | Temp (°F) | Material | Standard | Design | Class | Ends | Stem | Seat | Disc | Bonnet | Voltage | Hz | Ph | Cycle Time | Input/Output Requirements | |
| AS | Main Feed Water Stop/Check to Economizer & Boiler Valve | B12-2074B-02TS | 208-4792296 | (V-93 & V-94) | 2 | Globe Stop | No | 4" | 40 | 920 | 263 | Carbon Steel (Cast or Forged) | A216 Gr. WCB or A105 | ASME B16.10 & B16.34 | 600LB | Butt Weld | CR-13 | Hard-Faced | Hard-Faced | Bolted | N/A | N/A | N/A | |||
| AS | Superheater Steam Stop Valve w/ MOV | B14-2085B-05TS-M | 207-4792286 | (V-1 & V-2) | 2 | Angle Globe Stop-Check | Y, 3/4", Series A | 6" | 40 | 705 | 875 | CR-MO | ||||||||||||||
| (Cast) | A217 Gr. WC6 or A182 Gr. F11 CL 2 | ASME B16.10 & B16.34 | 600LB | Butt Weld | CR-13 | Hard-Faced | Hard-Faced | Bolted | 440 | 60 | 3 | 15 sec. | Two (2) Contactors - Push Button Close |
One (1) Contactor - Indicator Light Open/Close
| AS | Desuperheater Outlet Steam Stop Valve w/ MOV | B13-2085B-02TS-M | 514-4792911 | (V-3 & V-4) | 2 | Globe | |||||||||||||
| Stop-Check | Y, 3/4", Series A | 5" | 40 | 705 | 725 | Carbon Steel (Cast or Forged) | A216 Gr. WCB or A105 | ASME B16.10 & B16.34 | 600LB | Butt Weld | CR-13 | Hard-Faced | Hard-Faced | Bolted | 440 | 60 | 3 | 15 sec. | Two (2) Contactors - Push Button Close |
One (1) Contactor - Indicator Light Open/Close
| AS | Desuperheater Steam to Soot Blowers Valve | ||||||||||||||||||||
| B09-2074B-02TS | 514-4792911 | (V-70 & V71) | 2 | Globe Stop | No | 2-1/2" | 40 | 705 | 725 | Carbon Steel (Cast or Forged) | A216 Gr. WCB or A105 | ASME B16.10 & B16.34 | 600LB | Butt Weld | CR-13 | Hard-Faced | Hard-Faced | Bolted | N/A | N/A | N/A |
Procurement Spec
| General Info | Ship Class | AS | AS | AS | AS | |
| Service | Superheater Steam Stop Valve w/ MOV | Desuperheater Outlet Steam Stop Valve w/ MOV | Desuperheater Steam to Soot Blowers Valve | Main Feed Water Stop/Check to Economizer & Boiler Valve | ||
| Velan Dwg. | B14-2085B-05TS-M w/ Bypass | B13-2085B-02TS-M w/ Bypass | B09-2074B-02TS | B12-2074B-02TS | ||
| Reference Dwg. | 207-4792286 | 514-4792911 | 514-4792911 | 208-4792296 | ||
| Ref Dwg Valve | (V-1 & V-2) | (V-3 & V-4) | (V-70 & V71) | (V-93 & V-94) | ||
| Qty./Ship | 2 | 2 | 2 | 2 | ||
| Salient Characteristics | Valve Type | Angle Globe | ||||
| Stop-Check (OS&Y) | Globe | |||||
| Stop-Check (OS&Y) | Globe Stop (OS&Y) | Globe Stop (OS&Y) | ||||
| Bypass | Y, 3/4", Series A, RH of Flow | Y, 3/4", Series A, LH of Flow | No | No | ||
| Size | 6" | 5" | 2-1/2" | 4" | ||
| Sys. Pipe SCH | 40 | 40 | 40 | 40 | ||
| Design Data | Pressure (psig) | 705 | 705 | 705 | 920 | |
| Temp (°F) | 875 | 725 | 725 | 263 | ||
| Medium | Superheated Steam | Desuperheated Steam | Desuperheated Steam | Feedwater | ||
| Construction | Material | CR-MO | ||||
| (Cast or Forged) | Carbon Steel | |||||
| (Cast or Forged) | Carbon Steel | |||||
| (Cast or Forged) | Carbon Steel |
(Cast or Forged)
| Standard | A217 Gr. WC6 or | ||
| A182 Gr. F11 CL 2 | A216 Gr. WCB or | ||
| A105 | A216 Gr. WCB or | ||
| A105 | A216 Gr. WCB or |
A105
| Design | ASME B16.10 & B16.34 | ASME B16.10 & B16.34 | ASME B16.10 & B16.34 | ASME B16.10 & B16.34 | ||
| Pressure Class | 600LB | 600LB | 600LB | 600LB | ||
| Ends | Butt Weld | Butt Weld | Butt Weld | Butt Weld | ||
| Bonnet-Style | Bolted Bonnet | Bolted Bonnet | Bolted Bonnet | Bolted Bonnet | ||
| Stem | CR-13 | CR-13 | CR-13 | CR-13 | ||
| Seat | Stellite/Hard-Faced | Stellite/Hard-Faced | Stellite/Hard-Faced | Stellite/Hard-Faced | ||
| Disc | Stellite/Hard-Faced | Stellite/Hard-Faced | Stellite/Hard-Faced | Stellite/Hard-Faced | ||
| Motor Operator | Voltage | 440 | 440 | N/A | N/A | |
| Hz | 60 | 60 | N/A | N/A | ||
| Ph | 3 | 3 | ||||
| Cycle Time | 15 sec. | 15 sec. | N/A | N/A | ||
| Input/Output Requirements | Two (2) Contactors - Push Button Close | |||||
| One (1) Contactor - Indicator Light Open/Close | Two (2) Contactors - Push Button Close |
One (1) Contactor - Indicator Light Open/Close
| BYPASS GUIDANCE | ||
| Plan View | ||
| Left Hand of Flow | Plan View |
Right Hand of Flow
Photos - Main FW
Photos - Superheater Steam Stop
VALVE ACTUATOR
Photos - Desuperhter Steam Stop
VALVE ACTUATOR
Photos - Soot Blower Valve image1.png image2.png image3.png image4.png image5.png image6.png image7.png image8.png image9.png image10.png image11.png