VA250-17-B-0859 541-17-507 -- Bid Issue - DRAWINGS.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| VA250-17-B-0859-00004000.docx | DOCX document | |
| VA250-17-B-0859-00004002.pdf | ||
| VA250-17-B-0859-00004001.pdf | ||
| VA250-17-B-0859-00003000.docx | DOCX document | |
| VA250-17-B-0859-00002003.pdf | ||
| VA250-17-B-0859-00002002.pdf | ||
| VA250-17-B-0859-00002001.pdf | ||
| VA250-17-B-0859-00002000.docx | DOCX document | |
| VA250-17-B-0859-00001000.docx | DOCX document | |
| VA250-17-B-0859-00001001.pdf | ||
| VA250-17-B-0859-001.docx | DOCX document | |
| VA250-17-B-0859-003.pdf | ||
| VA250-17-B-0859-007.pdf | ||
| VA250-17-B-0859-002.pdf | ||
| VA250-17-B-0859-005.pdf | ||
| VA250-17-B-0859-008.xls | XLS spreadsheet | |
| VA250-17-B-0859-006.pdf | ||
| VA250-17-B-0859-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A B
C
D E F
G
B
C
ICP
I C
P
GI-1
TITLE SHEET & DRAWING
INDEX
SITE KEY PLAN
NTS
10701 EAST BLVD. CLEVELAND, OH. 44106
DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER - WADE PARK
Cleveland Veterans Affairs
Medical Center
MODERNIZE SPS ELEVATORS SE-3 & SE-4 PROJECT
DRAWING INDEX
PROJECT NO. 541-17-507
GI-1 TITLE SHEET & DRAWING INDEX
ARCHITECTURAL
A-1.1 ENLARGED ELEVATOR PLANS - 1ST & 2ND FLOOR AND PIT LEVEL
A-2.0 REFLECTED CEILING PLAN, INTERIOR ELEVATIONS AND DETAILS
MECHANICAL/HVAC
M-0.1 MECHANICAL GENERAL NOTES, DETAILS, AND SCHEDULES
M-1.1 NEW WORK/DEMO - PARTIAL FLOOR PLAN - MECHANICAL
ELECTRICAL
E-0.1 ELECTRICAL GENERAL NOTES AND SYMBOL LEGEND
E-1.1 DEMO/NEW WORK - PARTIAL FLOOR PLANS - ELECTRICAL
E-2.0 ELECTRICAL DETAILS
BID ISSUE SUBMISSION
5.19.17
BUILDING MASTER KEY PLAN
NTS
FIRST FLOOR
NORTH NORTH
PROJECT SITE
ELEVATORS
SE-3 & SE-4
I. PROJECT LOCATION: CLEVELAND VETERANS AFFAIRS MEDICAL CENTER
10701 EAST BLVD.
CLEVELAND, OHIO
II. DESCRIPTION & USER GROUP CLASSIFICATION OF BLDG
A. NATURE OF PROJECT: IMPROVEMENTS TO TWO (2) EXISTING ELEVATORS
B. DESIGN CODES: 2015 NPFA LIFE SAFETY CODE 101, IBC 2015
C. USE GROUP: I-2 - HEALTH CARE - NO CHANGE PROPOSED
D. CONSTRUCTION TYPE: TYPE I -332, IB - NON-COMBUSTIBLE, PROTECTED
FIRE RATED CONSTRUCTION (LSC A.8.2.1.2)
EXTERIOR BEARING WALLS 3 HRS
INTERIOR BEARING WALLS 3 HRS
STRUCTURAL COLUMNS 3 HRS (SUPPORTING > 1 FLOOR)
2 HRS (SUPPORTING 1 FLOOR ONLY)
2 HRS (SUPPORTING ROOF ONLY)
BEAMS, GIRDERS, TRUSSES 3 HRS (SUPPORTING > 1 FLOOR, COLS., OR BEARING
WALLS
2 HRS (ALL OTHERS)
FLOOR-CEILING ASSEMBLIES 2 HRS
ROOF-CEILING ASSEMBLIES 1
HRS
INTERIOR NON-BEARING WALLS 0 HRS
EXTERIOR NON-BEARING WALLS 0 HRS
WALL ASSEMBLIES
EXIT ACCESS CORRIDOR WALLS 0 HR SMOKE PARTITIONS
ELEVATOR MACHINE ROOMS 2 HR FIRE BARRIERS
ELEVATOR HOISTWAYS 2 HR FIRE BARRIERS
E. PROJECT AREA: 180 GSF
F. PROJECT AREA OCCUPANT LOAD: NOT APPLICABLE
G. FIRE PROTECTION EXISTING BUILDING FULLY SPRINKLED. NO MODIFICATIONS
PROPOSED
CODE INFORMATION
Revisions: Date
65% CD's SUBMISSION 2.20.17
DAKCJK5.19.17
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
Stanley J. Kaczmar, License #4988
Expiration Date: 12/31/2017
N
O
T
F
R
C
N
S
T
R
U
C
T
I
O
N
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
CLEVELAND VAMC
100% CD's SUBMISSION 4.14.17
Bid Issue SUBMISSION 5.19.17
126 124
127 128 122
6'-0"
E X
P
I T
2'-0" +/-
EX. PIT
8"
E X
P
I T
8" 2'-0" +/-
EX. PIT
Revisions: Date
5.19.17 CJK DAK
A-1.1
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Construction and Facilities
Management
N
N
S
T
R
U
C
T
I
O
N
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
2.20.1765% CD's SUBMISSION
ENLARGED ELEVATOR PLANS - 1ST &
2ND FLOOR AND PIT LEVEL
3/8" = 1'-0"
ENLARGED ELEVATOR PLANS
PARTIAL FIRST FLOOR
EX. VCT FLOORING
TO REMAIN
4. WHERE NEW UTILITIES ARE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL
REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME, AND PATCH AND REPAIR
WITH NEW TO MATCH EXISTING CONDITIONS.
GENERAL NOTES:
EXISTING WALLS TO REMAIN
1. CONSIDER ALL AREAS OWNER-OCCUPIED, UNLESS OTHERWISE NOTED.
2. ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN
AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE
REQUIREMENTS OF ALL APPLICABLE CODES.
3. PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING
CONDITIONS.
5. ALL DAMAGE TO EXISTING AREAS OCCURRING AS A RESULT OF CONSTRUCTION SHALL BE
REPAIRED AS REQUIRED BY CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL,
CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL
BE REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO OWNER.
6. ALL NEW PENETRATIONS IN FIRE RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS
REQUIRED.
12. ALL FLOOR, WALL, CEILING, AND MISC. FIRE RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE
OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND / OR AS REQUIRED BY CODE. ALL
EXISTING FIRE RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED.
FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRE STOPPING, FIRE RATED DOORS
AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR
INSPECTION BY THE BUILDING OFFICIAL.
7. CONSTRUCTION ACTIVITIES FOR THIS PROJECT OCCUR WITHIN A STERILE ENVIRONMENT.
CONSTRUCTION AREAS MUST BE PROPERLY SCREENED OFF FROM ALL SURROUNDING AREAS,
WHICH WILL BE OCCUPIED AND IN USE THROUGHOUT THE ENTIRETY OF CONSTRUCTION.
COORDINATE ALL REQUIRED SCREENING AND ISOLATION WITH COR. EXISTING EQUIPMENT IN
ROOMS MUST BE PROTECTED THROUGHOUT CONSTRUCTION, AND ALL CONSTRUCTION ACTIVITIES
IN "CLEAN" SPACES MUST BE PROPERLY ISOLATED FROM THE SURROUNDING SPACES
THROUGHOUT THEIR ENTIRETY. GC SHALL PREPARE AN EQUIPMENT PROTECTION PLAN AND
SUBMIT TO THE COR FOR REVIEW AND APPROVAL. GC SHALL COORDINATE WITH THE COR TO
DETERMINE ALL PROTECTION REQUIREMENTS.
ITEMS TO BE DEMOLISHED
8. CONTRACTOR SHALL PROVIDE DUST REMOVING WALK-OFF MATS (TACKY MAT) AT ALL
CONSTRUCTION ENTRY POINTS
9. DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"
ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS. ALL
DEMOLITION WORK BEING DONEIS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE
TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO
VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
10. THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
11. FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
13. DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING
OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY
REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE
PROJECT AREA.
14. ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S
OPERATIONS AS DETERMINED BY THE COR.
SYMBOL LEGEND:
INDICATES NEW DOOR
INDICATES EXISTING DOOR TO REMAIN
TEMPORARY PARTITION WALL W/3'-0" X 7'-0" FLUSH HM DOOR FOR CONTRACTOR ACCESS
ONLY. WALL AND DOOR TO BE REMOVED UPON COMPLETION OF WORK. PATCH REPAIR
EXISTING CONDITIONS AS REQUIRED UPON REMOVAL OF ALL TEMPORARY CONSTRUCTION.
REFER TO TYPICAL TEMPORARY PARTITION DETAIL ON SHEET A-2.0
EXISTING GYP. BD. CEILINGS
EXISTING ACOUSTIC TILE
CEILINGS
EXISTING 2 HR RATED FIRE
BARRIER ASSEMBLY
A-2.0
B
C
D
A
A-2.0
D
A
B
C
E
A-2.0
E
A-2.0
CLEAN SIDE
SPD DEPARTMENT
EXISTING
DIRTY SIDE
SPD DEPARTMENT
EXISTING
EX. CERAMIC TILE
FLOORING TO REMAIN
"CLEAN" ELEVATOR SE-4
"DIRTY" ELEVATOR SE-3
MACHINE ROOM
ELEVATOR
EXISTING
REFER TO MECHANICAL AND ELECTRICAL
DRAWINGS FOR ALL MEP WORK ASSOCIATED WITH
MACHINE ROOM. REFER TO SPEC SECTION 142500
FOR ALL MACHINE ROOM EQUIPMENT TO BE
REMOVED AND REPLACED WITH NEW. FINAL ROOM
LAYOUT TO BE PROVIDED BY ELEVATOR
CONTRACTOR. SUBMIT TO COR FOR REVIEW AND
APPROVAL
4.14.17100% CD's SUBMISSION
3/8" = 1'-0"
ENLARGED ELEVATOR PLANS
PARTIAL SECOND FLOOR
STORAGE
EX. MEDICAL
(DIRTY SIDE)
MED. STORAGE
EXISTING
(CLEAN SIDE)
E
A-2.0
SIM.
E
A-2.0
SIM.
REFER TO FIRST FLOOR
PLAN ABOVE FOR ALL
ELEVATOR CAB WORK
EXISTING WALL-MTD.
FIRE EXTINGUISHER
TO REMAIN
MACHINE ROOM
FINISH SCOPE:
REPAINT ALL FOUR
(4) EXISTING WALLS
3/8" = 1'-0"
ENLARGED PLAN
ELEVATOR PIT LEVEL
MED. STORAGE
EXISTING
(CLEAN SIDE)
A
A
A
A-2.0
A-2.0
CONSTRUCTION NOTES:
HOISTWAY ENTRANCE SCOPE: EXISTING STAINLESS STEEL ON HOISTWAY DOOR FRAMES TO BE
REMOVED, AND FRAMES SHALL BE RE-CLAD WITH NEW SATIN STAINLESS STEEL - VERIFY DIMENSIONS
IN FIELD. RETAIN EXISTING DOOR OPENER OVERRIDE HOLES IN FACE OF DOOR. HOISTWAY ACCESS
SHALL BE ADDED TO BOTH TERMINAL LANDINGS, MOUNTED IN HOISTWAY JAMBS. EXISTING FASCIA, TOE GUARD, AND DUST COVERS SHALL BE RETAINED. REPLACE ANY MISSING LOCATIONS - VERIFY
SCOPE IN FIELD
EXISTING SILL TO REMAIN AND BE RECLEANED AND POLISHED ONLY. EXISTING SILL SUPPORTS
SHALL BE CLEANED FREE OF DUST.
EXISTING VCT FLOORING IN ELEVATOR CABS TO BE REMOVED ENTIRELY. PREP EXISTING CAB
SUBFLOOR AS REQUIRED TO RECEIVE NEW SHEET VINYL FLOORING WITH HEAT WELDED SEAMS
EXISTING STAINLESS STEEL RAILINGS, STAINLESS STEEL PANELING AND BASE, AND PLASTIC
LAMINATE-FACED WALL PANELS TO BE REMOVED. PROJECT INTENT IS FOR THE ENTIRETY OF
EXISTING INTERIOR WALL FINISHES TO BE REMOVED AND REPLACED WITH NEW - SEE INT. ELEVS.
EXISTING ELEVATOR CONTROLS TO BE REMOVED AND REPLACED - REFER TO SPECIFICATIONS FOR
REPLACEMENT
NOTE: REFER TO SPEC SECTION 14 25 00 "HYDRAULIC ELEVATOR MODERNIZATION" FOR FULL
MODERNIZATION SCOPE. SCOPE DEPICTED BELOW IS LIMITED TO INTERIOR FINISH AND GENERAL LIFE
SAFETY UPGRADES. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
DEMOLITION/IMPROVEMENT SCOPE
NEW 3" W STAINLESS STEEL HANDRAILS, ATTACHED TO NEW STAINLESS STEEL WALL PANEL
ASSEMBLY W/MIN. (4) ATTACHMENTS - MATCH EXISTING PROFILE. SEE ELEVATION FOR INSTALLATION
HEIGHTS
HATCHED AREA INDICATES NEW SATIN STAINLESS STEEL WALL PANELS OVER
PLYWOOD SUBSTRATE. SEE ELEVATION FOR SEAM LOCATION
EXISTING LIGHT SOFFIT ASSEMBLY AND 7" H STAINLESS STEEL END TRIM TO REMAIN, PROTECT AS
REQUIRED THROUGHOUT CONSTRUCTION. NEW LED LIGHTING TO BE PROVIDED
LOCATION OF NEW HORIZONTAL ELEVATOR CONTROL PANEL IN FORMER REMOVED, EXISTING
CONTROL PANEL. VERIFY FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT SHEET AND
COORDINATION SIZE OF WALL OPENING ACCORDINGLY
LOCATION OF NEW VERTICAL ELEVATOR CONTROL PANEL IN FORMER REMOVED, EXISTING CONTROL
PANEL. VERIFY FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT SHEET AND COORDINATION SIZE OF
WALL OPENING ACCORDINGLY
LOCATION OF NEW EMERGENCY PHONE IN FORMER REMOVED, EXISTING PHONE LOCATION. VERIFY
FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT SHEET AND COORDINATION SIZE OF WALL OPENING
ACCORDINGLY
EXISTING STAINLESS STEEL FASCIA ASSEMBLY AND FLOOR INDICATOR UNIT TO BE REMOVED AND
REPLACED WITH NEW. VERIFY FLOOR INDICATOR UNIT WITH SELECTED MANUFACTURER. RECLAD
EXISTING RETURNS WITH NEW SATIN STAINLESS STEEL.
LOCATION OF NEW ELEVATOR CALL BUTTON UNIT IN FORMER REMOVED, LOCATION. GRAPHIC
SHOWN IS OF EXISTING UNIT. REMOVE EXISTING FRP WAINSCOT PANEL IN ITS ENTIRETY AND
FURNISH NEW TO MATCH EXISTING. VERIFY OPENING SIZE FOR NEW CALL BUTTON UNIT IN FIELD
WITH MANUFACTURER'S CUT SHEET AND COORDINATION SIZE OF OPENING ACCORDINGLY. NOTE:
REMOVAL OF FRP PANEL SCOPE OCCURS AT 1ST FLOOR OF CLEAN SIDE ELEVATOR ONLY.
EX. CORNER GUARD TO BE REMOVED AND REINSTALLED UPON INSTALLATION OF NEW FRP PANEL.
NOTE: CLEAN SIDE ELEVATOR SCOPE ONLY
LOCATION OF NEW FLOOR LEVEL INDICATOR PANEL IN FORMER REMOVED, EXISTING LOCATION.
GRAPHIC SHOWN IS OF EXISTING UNIT. VERIFY FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT
SHEET AND COORDINATION SIZE OF WALL OPENING ACCORDINGLY. PATCH EXISTING GYP. BD. AND
REPAINT AS REQUIRED
EXISTING NON-RATED HOLLOW METAL DOOR AND FRAME ASSEMBLY TO BE REMOVED AND REPLACED
WITH NEW 3'-0" X 7'-0", 90 MIN. RATED FLUSH HOLLOW METAL DOOR AND WELDED FRAME. PAINT TO
MATCH EXISTING DOORS. DOOR SHALL BE PROVIDED WITH CLOSER AND DOOR LEVER AND LOCK TO
MATCH EXISTING HARDWARE IN SPACE. COORDINATE KEYING WITH COR. ALL NEW HARDWARE
SHALL BE UL LISTED
HATCHED REGION INDICATES EXISTING 24 x 24 x 9-1/2" D SUMP PIT TO BE INCREASED IN SIZE FOR
NEW SUMP PUMP INSTALLATION. DEMO EXISTING BOTTOM SLAB AND 8" OF PERIMETER SLAB AS
SHOWN. REFER TO SECTION DETAIL FOR PIT MODIFICATION. REFER TO MEP DWGS. FOR SUMP PUMP
INFORMATION
EXISTING STEEL PIT LADDERS TO REMAIN AND BE INCREASED IN DEPTH AWAY FROM WALL WITH NEW
ANGLE ATTACHMENTS. SEE DETAIL
EXISTING UTILITY PENETRATIONS THRU 2-HR RATED HOISTWAY WALL TO BE FIRESTOPPED ON BOTH
SIDES OF WALL - SEE DETAIL
EXISTING CAR DOORS AND HARDWARE TO BE REMOVED AND REPLACED WITH NEW 2-SPEED/SIDE
SLIDE DOORS - SATIN STAINLESS STEEL FINISH. SEE SPECS.
EXISTING HOISTWAY DOORS AND HARDWARE TO BE REMOVED AND REPLACED WITH NEW
2-SPEED/SIDE SLIDE DOORS - SATIN STAINLESS STEEL FINISH. SEE SPECS.
ALIGN
ALIGN
EXISTING DOOR SHALL BE USED
FOR CONTRACTOR ACCESS
DURING CONSTRUCTION.
COORDINATE WITH COR
REQUIREMENTS FOR SIGNAGE TO
BE PROVIDED BY GC
ALIGN
ALIGN ALIGN
NOTE: EX. WINDOWS SHALL
BE BLOCKED OFF WITH
1-5/8" MTL. STUD WALL
ASSEMBLY W/ONE (1)
LAYER
" THK. GYP. BD. UP
TO UNDERSIDE OF EX.
CEILING
REFER TO MECHANICAL
AND ELECTRICAL
DRAWINGS FOR ALL MEP
WORK ASSOCIATED WITH
ELEVATOR PITS
REFER TO SPEC
SECTION 142500 FOR
ALL WORK ASSOCIATED
WITH CAR PLUNGER
AND OTHER ELEVATOR
PIT EQUIPMENT
"DIRTY"
"CLEAN" "CLEAN" "CLEAN"
"DIRTY" "CLEAN" "CLEAN"
FIRESTOPPING SCOPE: WHERE EXISTING
PENETRATING ITEMS THRU MACHINE ROOM WALLS
ARE TO BE REMOVED AS A PART OF THIS PROJECT,
EXISTING 2 HR WALL ASSEMBLIES SHALL BE
RESTORED WITH MATCHING CONSTRUCTION
MATERIALS TO FULLY PATCH/REPAIR FORMER
PENETRATIONS. WHERE NEW PENETRATIONS
OCCUR, SAME SHALL BE FIRESTOPPED WITH A
UL-RATED 2 HR RATED THRU-WALL PENETRATION
ASSEMBLY. GC SHALL SUBMIT ALL UL ASSEMBLIES
FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION
DASHED LINES INDICATE EXISTING
HOISTWAY VENTS W/FIRE DAMPERS AND
ACCESS PANEL AT TOP OF HOISTWAY
ABOVE. ACCESS PANEL TO BE REMOVED
AND REPLACED WITH 90 MIN RATED
ACCESS DOOR RATED FOR EXTERIOR
ENVIRONMENTS - VERIFY EXISTING SIZE IN
FIELD. HOISTWAY VENTS AND DAMPERS
TO REMAIN
DASHED LINES INDICATE EXISTING HOISTWAY VENTS
W/FIRE DAMPERS AND ACCESS PANEL AT TOP OF
HOISTWAY ABOVE. ACCESS PANEL TO BE REMOVED AND
REPLACED WITH 90 MIN RATED ACCESS DOOR RATED
FOR EXTERIOR ENVIRONMENTS - VERIFY EXISTING SIZE
IN FIELD. HOISTWAY VENTS AND DAMPERS TO REMAIN
A-2.0
A
A
A
EXISTING C.I.P. CONCRETE HOISTWAY
SHAFT ENCLOSURE AND CMU DIVIDER
WALL TO REMAIN, TYP.
EXISTING C.I.P. CONCRETE HOISTWAY
SHAFT ENCLOSURE AND CMU DIVIDER
WALL TO REMAIN, TYP.
EXISTING C.I.P.
CONCRETE
HOISTWAY SHAFT
ENCLOSURE AND
CMU DIVIDER
WALL TO REMAIN,
TYP.
5.19.17Bid Issue SUBMISSION
V
I F
B O
T T
M
I L
T
P
I L
5 1/2" TYP. 5 1/2" TYP.
2" TYP.
V
I F
B O
T T
I L
T
I L
2" TYP.
5 1/2" TYP. 5 1/2" TYP.
7'-9 1/2" +/- VIF 5'-5" +/- VIF
1 2
V
I F
B O
T T
I L
T
I L
5 1/2" TYP.5 1/2" TYP.
2" TYP.
7'-9 1/2" +/- VIF 5'-5" +/- VIF
B O
T T
I L
T
I L
1 2
1'-6" +/-
NEW FRP
F
R P
M A
T C
H
E
X I S
T I N
G
H
T
2'-8"
1" 6" 2'-1"
1"
8"
EMBED
EQ. EQ.
Revisions: Date
5.19.17 CJK DAK
A-2.0
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Construction and Facilities
Management
N
N
S
T
R
U
C
T
I
O
N
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
2.20.1765% CD's SUBMISSION
REFLECTED CEILING PLAN, INTERIOR
ELEVATIONS AND DETAILS
EX.
RECEPTACLE
TO REMAIN
4. WHERE NEW UTILITIES ARE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL
REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME, AND PATCH AND REPAIR
WITH NEW TO MATCH EXISTING CONDITIONS.
GENERAL NOTES:
EXISTING WALLS TO REMAIN
1. CONSIDER ALL AREAS OWNER-OCCUPIED, UNLESS OTHERWISE NOTED.
2. ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN
AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE
REQUIREMENTS OF ALL APPLICABLE CODES.
3. PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING
CONDITIONS.
5. ALL DAMAGE TO EXISTING AREAS OCCURRING AS A RESULT OF CONSTRUCTION SHALL BE
REPAIRED AS REQUIRED BY CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL,
CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL
BE REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO OWNER.
6. ALL NEW PENETRATIONS IN FIRE RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS
REQUIRED.
12. ALL FLOOR, WALL, CEILING, AND MISC. FIRE RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE
OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND / OR AS REQUIRED BY CODE. ALL
EXISTING FIRE RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED.
FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRE STOPPING, FIRE RATED DOORS
AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR
INSPECTION BY THE BUILDING OFFICIAL.
7. CONSTRUCTION ACTIVITIES FOR THIS PROJECT OCCUR WITHIN A STERILE ENVIRONMENT.
CONSTRUCTION AREAS MUST BE PROPERLY SCREENED OFF FROM ALL SURROUNDING AREAS,
WHICH WILL BE OCCUPIED AND IN USE THROUGHOUT THE ENTIRETY OF CONSTRUCTION.
COORDINATE ALL REQUIRED SCREENING AND ISOLATION WITH COR. EXISTING EQUIPMENT IN
ROOMS MUST BE PROTECTED THROUGHOUT CONSTRUCTION, AND ALL CONSTRUCTION ACTIVITIES
IN "CLEAN" SPACES MUST BE PROPERLY ISOLATED FROM THE SURROUNDING SPACES
THROUGHOUT THEIR ENTIRETY. GC SHALL PREPARE AN EQUIPMENT PROTECTION PLAN AND
SUBMIT TO THE COR FOR REVIEW AND APPROVAL. GC SHALL COORDINATE WITH THE COR TO
DETERMINE ALL PROTECTION REQUIREMENTS.
ITEMS TO BE DEMOLISHED
8. CONTRACTOR SHALL PROVIDE DUST REMOVING WALK-OFF MATS (TACKY MAT) AT ALL
CONSTRUCTION ENTRY POINTS
9. DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"
ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS. ALL
DEMOLITION WORK BEING DONEIS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE
TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO
VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
10. THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
11. FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
13. DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING
OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY
REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE
PROJECT AREA.
14. ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S
OPERATIONS AS DETERMINED BY THE COR.
SYMBOL LEGEND:
INDICATES NEW DOOR
INDICATES EXISTING DOOR TO REMAIN
TEMPORARY PARTITION WALL W/3'-0" X 7'-0" FLUSH HM DOOR FOR CONTRACTOR ACCESS
ONLY. WALL AND DOOR TO BE REMOVED UPON COMPLETION OF WORK. PATCH REPAIR
EXISTING CONDITIONS AS REQUIRED UPON REMOVAL OF ALL TEMPORARY CONSTRUCTION.
REFER TO TYPICAL TEMPORARY PARTITION DETAIL ON SHEET A-2.0
EXISTING GYP. BD. CEILINGS
EXISTING ACOUSTIC TILE
CEILINGS
EXISTING 2 HR RATED FIRE
BARRIER ASSEMBLY
1/2"=1'-0"
INTERIOR ELEVATION
ELEVATOR CAB - SIDE
A
A-2.0
1/2"=1'-0"
INTERIOR ELEVATION
ELEVATOR CAB - REAR
B
A-2.0
1/2"=1'-0"
INTERIOR ELEVATION
ELEVATOR CAB - SIDE
C
A-2.0
1/2"=1'-0"
INTERIOR ELEVATION
ELEVATOR CAB - FRONT
D
A-2.0
E X
L
I G
H T
S O
F F
I T
T O
R E
M A
I N
7 7
21 21
1/2"=1'-0"
INTERIOR ELEVATION
ELEVATOR CAB - EXTERIOR
E
A-2.0
2 2
4.14.17100% CD's SUBMISSION
CONSTRUCTION NOTES:
HOISTWAY ENTRANCE SCOPE: EXISTING STAINLESS STEEL ON HOISTWAY DOOR FRAMES TO BE
REMOVED, AND FRAMES SHALL BE RE-CLAD WITH NEW SATIN STAINLESS STEEL - VERIFY DIMENSIONS
IN FIELD. RETAIN EXISTING DOOR OPENER OVERRIDE HOLES IN FACE OF DOOR. HOISTWAY ACCESS
SHALL BE ADDED TO BOTH TERMINAL LANDINGS, MOUNTED IN HOISTWAY JAMBS. EXISTING FASCIA, TOE GUARD, AND DUST COVERS SHALL BE RETAINED. REPLACE ANY MISSING LOCATIONS - VERIFY
SCOPE IN FIELD
EXISTING SILL TO REMAIN AND BE RECLEANED AND POLISHED ONLY. EXISTING SILL SUPPORTS
SHALL BE CLEANED FREE OF DUST.
EXISTING VCT FLOORING IN ELEVATOR CABS TO BE REMOVED ENTIRELY. PREP EXISTING CAB
SUBFLOOR AS REQUIRED TO RECEIVE NEW SHEET VINYL FLOORING WITH HEAT WELDED SEAMS
EXISTING STAINLESS STEEL RAILINGS, STAINLESS STEEL PANELING AND BASE, AND PLASTIC
LAMINATE-FACED WALL PANELS TO BE REMOVED. PROJECT INTENT IS FOR THE ENTIRETY OF
EXISTING INTERIOR WALL FINISHES TO BE REMOVED AND REPLACED WITH NEW - SEE INT. ELEVS.
EXISTING ELEVATOR CONTROLS TO BE REMOVED AND REPLACED - REFER TO SPECIFICATIONS FOR
REPLACEMENT
NOTE: REFER TO SPEC SECTION 14 25 00 "HYDRAULIC ELEVATOR MODERNIZATION" FOR FULL
MODERNIZATION SCOPE. SCOPE DEPICTED BELOW IS LIMITED TO INTERIOR FINISH AND GENERAL LIFE
SAFETY UPGRADES. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
DEMOLITION/IMPROVEMENT SCOPE
NEW 3" W STAINLESS STEEL HANDRAILS, ATTACHED TO NEW STAINLESS STEEL WALL PANEL
ASSEMBLY W/MIN. (4) ATTACHMENTS - MATCH EXISTING PROFILE. SEE ELEVATION FOR INSTALLATION
HEIGHTS
HATCHED AREA INDICATES NEW SATIN STAINLESS STEEL WALL PANELS OVER
PLYWOOD SUBSTRATE. SEE ELEVATION FOR SEAM LOCATION
EXISTING LIGHT SOFFIT ASSEMBLY AND 7" H STAINLESS STEEL END TRIM TO REMAIN, PROTECT AS
REQUIRED THROUGHOUT CONSTRUCTION. NEW LED LIGHTING TO BE PROVIDED
LOCATION OF NEW HORIZONTAL ELEVATOR CONTROL PANEL IN FORMER REMOVED, EXISTING
CONTROL PANEL. VERIFY FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT SHEET AND
COORDINATION SIZE OF WALL OPENING ACCORDINGLY
LOCATION OF NEW VERTICAL ELEVATOR CONTROL PANEL IN FORMER REMOVED, EXISTING CONTROL
PANEL. VERIFY FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT SHEET AND COORDINATION SIZE OF
WALL OPENING ACCORDINGLY
LOCATION OF NEW EMERGENCY PHONE IN FORMER REMOVED, EXISTING PHONE LOCATION. VERIFY
FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT SHEET AND COORDINATION SIZE OF WALL OPENING
ACCORDINGLY
EXISTING STAINLESS STEEL FASCIA ASSEMBLY AND FLOOR INDICATOR UNIT TO BE REMOVED AND
REPLACED WITH NEW. VERIFY FLOOR INDICATOR UNIT WITH SELECTED MANUFACTURER. RECLAD
EXISTING RETURNS WITH NEW SATIN STAINLESS STEEL.
LOCATION OF NEW ELEVATOR CALL BUTTON UNIT IN FORMER REMOVED, LOCATION. GRAPHIC
SHOWN IS OF EXISTING UNIT. REMOVE EXISTING FRP WAINSCOT PANEL IN ITS ENTIRETY AND
FURNISH NEW TO MATCH EXISTING. VERIFY OPENING SIZE FOR NEW CALL BUTTON UNIT IN FIELD
WITH MANUFACTURER'S CUT SHEET AND COORDINATION SIZE OF OPENING ACCORDINGLY. NOTE:
REMOVAL OF FRP PANEL SCOPE OCCURS AT 1ST FLOOR OF CLEAN SIDE ELEVATOR ONLY.
EX. CORNER GUARD TO BE REMOVED AND REINSTALLED UPON INSTALLATION OF NEW FRP PANEL.
NOTE: CLEAN SIDE ELEVATOR SCOPE ONLY
LOCATION OF NEW FLOOR LEVEL INDICATOR PANEL IN FORMER REMOVED, EXISTING LOCATION.
GRAPHIC SHOWN IS OF EXISTING UNIT. VERIFY FINAL SIZE IN FIELD WITH MANUFACTURER'S CUT
SHEET AND COORDINATION SIZE OF WALL OPENING ACCORDINGLY. PATCH EXISTING GYP. BD. AND
REPAINT AS REQUIRED
EXISTING NON-RATED HOLLOW METAL DOOR AND FRAME ASSEMBLY TO BE REMOVED AND REPLACED
WITH NEW 3'-0" X 7'-0", 90 MIN. RATED FLUSH HOLLOW METAL DOOR AND WELDED FRAME. PAINT TO
MATCH EXISTING DOORS. DOOR SHALL BE PROVIDED WITH CLOSER AND DOOR LEVER AND LOCK TO
MATCH EXISTING HARDWARE IN SPACE. COORDINATE KEYING WITH COR. ALL NEW HARDWARE
SHALL BE UL LISTED
HATCHED REGION INDICATES EXISTING 24 x 24 x 9-1/2" D SUMP PIT TO BE INCREASED IN SIZE FOR
NEW SUMP PUMP INSTALLATION. DEMO EXISTING BOTTOM SLAB AND 8" OF PERIMETER SLAB AS
SHOWN. REFER TO SECTION DETAIL FOR PIT MODIFICATION. REFER TO MEP DWGS. FOR SUMP PUMP
INFORMATION
EXISTING STEEL PIT LADDERS TO REMAIN AND BE INCREASED IN DEPTH AWAY FROM WALL WITH NEW
ANGLE ATTACHMENTS. SEE DETAIL
EXISTING UTILITY PENETRATIONS THRU 2-HR RATED HOISTWAY WALL TO BE FIRESTOPPED ON BOTH
SIDES OF WALL - SEE DETAIL
EXISTING CAR DOORS AND HARDWARE TO BE REMOVED AND REPLACED WITH NEW 2-SPEED/SIDE
SLIDE DOORS - SATIN STAINLESS STEEL FINISH. SEE SPECS.
EXISTING HOISTWAY DOORS AND HARDWARE TO BE REMOVED AND REPLACED WITH NEW
2-SPEED/SIDE SLIDE DOORS - SATIN STAINLESS STEEL FINISH. SEE SPECS.
AREA
ACCESSIBLE TO
VA STAFF
CONSTRUCTION
AREA
SCALE: 3/4" = 1'-0"
TYP. TEMP. PARTITION DETAIL
A-2.0
" GYP. BD. BOTH SIDES ON
3-5/8" METAL STUDS @ 24"
O.C.
PAINT AS DIRECTED BY
COR
EXTEND TEMP. PARTITIONS
TO UNDERSIDE OF
EXISTING CEILING - VERIFY
CEILING MATERIALS AND
HEIGHT IN FIELD
1"=1'-0"
SECTION DETAIL
SUMP PIT
A-2.0
EXISTING C.I.P. CONC.
WALL TO REMAIN. CMU
WALL MAY OCCUR, SEE
PLANS
SUMP PUMP AND
FIBERGLASS LINER
BASIN, SEE MEP DWGS.
DASHED LINES INDICATES EX. PIT
CONST. TO BE DEMO'D
STEEL ACCESS LID,
SEE MECH. DWGS.
NEW 6" C.I.P. CONC. WALLS
AND BOTTOM SLAB
#4 X 12" @ 10" O.C.
DRILL INTO EXIST. SLAB
AND GROUT SOLID
USING HILTI HIT HY200
ANCHORAGE SYSTEM
(OR EQUAL), TYP. @
PERIMETER OF PIT
EXISTING SLAB
FORM NOTCH IN TOP
OF CONCRETE FOR
BASIN & LID - VERIFY
FINAL DIMS.
W/SELECTED BASIN
EXISTING AND NEW PIPE PENETRATIONS -
BASIS OF FIRESTOP DESIGN = 2 HR UL
SYSTEM C-AJ-5138 (OR APPROVED EQUAL):
NOTE: SYSTEM SHALL OCCUR ON BOTH
SIDES OF THE CMU WALL. PACK EXISTING
ANNULAR SPACE AROUND PIPE WITH MIN. 4
PCF MINERAL WOOL BATT INSULATION
COMPRESSED TIGHTLY TO DEPTH TO
ACCOMMODATE FIRE SEALANT COVERING -
MIN. DEPTH 3". FIRE SEALANT SHALL BE
INSTALLED TO LEVEL FLUSH W/EXISTING
WALL SURFACE - MIN. DEPTH OF
". SEALANT:
SPECSEAL LCI SEALANT. IF ALTERNATE
SYSTEM IS PROPOSED, EQUAL FIRESTOP
SYSTEM MUST BE SUBMITTED BY GC TO COR
AND ARCHITECT FOR APPROVAL.
EXISTING 2 HR RATED CMU BLOCK WALL.
EXISTING ELEC. CONDUIT PENETRATION - BASIS OF
FIRESTOP DESIGN = 2 HR UL SYSTEM C-AJ-6038 (OR
APPROVED EQUAL):
NOTE: SYSTEM SHALL OCCUR ON BOTH SIDES OF THE
CMU WALL. MIN.
" THK. BAND OF FIRE SEALANT
AROUND PERIMETER OF PENETRANT. BAND SHALL
PROJECT 1" PAST FACE OF ALUM. COMPOSITE SHEET
SYSTEM. NOMINAL
" DIA. BEAD OF FIRE SEALANT
POSITIONED UNDER COMPOSITE SHEET AROUND
ENTIRE PERIMETER SHALL BE PROVIDED. SEALANT:
SPECSEAL LCI SEALANT. COMPOSITE SHEET SYSTEM
SHALL LAP ONTO WALL SURFACE MIN. 2" AND BE
ATTACHED BY MIN.
" DIA. BY 1-1/4" LONG STEEL CONC.
SCREWS IN CONJUNCTION WITH MIN. 1-1/4" DIA. STEEL
FENDER WASHERS. SPACING OF FASTENERS SHALL
NOT EXCEED 6" O.C. SPEC: SPECSEAL CS COMPOSITE
SHEET. IF ALTERNATE SYSTEM IS PROPOSED, EQUAL
FIRESTOP SYSTEM MUST BE SUBMITTED BY GC TO COR
AND ARCHITECT FOR APPROVAL.
DASHED LINES
INDICATE
EXISTING HOLE
IN CMU WALL
SCALE: 1-1/2" = 1'-0"
FIRESTOP DETAIL
A-2.0
3/8" = 1'-0"
REF. CEILING PLAN
PARTIAL FIRST FLOOR & ELEVATOR CAB
"DIRTY"
"CLEAN"
"CLEAN"
"DIRTY"
"CLEAN"
"CLEAN"
CLEAN SIDE
SPD DEPARTMENT
EXISTING
DIRTY SIDE
SPD DEPARTMENT
EXISTING
MACHINE ROOM
ELEVATOR
EXISTING
"CLEAN"
BASE BID: EXISTING METAL CEILINGS,
DIFFUSERS, AND EMERG. LIGHT
FIXTURE TO BE REMOVED. FURNISH
AND INSTALL NEW METAL CAB CEILING,
EXHAUST DIFFUSERS, ACCESS PANEL,
AND EMERGENCY LIGHT FIXTURE.
DEDUCT ALTERNATE #1: EXISTING
METAL CAB CEILING, EXHAUST
DIFFUSERS, ACCESS PANEL, AND
EMERGENCY LIGHT FIXTURE TO
REMAIN. METAL CEILING AND ACCESS
PANEL TO BE REPAINTED.
EXISTING FLUORESCENT TUBE
FIXTURES IN SOFFIT TO BE
REMOVED AND REPLACED WITH
NEW LED SPECS, TYP. BOTH
CABS, ALL SOFFITS. EXISTING
LENS AND STAINLESS STEEL
ENCLOSURE TO REMAIN
TEMPORARY BARRIER REQUIREMENT: REFER TO
MECH. DWGS. FOR NEW PLUMBING ROUTING ABOVE
EXISTING CEILINGS. IN ALL "CLEAN" AREAS,
CONSTRUCTION ACTIVITIES MUST BE FULLY ISOLATED
FROM SURROUNDING SPACES. COORDINATE
REQUIREMENTS WITH COR. WHERE EXISTING GYP. BD.
CEILINGS MUST BE REMOVED TO ROUTE PIPING, GC
SHALL PATCH AND REPAIR WITH NEW GYP. BD. AND
REPAINT WITH MATCHING FINISH
NEW MACHINE ROOM LIGHT TO
REPLACE EXISTING, SEE ELEC.
REPAINT EXISTING
MACHINE ROOM
CEILING
1"=1'-0"
PLAN DETAIL
PIT LADDER
A-2.0
EXISTING RUNGS AND SIDE RAILS TO
REMAIN AND BE REUSED. GC SHALL
PROVIDE FULLY ADHERED NON-SKID
SURFACE TO ALL RUNGS - VERIFY
QUANTITY IN FIELD
EXISTING STEEL BRACKETS SHALL BE
REMOVED, AND NEW LONGER BRACKETS SHALL
BE FURNISHED AND INSTALLED TO INCREASE
THE CENTERLINE DIMENSION SHOWN TO 5"
MINIMUM. WELD BRACKETS TO EXISTING SIDE
RAILS. EXISTING BOLTS AND ATTACHMENT
LOCATIONS TO BE REUSED AND INSTALLED AT
FORMER WALL LOCATIONS. PAINT BRACKETS
TO MATCH LADDER. INCLUDE TEN (10)
BRACKETS PER LADDER IN BID
5" MINIMUM FROM WALL TO
CENTERLINE OF SIDE RAILS SHALL BE
PROVIDED
TYPICAL STAINLESS STEEL
BASE NOTE: VENTILATION
SLOTS SHALL BE PROVIDED -
FINAL LAYOUT TO BE
DETERMINED BY ELEV.
CONTRACTOR
TYPICAL STAINLESS STEEL
BASE NOTE: VENTILATION
SLOTS SHALL BE PROVIDED -
FINAL LAYOUT TO BE
DETERMINED BY ELEV.
CONTRACTOR
NEW VAPOR BARRIER
#4 X 12" @ 10" O.C.
DRILL INTO EXIST. WALL
AND GROUT SOLID
USING HILTI HIT HY200
ANCHORAGE SYSTEM
(OR EQUAL), TYP. @
PERIMETER OF PIT
#4 REBAR, IN BOTH
DIRECTIONS, @ 10" O.C.
#4 REBAR, IN BOTH
DIRECTIONS, @ 10" O.C.
5.19.17Bid Issue SUBMISSION
HVAC NEW WORK GENERAL NOTES
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
5.19.17
2.20.17
4.14.17
5.19.17
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
65% DD SUBMISSION
100% CD SUBMISSION
BID ISSUE SUBMISSION
MECH. GEN. NOTES,
DETAILS, AND SCHEDULES
M0.1
CJS SRP
PLAN NOTES
CODED NOTES
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
5.19.17
2.20.17
4.14.17
5.19.17
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
65% DD SUBMISSION
100% CD SUBMISSION
BID ISSUE SUBMISSION
NEW WORK/DEMO - PARTIAL
FLOOR PLAN - MECHANICAL
M1.1
CJS SRP
DEMOLITON - PARTIAL FIRST FLOOR PLAN - HVAC
NEW WORK - PARTIAL FIRST FLOOR PLAN -HVAC
ABBREVIATION LEGEND FIRE ALARM LEGEND
LIGHTS/SWITCHES LEGEND
POWER LEGEND GENERAL LEGEND
LIGHTING FIXTURE SCHEDULE
ELECTRICAL GENERAL NOTES
CODED NOTES
PARTIAL POWER RISER DIAGRAM
PARTIAL POWER RISER DIAGRAM
NEW WORK
DEMOLITION
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
5.19.17
2.20.17
4.14.17
5.19.17
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
65% DD SUBMISSION
100% CD SUBMISSION
BID ISSUE SUBMISSION
GENERAL NOTES AND
SYMBOL LEGEND
E-0.1
MH MK
PLAN NOTES
CODED NOTES
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
5.19.17
2.20.17
4.14.17
5.19.17
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
65% DD SUBMISSION
100% CD SUBMISSION
BID ISSUE SUBMISSION
DEMO/NEW WORK - PARTIAL
FLOOR PLANS - ELECTRICAL
E-1.1
MH MK
DEMOLITON - PARTIAL FIRST FLOOR PLAN - ELECTRICAL
NEW WORK - PARTIAL FIRST FLOOR PLAN - ELECTRICAL
AutoCAD SHX Text H1M
AutoCAD SHX Text X
AutoCAD SHX Text L1M
AutoCAD SHX Text X
AutoCAD SHX Text
SL1S
AutoCAD SHX Text X
AutoCAD SHX Text
EMDP-1
AutoCAD SHX Text X
AutoCAD SHX Text
TS2
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
MCC-E1
AutoCAD SHX Text X
AutoCAD SHX Text
MCC-N1
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HT
AutoCAD SHX Text
SMP
AutoCAD SHX Text R
AutoCAD SHX Text
TS3
AutoCAD SHX Text X
AutoCAD SHX Text
ATS# 12
AutoCAD SHX Text X
AutoCAD SHX Text
TS1
AutoCAD SHX Text X
AutoCAD SHX Text
T-NAC11
AutoCAD SHX Text X
AutoCAD SHX Text
ATS# 11
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
DPHL11CR1
AutoCAD SHX Text X
AutoCAD SHX Text
EGDP
AutoCAD SHX Text X
AutoCAD SHX Text
HDPA
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
B1PNH1
AutoCAD SHX Text X
AutoCAD SHX Text
UPS
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
DPHL11S1
AutoCAD SHX Text X
AutoCAD SHX Text
ATS 3
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
SMP/ELEV
AutoCAD SHX Text
SMP/ELEV
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
LTG
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 114A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C100D
AutoCAD SHX Text C109A
AutoCAD SHX Text 1C224
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MCC-E1
AutoCAD SHX Text X
AutoCAD SHX Text
MCC-N1
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text H1M
AutoCAD SHX Text X
AutoCAD SHX Text L1M
AutoCAD SHX Text X
AutoCAD SHX Text
SL1S
AutoCAD SHX Text X
AutoCAD SHX Text
EMDP-1
AutoCAD SHX Text X
AutoCAD SHX Text
TS2
AutoCAD SHX Text X
AutoCAD SHX Text
HT
AutoCAD SHX Text
SMP
AutoCAD SHX Text
TS3
AutoCAD SHX Text X
AutoCAD SHX Text
ATS# 12
AutoCAD SHX Text X
AutoCAD SHX Text
TS1
AutoCAD SHX Text X
AutoCAD SHX Text
T-NAC11
AutoCAD SHX Text X
AutoCAD SHX Text
ATS# 11
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
DPHL11CR1
AutoCAD SHX Text X
AutoCAD SHX Text
EGDP
AutoCAD SHX Text X
AutoCAD SHX Text
HDPA
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
B1PNH1
AutoCAD SHX Text X
AutoCAD SHX Text
UPS
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
DPHL11S1
AutoCAD SHX Text X
AutoCAD SHX Text
ATS 3
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GFI
AutoCAD SHX Text W1
AutoCAD SHX Text W1
AutoCAD SHX Text
WP/GFI
AutoCAD SHX Text
WP/GFI
AutoCAD SHX Text W1
AutoCAD SHX Text W1
AutoCAD SHX Text
SMP/ELEV
AutoCAD SHX Text
SMP/ELEV
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
FT/ELEV
AutoCAD SHX Text
SMP/ELEV
AutoCAD SHX Text
FT/ELEV
AutoCAD SHX Text
SMP/ELEV
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
ECU
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
SUMP
AutoCAD SHX Text S1
AutoCAD SHX Text
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
LTG
AutoCAD SHX Text X
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 114A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C100D
AutoCAD SHX Text C109A
AutoCAD SHX Text 1C224
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SE-3
AutoCAD SHX Text
SE-4
AutoCAD SHX Text
TO SE-3
AutoCAD SHX Text
TO ATS# 12
AutoCAD SHX Text
AutoCAD SHX Text V
AutoCAD SHX Text
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
SUMP
AutoCAD SHX Text
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text A. REFER TO E1 FOR ELECTRICAL GENERAL NOTES. B. ELECTRICAL ITEMS SHOWN DASHED AND INDICATED TO BE REMOVED SHALL BE DISCONNECTED AND ALL ASSOCIATED CONDUIT AND WIRING BE REMOVED BACK TO SOURCE OR NEXT DEVICE TO REMAIN. C. FLUSH MOUNTED DEVICES TO BE REMOVED FROM EXISTING WALLS TO REMAIN SHALL HAVE WALL PATCHED AS DIRECTED BY ARCHITECT. D. COORDINATE ELEVATOR EQUIPMENT LAYOUT WITH ELEVATOR EQUIPMENT INSTALLER PRIOR TO FINAL INSTALLATION. E. ALL DEVICES INSTALLED IN ELEVATOR CABINET(S) SHALL BE INSTALLED BY ELEVATOR EQUIPMENT SUPPLIER.
AutoCAD SHX Text
1. DISCONNECT SWITCH TO BE REMOVED. 2. ELEVATOR EQUIPMENT TO BE REMOVED. 3. ELEVATOR PANELBOARD TO REMAIN. 4. EXISTING WALL MOUNTED JUNCTION BOX TO REMAIN. REFER TO ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION. FIELD VERIFY FOR EXACT LOCATION. 5. WALL MOUNTED ENVIRONMENTAL CONDITIONING SYSTEM "ECU-1" WALL MOUNTED ENVIRONMENTAL CONDITIONING SYSTEM "ECU-1" (208V,1PH,0.56FLA). CONNECT TO EXISTING ELEVATOR PANELBOARD. REMOVE (2-20A/1P) SPARE CIRCUIT BREAKERS AND PROVIDE NEW (20A/2P) CIRCUIT BREAKER. MATCH NEW CIRCUIT BREAKER IN EXISTING TYPE MANUFACTURER AND AIC RATING. PROVIDE MANUAL MOTOR STARTER FOR DISCONNECTING MEANS. PROVIDE 2-#12, 1-#12G, 3/4"c FOR HOMERUN AND CIRCUIT BETWEEN MANUAL MOTOR STARTER AND ECU. 6. RECONNECT NEW GFI RECEPTACLE TO EXISTING EMERGENCY BRANCH CIRCUIT. 7. EXISTING ELEVATOR SMOKE DETECTOR TO REMAIN ON FIRST AND SECOND FLOOR. 8. NEW RECEPTACLE. CIRCUIT TO EXISTING ELEVATOR PANELBOARD. PROVIDE NEW (20A/1P) CIRCUIT BREAKER IN EXISTING SPACE. MATCH CIRCUIT BREAKER IN EXISTING TYPE, MANUFACTURER AND AIC RATING. HOMERUN TO EXISTING PANELBOARD WITH 2-#12, 1-#12G, 3/4"C. 9. CONNECT NEW LIGHTING TO RECEPTACLE BRANCH CIRCUIT IN PIT VIA NEW ILLUMINATED WALL SWITCH. 10. SINGLE RECEPTACLE FOR SUMP PUMP TO EXISTING ELEVATOR PANELBOARD. PROVIDE NEW (20A/1P) CIRCUIT BREAKER IN EXISTING SPACE. MATCH CIRCUIT BREAKER IN EXISTING TYPE, MANUFACTURER AND AIC RATING. HOMERUN TO EXISTING PANELBOARD WITH 2-#12, 1-#12G, 3/4"C. 11. ELEVATOR DISCONNECT (60A/50AF/3P/480V). REFER TO ELEVATOR DISCONNECT/SHUNT TRIP WIRING DIAGRAM DETAIL FOR ADDITIONAL FIRE ALARM DEVICES THIS ROOM. 12. SMOKE AND FIXED TEMPERATURE DETECTORS MOUNTED IN BOTH ELEVATOR PIT AND TOP OF SHAFT. REFER TO ELEVATOR RECALL FIRE ALARM RISER FOR MORE INFORMATION. 13. EXISTING EQUIPMENT PANEL TRANSFER SWITCH "ATS-12, ASCO962 WITH BYPASS ISOLATION. ADD FORM "C" CONTACTS AS REQUIRED FOR ELEVATOR PRE-TRANSFER SIGNAL. 14. EXISTING MOTOR CONTROL CENTER. SEE PARTIAL POWER RISER DIAGRAM. 15. CONNECTION FOR ELEVATOR PRE-TRANSFER SIGNAL. COORDINATE CONNECTION WITH ELEVATOR INSTALLER. (TYP. FOR 2). 16. EXISTING UNIT SUBSTATION TO REMAIN. 17. CEILING MOUNTED TRANSFORMER TO REMAIN. 18. INSTALL ILLUMINATED WALL SWITCH BY PIT LADDER.
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HATHAWAY
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E-61777
AutoCAD SHX Text
MARLON
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
DATE
AutoCAD SHX Text 5/19/17
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 6'
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 6'
AutoCAD SHX Text
SCALE
IDENTIFICATION TAGGING DETAILS
(TYPICAL FOR ALL NAMEPLATES)
(REFER TO SPECIFICATIONS)
GENERAL NAMEPLATE DETAIL
TRANSFORMER/SAFETY SWITCH/
BRANCH OVERCURRENT PROTECTIVE
SWITCHBOARD/DISTRIBUTION PANEL/M.C.C./
DISCONNECT SWITCH/MOTOR
DEVICE OR STARTER NAMEPLATE
STARTER NAMEPLATE
VERTICALLY MOUNTED
HORIZONTALLY MOUNTED
TYPICAL DUPLEX RECEPTACLE FACEPLATE
FIRE ALARM WIRING DIAGRAM
ELEVATOR RECALL FIRE ALARM RISER
ADDRESSABLE FIRE ALARM SYSTEM, EQUIP. RM AND SHAFT SPRINKLERED
WALL SECTION
FLOOR SECTION
ELEVATOR DISCONNECT/SHUNT TRIP WIRING DIAGRAM
FIRESTOPPING DETAIL FOR PENETRATIONS
THROUGH FIRE-RATED CONSTRUCTIONS
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
5.19.17
2.20.17
4.14.17
5.19.17
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
VETERAN AFFAIRS MEDICAL CENTER
MODERNIZE SPS ELEVATORS SE-3 AND
SE-4
10701 EAST BLVD. CLEVELAND, OHIO
541-17-507
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
ELEVATOR CONSULTANT:
LERCH BATES
4995 BRADENTON AVE. SUITE 200 DUBLIN, OH 43017
P. 614.210.3909
65% DD SUBMISSION
100% CD SUBMISSION
BID ISSUE SUBMISSION
ELECTRICAL DETAILS
E-2.0
MCH MK
| TITLE SHEET |
| A-1.1 |
| A-2.0 |
| MECHANICAL |
| ELECTRICAL |
| Sheets and Views |
| E-0.1 |
| E-1.1 |
| E-2.0 |
| E-1.1.pdf |
| Sheets and Views |
| E-1.1 |