This document outlines requirements for a federal contract to supply 120,000 pounds of virgin 1,1,1,2 tetrafluoroethane (R-134a) refrigerant to the National Aeronautics and Space Administration Langley Research Center. The refrigerant must meet ARI-700 standards and the supplier must provide certification and safety documentation. Delivery of approximately 40,000 pounds per truck is required for bulk loading into the facility's storage tank on or after September 3, 2021. The supplier must equip trucks with pumps and fittings compatible with the receiving site's connections and be able to balance pressures during pumping. Interested vendors must submit quotes by July 8, 2021 referencing solicitation number 80LARC21Q767612 for consideration under the small business set aside for NAICS code 325120.

View the file

Other files

File Type Posted
RFQ_R134A_Instructions_Terms and Conditions.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIFICATIONS FOR TETRAFLUOROETHANE

Quantity of 120,000lbs Virgin (unused) 1,1,1,2 Tetrafluoroethane (R-134a). R- 134a shall conform to all requirements of the ARI-700 standard for new refrigerants.

The supplier shall provide an ARI-700 Certificate of Analysis for the delivery prior to unloading.

The delivery shall be made by tank trucks (approximately 40,000 pounds) to NASA Langley Research Center, Hampton, VA.

The supplier shall provide all hoses, fittings, pumps, and other equipment to connect to the R-134a storage tank.

The vapor and liquid connections on the storage tank are quick disconnect "E" series coupling, female dry-disconnect coupler, Hydraulics Inc., Part

#CP00110P1G1B.

Supplier shall provide the capability to connect the delivery truck to both the liquid and the vapor side of the Langley storage tank in order to provide the pressure balance needed to pump the delivered liquid R-134a into the storage tank.

The delivery tank-truck shall be equipped with an auxiliary pump. The Langley liquid storage tank, while primarily containing R-134a, may have a low mixture of air in the vapor layer that can contaminate the delivery truck. This can be overcome by using the auxiliary pump on their tractor/tank-truck to pump the delivery trailer to a near vacuum (thus returning the gas mixture back into the Langley storage tank).

The supplier shall provide a weight certificate at the time of delivery, as well as a Material Safety Data Sheet.

The facility will be contacted 24 hours before the delivery to prepare to receive the gas. Contact information will be provided.

Delivery date shall be on or after September 3rd, 2021, and subject to change contingent of prevailing conditions at the facility.