FIRE SUPPRESSION – POST WIDE
10/1/2020-9/30/2021 + 4 OPT YRS.
Table Of Contents.
| 1.0 General Information | 1 | |
| 1.1 | Overview | 1 |
| 2.0 Description of Services | 1 | |
2.1 Scope.
2.2 Fire Alarm/Suppression Systems
2.3 Sprinkler and Hood Suppression Systems
2.4 Special Requirements.
3.0 Work Capabilitiy Levels (Technical Exhibits).
1.0 General Information.
1.1 Overview. The Contractor shall inspect, repair and maintain all existing buildings, structures, and their components listed in real property records and other associated work as directed by the Contracting Officer Representative (COR) or the Contracting Officer (KO). The Contractor shall provide sustainment of vertical facilities such as buildings and all utilities plant structures within the five (5) foot demarcation line, excluding Army Family Housing.
2.0 Description of Services.
2.1 Scope. The Contractor shall provide all certification, labor, equipment, materials and supervision necessary to perform Inspection, Testing and Maintenance (ITM) on fire protection (suppression) and detection systems and ensure appropriate communications with alarm systems located at the United States Military Academy and Reservation, West Point, NY 10996 and Stewart Army Sub-post (STAS) at New Windsor, NY 12553, (see Technical Exhibits), in accordance with the manufacturer's recommendations and Unified Facilities Criteria (UFC) 3-600-02.
The Contractor shall also provide remote offsite monitoring compatible with the fire suppression system at STAS Buildings 107, 108 and 109.
2.2 Fire Alarm/Suppression Systems. (Local requirements).
2.3 Sprinkler and Hood Suppressuin Systems. Sprinkler and Hood Suppression Systems. The Contractor shall perform PM services on sprinkler systems and components listed at TE I IAW the latest edition NFPA 25, Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems and on hood suppression systems listed in TE I IAW the latest edition NFPA 17, Standard for Dry Chemical Extinguishing Systems for dry chemical systems and NFPA 17A, Standard for Wet Chemical Extinguishing Systems for wet fire extinguishing systems. The Contractor shall coordinate with the fire department and perform inspection, maintenance, and testing of fire protection systems. The fire protection systems shall comply with applicable NFPA Codes and TM 5-695, Maintenance of Fire Protection Systems
2.4 Special Requirements.
2.4.1. The Unified Facilities Criteria (UFC 3 -600-02, dated 1 January 2001, (as modified or updated) shall be incorporated in its entirety and shall constitute the scope of work/work statement and shall identify tasks not specifically identified in Contract Section C.5 SPECIFIC TASKS, to be performed under this contract.
2.4.2. The Contractor shall perform “5 year and 2 year” ITM tasks in the base year as stated in the UFC Tables. This will establish an ITM base line.
2.4.3. First option year will encompass those tasks through Annual ITM Service. Other option years will resume ITM tasks as scheduled.
2.4.4. Monthly tasks will be considered part of Annual Service for pricing.
2.4.5. The Contractor shall follow guidance found in the associated NFPA Code for tasks not specifically covered under the UFC. (UFC 1-7.1 and 1.7.2)
2.4.6. The UFC may be accessed on line in PDF format. The online address is: http://www.wbdg.org/ccb/DOD/UFC/ufc_3_600_02.pdf
2.4.7. ALARM SYSTEMS associated with this work statement are located in STAS bldg 108 & 109 and Pershing Center Building 2110 (West Point Museum).
2.4.8. The Contractor shall perform ITM on the Fire Control Instruments (FCI) fire alarm system located in Building 2110, West Point Museum, West Point, NY 10996.
2.4.9. The alarm system in Bldg 2110 (Museum) is included, because the fire alarm and fire suppression systems interact and each system depends on the other for initiation.
2.4.10 Applicable Documents
2.4.10.1 Documents applicable to the services to be performed under this work statement are listed below, and are not intended to be a complete listing.
All documents are mandatory (M) unless noted as Advisory (A)
Unified facilities criteria, UFC 3-600-02
National Fire Protection Association (NFPA): (M)* (M)* Mandatory while performing work beyond the scope of the UFC NFPA 25 Standard for ITM of Water-based Fire Protection Systems NFPA 72 National Fire Alarm Code NFPA 1221 Standard for ITM and Use of emergency Services Communication Systems NFPA 12 Carbon Dioxide Systems NFPA 13 Sprinkler Systems NFPA 17 Dry Chemical Systems NFPA 17A Wet Chemical Systems NFPA 20 Fire Pumps NFPA 96 Commercial Cooking Operations Occupational Safety and Health Act (OSHA) 029 CFR 1910 Corp of Engineers Safety and Health Requirements Manual EM 385-1-1 (Latest edition) Manual of installation, operation and maintenance of the automatic control for engine driven fire pumps published by the King-Knight Company (A) Installation and operating instructions for King-Knight engine driven fire pump control panel Model # FP68d (A) Automatic sprinkler pre-action or deluge sprinkler system (with automatic valve-model c) published by Automatic Sprinkler Corp. Of America (A) Peerless multi-stage pumps – types TMUA & TMUAH published by Peerless Pumps, Indiana (A) Automatic Sprinkler wet pipe sprinkler system (with automatic alarm valve – Model 153 and automatic retarding chamber – Model A-2 automatic valves published by Automatic Sprinkler Corp. Of America (A) Clayton automatic valves instruction manual, published by Cla-Val co, Newport Beach, CA. (A).
3.0 Work Capability Levels (Technical Exhibits).
TECHNICAL EXHIBIT I
SYSTEM LISTING
| Kitchen hood systems |
| Sprinkler systems |
| Co2 systems |
| Fire pumps |
| Building |
| Kitchen hood system |
| Wet, dry, deluge pre-action systems |
| Co2 systems |
| Number of cylinders |
| Electric fire pumps |
| Diesel fire pumps |
| Cylinder removal |
| Back |
Flow Prev.
2-16 2-2, 2-3 2-4, 2-5
(2-14 Water Tank)
Building 107
| Building 108 |
| - |
| 3 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 109 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 140 |
| 2 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 500 |
| 1 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 600 |
| - |
| 2 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 601 |
| - |
| 3 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 602 |
| 2 |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| - |
| Building 603 |
| 2 |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| 1 |
| Building 604 |
| 1 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 606 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 2 |
| Building 607 |
| - |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| - |
Building 609
| Building 613 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 616 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 620 |
| 2 |
| 5 |
| - |
| - |
| 1 |
| - |
| - |
| - |
| Building 621 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 622 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 624 |
| 1 |
| 5 |
| - |
| - |
| 1 |
| - |
| - |
| - |
| Building 626 |
| - |
| 3 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 635 |
| 2 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 646 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 648 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 652 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 654 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 655 |
| 2 |
| 4 |
| - |
| - |
| 1 |
| - |
| - |
| 1 |
| Building 656 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 662 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 664 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 665 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 667 |
| - |
| 5 |
| - |
| - |
| 1 |
| - |
| - |
| 1 |
| Building 673 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 681 |
| - |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| - |
| Building 683 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
Building 687
| Bldg 700B |
| 1 |
| 2 |
| - |
| - |
| 1 |
| - |
| x |
| 2 |
| Building 707 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 708 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 714 |
| 1 |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| 1 |
Building 717A
| Building 718 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 727 |
| - |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| - |
| Building 735 |
| - |
| 1 |
| - |
| - |
| 1 |
| - |
| - |
| 1 |
| Building 738 |
| - |
| 1 |
| - |
| - |
| - |
| 1 |
| - |
| 1 |
| Building 740 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 745 |
| 7 |
| 2 |
| 2 |
| 4 |
| 2 |
| - |
| - |
| 2 |
| Building 747 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Building 751 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 752 |
| - |
| 2 |
| 1 |
| 12 |
| 1 |
| - |
| - |
| 1 |
| Building 756 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
Building 758
| Building 785 |
| - |
| 3 |
| - |
| - |
| - |
| - |
| - |
| - |
Building 793
Building 795
| Building 806 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 2 |
| Building 813 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
Building 854
Building 913
| Building 917 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Building 950 |
| 2 |
| 4 |
| - |
| - |
| - |
| - |
| - |
| 6 |
| Bldg 1200 |
| 1 |
| 2 |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 1202 |
| 5 |
| 2 |
| - |
| - |
| - |
| - |
| - |
| 2 |
| Bldg 1203 |
| 1 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 1204 |
| 2 |
| 4 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Bldg 1207A |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| Bldg 1224 |
| 1 |
| - |
| - |
| - |
| - |
| 1 |
| - |
| - |
| Bldg 1230 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 1534 |
| 1 |
| 1 |
| - |
| - |
| - |
| - |
| X |
| - |
| Bldg 1940 |
| 1 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 1944 |
| - |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 1946 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 1950 |
| 1 |
| - |
| - |
| - |
| - |
| - |
| - |
| - |
| Bldg 2107 |
| - |
| 2 |
| - |
| - |
| - |
| - |
| - |
| 1 |
| TOTAL SYSTEMS |
| 63 |
| 143 |
| 7 |
| 32 |
| 17 |
| 6 |
| 4 |
| 50 |
NOTE: Although every effort has been made to ensure inventory accuracy, the equipment listed in the following Technical Exhibits are to be considered as general information only and may or may not reflect actual conditions or equipment encountered during the performance of this work statement. Equipment differing from this inventory will be considered to be included. Upgrade and renovation projects are ongoing. As systems or system conditions change, they will be incorporated under the intent of this work statement. An example of this might be a system that is currently under warrantee and will be out of warrantee sometime during the period of performance of this contract. Another example of this is the King-Knight controller panel at STAS Bldg 107. Although the controller panel is in place, it is not serving its design function as a system or component controller, but is being utilized as a power source for an associated system.
NOTE: Systems under warrantee will have ITM services performed under this work statement. The obvious distinction is that repair work will not be performed.
TECHNICAL EXHIBIT II
Fire Pump Information Building / Location:
STAS 107
| Storage Tank | | | 200,000 gal. | |
| Storage Tank Cathodic Protection: | Penwalt Model 1087 | | | |
| | | | System #16.962 |
| Backflow Preventer: | | 1 ea Clayton model RP | | |
| Jockey Pump: | | | 1 ea 5HP Peerless Size 1-1/4 | |
| | | | TMUA 4, 26 GPM |
| Deluge Pumps: | | 2 ea Peerless Model 8AF20B | | |
| | | | 2000 GPM |
| Engines: | | | 2 ea Detroit Diesel Model 6061AZ | |
| Fire Pump Controllers | | 2 ea King-Knight Model FP6812PCRD | | |
| Master Controller: | | 1 ea King-Knight Unit #2633 | | |
| Power inverter: | | 1 ea King-Knight Model 26-926 | | |
Battery Charger and Transfer Switch: Goulds Model GRF48S3
STAS 108/109 (Quantities are per building)
| Deluge Valves: | 2 ea Automatic Sprinkler Corp of America | |
| | Model “C,” electrically operated |
| Heat detectors: | 28 ea Notifier Model WPB502 | |
| Sprinkler Heads” | 235 ea. | |
Bldg. 602 Grant Barracks Pump:
Manufacturer: Aurura Model: 481-SF Serial #: 84-66856 Rated GPM: 750 Rated RPM: 1770
Driver:
Electric Manufacturer:
Model:
Serial #:
Rated HP: Rated RPM
Controller:
Manufacturer: Firetrol Serial #: FTA 750-AA30H
Bldg. 603 West Point Club Pump:
| Manufacturer: | Aurora | | | |
| Model or Type: | | 483BF | | |
| Serial Number: | | 97-66-48 | | |
| Rated GPM: | 750 | | Rated RPM: | 1770 |
Driver:
| Electric | | |
| Manufacturer: | | U.S. Motors | |
| Model or Type: | AV DP | | |
| Serial Number: H19252/A08A1890461F | | |
| Rated HP: 25 | | Rated RMP:1760 |
| Electric Drivers: | | Rated Volts:208 |
| Operating Volts: | |
| Rated PL Amps:69 | |
Controller:
| Manufacturer: | | Joslyn Clark |
| Model or Type: | | C8B142-4 |
| Serial Number: | 73452 62-01 | |
Building 607 Lincoln Hall Pump:
| Manufacturer: | | Peerless |
| Model or Type: | | 5AEF8 |
| Serial Number: | | 451357 |
| Rated GPM: | 750 Rated RPM: | 3550 |
Driver:
| Electric: | | |
| Manufacturer: | LincGvard | |
| Model or Type: | 324RS | |
| Serial Number: | 3340012 | |
| Rated HP: 50 | Rated RMP: | 3490 |
| Electric Drivers: | | Rated Volts: | 60 |
| Operating Volts: | 440 | |
| Rated PL Amps: | 60 | |
Controller:
| Manufacturer: | | Joslyn Clark |
| Model or Type: | | 680174-4 |
| Serial Number: | 72442760-1-1 | |
Building 620 1st of First Dorm
Pump:
| Manufacturer: | | Patterson | | |
| Model or Type: | | 4X3ME | | |
| Serial Number: | | FP-69589 | | |
| Rated GPM: | 500 | | Rated RPM: | 1770 |
Driver:
| Electric: | | | |
| Manufacturer: | | U.S. Electric | |
| Model or Type: | | G213A | |
| Serial Number: | | A04A035R122R-13 | |
| Rated HP: | 50 | Rated RPM: | 1775 |
| Electric Drivers: | | Rated Volts: | 460 |
| Operating Volts: | 440 | |
| Rated PL Amps: | 64 | |
Controller:
| Manufacturer: | | Hubbell |
| Model or Type: | | LX1800 |
| Serial Number: | A714118-1-1 | |
Building 624 Meddac Enlisted Dormitory Pump:
| Manufacturer: | | Patterson | | |
| Model or Type: | | 4X3 | | |
| Serial Number: | | FP-C3010 | | |
| Rated GPM: | 500 | | Rated RPM: | 1770 |
Driver:
| Electric | | | | |
| Manufacturer: | | Continental | | |
| Model or Type: | | LF184200C | | |
| Serial Number: | | FRM-258T | | |
| Rated HP: | 20 | | Rated RMP: | 1755 |
| Electric Drivers: | | Rated Volts: | | 460 | |
| Operating Volts: | 440 | | | |
| Rated PL Amps: | 23 | | | |
Controller:
| Manufacturer: | | Hubbell |
| Model or Type: | | LX1800 |
| Serial Number: | A529088-1-1 | |
Bldg. 655 Eisenhower Hall Pump:
Manufacturer: AC Fire Pumps Model: 8100 Serial #: 12-063079-01-01/QKP660 Rated GPM: 1000 Rated RPM: 1765 Driver:
Electric Manufacturer: WEG Model: 050180P3EFP326TS Serial #:
Rated HP: 50 Rated RPM: 1770 Operating volts: 460 Rated APMS: 120 Controller:
Manufacturer: Joslyn Clark Model: G2C174-53RT4 Serial #: 344983
Building 681 Garrison Headquarters Pump:
| Manufacturer: | Fairbanks Morse | |
| Model or Type: | 28230-F | |
| Serial Number: | K4C1-024558 | |
| Rated GPM: 750 | Rated RPM: | 1775 |
Driver:
| Electric: | | | |
| Manufacturer: | | U.S. Motors | |
| Model or Type: | | G215A | |
| Serial Number: | | W07W174R018R-2 | |
| Rated HP: 50 | | Rated RMP: | |
| Electric Drivers: | | Rated Volts: | | 460 |
| Operating Volts: | 440 | | |
| Rated PL Amps: | 64 | | |
Controller:
| Manufacturer: | Firetrol |
| Model or Type: | FTA1800-AB50B |
| Serial Number: | |
Bldg 693 Craft Shop Pump:
Manufacturer: AC Fire Pump Model: 7L83 1580 Serial #: 06-046645-01-01/QKS66 Rated GPM: 500 Rated RPM: 3550 Driver:
Electric Manufacturer: US Electric motors Model: AD23 Serial #: J05 3013066OP H-019 Rated HP: 30 Rated RPM: 3530 Rated Volts: 200/400 Rated AMPS: 80/40 Controller:
Manufacturer: Metron Model: MP435H-30-208C Serial #: MA-06N22559-11
700B Kimsey Athletic Center
| Manufacturer: | | Sterling Peerless Pump |
| Model or Type: | | 6AFF16 |
| Serial Number: | | 573816 |
| Rated GPM: 1250 @ 125psi | Rated RPM: 1780 | |
Driver:
| Electric: | | |
| Manufacturer: | | U.S. Electric Motors |
| Model or Type: | | ADO6A |
| Serial Number: | | 006-ADO6A-H |
| Rated HP: 150 | | Rated RMP: 1785 |
| Electric Drivers: | | Rated Volts: | 460 |
| Operating Volts: | 380 | |
| Rated PL Amps: | 172 | |
Controller:
| Manufacturer: | | Firetrol Inc. |
| Model or Type: | | |
| Serial Number: | FTA1900-AE150B | |
Building 714 Holleder Sports Complex
| Manufacturer: | Aurora Pump | |
| Model or Type: | 481-SF | |
| Serial Number: | 83-66230 | |
| Rated GPM: 1000 | Rated RPM: | 1770 |
Driver:
| Electric: | | | |
| Manufacturer: | | Lincguard | |
| Model or Type: | | 326T | |
| Serial Number: | | 2854608 | |
| Rated HP: 50 | | Rated RMP: | 1770 |
| Electric Drivers: | | Rated Volts: | | 460 |
| Operating Volts: | 480 | | |
| Rated PL Amps: | 62.5 | | |
Controller:
| Manufacturer: | | Sylvania |
| Model or Type: | | C3B174-4F |
| Serial Number: | 391610-1-1 | |
Bldg 727 Arvin Gym Pump:
Manufacturer: Aurora Model: 481BF Serial #: 95-6617 Rated GPM: 2000 Rated RPM: 1770 Driver:
Electric;
Manufacturer: Marathon Model: 1L 445TSTDS7936AN W Serial #: 09180960-10/19-01 Rated HP: 250 Rated RPM: 1780 Operating volts:460 Rated AMPS: 278 Controller;
Manufacturer: Joslyn Clark Model: C4E244-4TBV Serial #: 7298750-1-1
Bldg. 735 Scott Barracks Pump:
| Manufacturer: | | Aurora | | |
| Model or Type: | | 481-BF | | |
| Serial Number: | | | | |
| Rated GPM: | 500 | | Rated RPM: | 3560 |
Driver:
| Diesel: | | | | |
| Manufacturer: | | Marathon | | |
| Model or Type: | | | | |
| Serial Number: | | No Serial Number | | |
| Rated HP: | | Rated RMP: | | 3560 |
| Electric Drivers: | | Rated Volts: | | 440 | |
| Operating Volts: | | | | |
| Rated PL Amps: | 34.5 | | | |
Controller:
| Manufacturer: | | Unknown |
| Model or Type: | | Unknown |
| Serial Number: | Unknown | |
Bldg. 738 Sherman Barracks Pump:
| Manufacturer: | | | Aurora |
| Model or Type: | | | 99-65987 |
| Serial Number: | | | 2565981 |
| Rated GPM: | 750 gpm | Rated RPM: | 1750 |
Driver:
| Diesel: | | |
| Manufacturer: | | Clark Detroit Diesel |
| Model or Type: | | PDFP-L4YN 2500F |
| Serial Number: | | 1108850F |
| Rated HP: 60-67 | Rated RMP: | 1750/2100 | |
| Electric Drivers: | | Rated Volts: | |
| Operating Volts: | | |
| Rated PL Amps: | | |
Controller:
| Manufacturer: | Joslyn Clark Diesel |
| Model or Type: | A10710 |
| Serial Number: | #4018850F |
Bldg. 745 Washington Hall Sprinkler System Fire Pump Pump:
| Manufacturer: | | Aurora | | |
| Model or Type: | | | | |
| Serial Number: | | 9765695-483 BF | | |
| Rated GPM: | 1000 | | Rated RPM: | 3550 |
Driver:
| Electric: | | |
| Manufacturer: | | Marathon |
| Model or Type: | | |
| Serial Number: | | YE364TT05820Ann |
| Rated HP: 75 | | Rated RMP: 3550 |
| Electric Drivers: | | Rated Volts: 480/440 | |
| Operating Volts: | | |
| Rated PL Amps: 184/92 | | |
Controller:
| Manufacturer: | Joslyn Clarke |
| Model or Type: | |
| Serial Number: C8 B 194-473403 364HPVTOS | |
745 Washington Hall Standpipe Fire Pump Pump:
| Manufacturer: | |
| Model or Type: | |
| Serial Number: | |
| Rated GPM: | Rated RPM: |
Driver:
| Electric: | | |
| Manufacturer: | | U.S. Motors |
| Model or Type: | | 445 TS-CW181-0550 |
| Serial Number: | | |
| Rated HP: 250 | | Rated RMP: 1780 |
| Electric Drivers: | | Rated Volts: 480/460 | |
| Operating Volts: | | |
| Rated PL Amps: 284 | | |
Controller:
| Manufacturer: | | Firetrol |
| Model or Type: | | FTA 1000 |
| Serial Number: | AA250B-ACR | |
Bldg. 752 Mahan Hall Pump:
| Manufacturer: | | Patterson |
| Model or Type: | | 5x4M |
| Serial Number: | | #FP-C013173-001 |
| Rated GPM: 750 gpm | Rated RPM: | 1800 |
Driver:
| Electric: | | | |
| Manufacturer: | | Westinghouse | |
| Model or Type: | | 6213A | |
| Serial Number: | | #A06A121R214R-12 | |
| Rated HP: 50 | | Rated RMP: | 1770 |
| Electric Drivers: | | Rated Volts | 230/460: | |
| Operating Volts: | 480 | | |
| Rated PL Amps: | 128 | | |
Controller:
| Manufacturer: | | Hubbell |
| Model or Type: | | LX2200 |
| Serial Number: | A820108-1-1 | |
Bldg. 753N Science Center Pump:
| Manufacturer: | | Patterson Fire Pump | | |
| Model or Type: | | 6x5x17 | | |
| Serial Number: | | FP-C017440-001 | | |
| Rated GPM: | 1000 gpm | | Rated RPM: | 1800 |
Driver:
| Electric: | | | |
| Manufacturer: | | U.S. Electric Motor | |
| Model or Type: | | A SF1.15 | |
| Serial Number: | | 003-5777A-M | |
| Rated HP: 75 | | Rated RMP: | 1775 |
| Electric Drivers: | | Rated Volts: | | 230/460 |
| Operating Volts: | 480 | | |
| Rated PL Amps: 185.4/92.7 | | | |
Controller:
| Manufacturer: | | Master |
| Model or Type: | | ECA-75-46FHJKNO |
| Serial Number: | 82649 | |
Building 758 Thomas Jefferson Library
| Manufacturer: | | Armstrong | | |
| Model or Type: | | series 4600F | | |
| Rated GPM: | 1000 gpm | | Rated RPM: | 3500 |
Driver:
Electric:
Manufacturer: Emerson Model: AC93A Serial #: J03-AC93A-M Rated HP: 100 Rated RPM: 3565 Electric Driver:
| Operating Volts: | 480 (3PH) |
| Rated PL Amps: 185.4/92.7 | |
Controller:
| Manufacturer: | Metron |
| Model or Type MP700 | |
Serial #: MA-06N22607-11
Bldg 1610 TMP pump house
Manufacturer: AC Pumps Model: VIT Serial #: 10-568884-01-01/QKK320 Rated GPM: 1500 Rated RPM: 1770 Driver;
Manufacturer: US Electric Motors Model: H0200S2SLG-C Serial #: R01-30717705-6T-01 Rated HP: 200 Rated RPM: 1775 Rated Volts: 460 Rated AMPS: 225 Controller:
Manufacturer: Metron Model: MP450-200-480C MTS Serial #PA-10N43552-11
Building 2101 Spellman Hall Pump #1
| Manufacturer: | Aurora Pump | |
| Model or Type: | 5-481-15 | |
| Serial Number: | 90N69943 | |
| Rated GPM: 1000 | Rated RPM: | 1750 |
Driver:
| Diesel: | | |
| Manufacturer: | | Caterpillar |
| Model or Type: | | 3208 |
| Serial Number: | | 90N69943 |
| Rated HP: 121 | Rated RMP: | 1750 |
| Electric Drivers: | | Rated Volts: | |
| Operating Volts: | | |
| Rated PL Amps: | | |
Controller:
| Manufacturer: | | Firetrol |
| Model or Type: | | |
| Serial Number: | FTA1100-AA24LN-AA | |
Building 2101 Spellman Hall Pump #2 Pump:
| Manufacturer: | Aurora Pump | |
| Model or Type: | 5-481-18 | |
| Serial Number: | 87-66707 | |
| Rated GPM: 1000 | Rated RPM: | 1750 |
Driver:
| Diesel: | | |
| Manufacturer: | | Caterpillar |
| Model or Type: | | 3208 |
| Serial Number: | | 90N69908 |
| Rated HP: 121 | Rated RMP: | 1750 |
| Electric Drivers: | | Rated Volts: | |
| Operating Volts: | | |
| Rated PL Amps: | | |
Controller:
| Manufacturer: | | Firetrol |
| Model or Type: | | |
| Serial Number: | FTA1100-AA24LN-AA | |
Building 667-B DHPW Pump:
| Manufacturer: | | Aurora | |
| Model or Type: | | 4x481x11l | FP PKG 481BF |
| Serial Number: | | 98-67380 | |
| Rated GPM: 750 | Rated RPM: | 3560 | |
Driver:
| Electric: | | | |
| Manufacturer: | US Electrical Motors | | |
| Model or Type: | | D | |
| Serial Number: | | 304-1000726-016R-10 | |
| Rated HP: 60 | | Rated RMP: | 3545 |
| Electric Drivers: | | Rated Volts: | 230/460 | |
| Operating Volts: | 440/480 | | |
| Rated PL Amps: | 146/73 | | |
Controller:
| Manufacturer: | | Fire Trol |
| Model or Type: | | |
| Serial Number: | FTA1350-AE60B | |
Building 1224 Golf Facilities Pump House
| Manufacturer: | | Armstrong |
| Model or Type: | 4600F | |
| Rated GPM: 1000 | | |
Driver:
| Diesel: |
| Manufacturer: Clarke |
| Model or Type: JU4H-UF30 Serial #: PE4045D471368 |
Rated HP: 60 Rated RPM: 1760 Controller:
| Manufacturer: | Torna |
| Model or Type: GPD | |
Serial #: Z 20506025 1/2
TECHNICAL EXHIBIT IV
West Point Sprinkler Systems
REPLACE WITH THE UPDATED TABLE THAT FOLLOWS
| Bldg. # |
| Building |
| Type of System |
| Alarm Transmitter |
| 140 |
| New CDC |
| Wet Pipe |
| Monaco Radio |
| 500 |
| Youth Activity Center |
| Wet Pipe |
| Monaco Radio |
| 600 |
| Taylor Hall [2] |
| Pre-Action & Wet Pipe |
| Monaco Radio |
| 601 |
| Thayer Hall [3] |
| Wet Pipe |
| Monaco Radio |
| 602 * |
| Grant Barracks |
| Wet Pipe |
| Monaco Radio |
| 603 * |
| West Point Club |
| Wet Pipe |
| Gamewell 249 |
| 604 |
| Power House |
| Pre-Action – Generator |
| Local |
| 606 |
| Cadet Clinics |
| Wet Pipe [Partial] |
| Monaco Radio |
| 607 * |
| Lincoln Hall |
| Wet Pipe |
| Monaco Radio |
| 613 |
| Johnson Stadium |
| Wet Pipe |
| Monaco Radio |
| 616 |
| Stern Law Enforcement Center |
| Wet Pipe |
| Monaco Radio |
| 620 * |
| First of 1st Dorm [2] |
| Wet Pipe & Dry Pipe |
| Gamewell 113 |
| 621 |
| Command Group HQ |
| Wet Pipe |
| Gamewell 138 |
| 624 * |
| Meddac Dorm [2] |
| Wet Pipe & Dry Pipe |
| Gamewell 135 |
| 626 |
| Thomas Hall [3] |
| Wet Pipe |
| Gamewell 136 |
| 635 |
| Cadet 1st Class Club |
| Dry Pipe |
| Monaco Radio |
| 646 |
| Defense Automated Printing Building |
| Wet Pipe |
| Gamewell 137 |
| 648 |
| Auto Craft Shop |
| Wet Pipe |
| Monaco Radio |
| 652 |
| Transit Billeting |
| Wet Pipe [13R] |
| Monaco Radio |
| 654 |
| Transit Billeting |
| Wet Pipe [13R] |
| Monaco Radio |
[4]
| Wet Pipe, Dry Pipe, Deluge |
| Gamewell 324 |
| 656 |
| Transit Billeting |
| Wet Pipe |
| Monaco Radio |
| 662 |
| Transit Billeting |
| Dry Pipe |
| Monaco Radio |
| 664 |
| Transit Billeting |
| Dry Pipe |
| Monaco Radio |
| 665 |
| Rifle/Pistol Range |
| Wet Pipe |
| Monaco Radio |
[4]
| Wet Pipe, Dry Pipe |
| Gamewell 334 |
& 335
| 673 |
| Arvin Annex |
| Dry Pipe – Attic Only |
| Monaco Radio |
| 681 * |
| Garrison HQ |
| Wet Pipe |
| Gamewell 333 |
| 683 |
| MWR Fitness & Education Center |
| Wet Pipe |
| Monaco Radio |
| 700B * |
| Kimsey Athletic Center |
| Wet Pipe |
| Monaco Radio |
| 700C * |
| Hoffman Press Box |
| Dry Pipe |
| Monaco Radio |
| 707 |
| Gross Sports Complex |
| Wet Pipe |
| Monaco Radio |
| 708 |
| Lichtenberg Tennis Center |
| Wet Pipe |
| Monaco Radio |
| 714 * |
| Holleder Center |
| Wet Pipe |
| Monaco Radio |
| 727 * |
| Arvin Gym |
| Wet Pipe |
| Monaco Radio |
| Bldg. # |
| Building |
| Type of System |
| Alarm Transmitter |
| 735 * |
| Scott Barracks |
| Wet Pipe |
| Monaco Radio |
| 738 * |
| Sherman Barracks |
| Wet Pipe |
| Monaco Radio |
| 740 * |
| Lee Barracks |
| Wet Pipe |
| Monaco Radio |
| 745 A/B * |
| Washington Hall |
[2] Wet Pipe & Dry Pipe [Partial Protection] Gamewell 211 & 212
| 747 |
| Nininger Hall |
| Wet Pipe |
| Monaco Radio |
| 751 |
| Pershing Barracks |
| Wet Pipe [Basement only] |
| Gamewell 243 |
[2]
| Wet Pipe & Pre Action [Partial Coverage] |
| Monaco Radio |
| 756 |
| Bradley Barracks |
| Wet Pipe [Basement Only] |
| Gamewell 216 – 219 |
| 757 * |
| Cadet Library [6] |
| Wet Pipe & Pre-Action |
| Gamewell 241 |
| 806 |
| Crew & Sailing Center |
| Wet Pipe |
| Monaco Radio |
| 913 |
| DOL Warehouse |
| Wet Pipe |
| Monaco Radio |
| 917 |
| General Warehouse |
| Wet Pipe |
| Gamewell 437 |
| 1202 |
| Shoppette [2] |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 1203 |
| Fire Station #2 |
| Wet Pipe |
| Monaco Radio |
| 1204 |
| Post Exchange [3] |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 1207 |
| Child Dev Center |
| Wet Pipe |
| Monaco Radio |
| 1207A |
| CDC Annex |
| Dry Pipe |
| Monaco Radio |
| 1585 |
| Camp Buckner Mess |
| Dry Pipe [Seasonal] |
| Monaco Radio |
| 2101 * |
| Spellman Hall [2] |
| Wet Pipe & Pre-Action |
| Monaco Radio |
| 2107 * |
| Visitors Center |
| Wet Pipe & Pre-Action |
| Monaco Radio |
[22]
| Wet Pipe , Dry Pipe, Pre-Action & Deluge |
| Monaco Radio |
* - denotes building has a fire pump supplements domestic pressure for fire protection.
West Point Sprinkler Systems Updated 03/01/09
* Systems with fire pump
| Bldg. # |
| Name |
| Type of System |
| Alarm Transmitter |
| 140 |
| New CDC |
| Wet Pipe |
| Monaco Radio |
| 500 |
| Youth Activity Ctr. |
| Wet Pipe |
| Monaco Radio |
| 600 |
| Taylor Hall |
| Pre-Action & Wet Pipe |
| Monaco Radio |
| 601 |
| Thayer Hall |
| Wet Standpipe Only |
| Monaco Radio |
| 602 * |
| Grant Barracks |
| Wet Pipe |
| Monaco Radio |
| 603 * |
| West Point Club |
| Wet Pipe |
| Monaco Radio |
| 604 |
| Power House |
| Pre-Action – Generator |
| Local |
| 606 |
| Cadet Clinics |
| Wet Pipe [Partial] |
| Monaco Radio |
| 607 * |
| Lincoln Hall |
| Wet Pipe |
| Monaco Radio |
| 609 |
| ODIA Locker Rooms |
| Wet Pipe |
| Monaco Radio |
| 613 |
| Johnson Stadium |
| Wet Pipe |
| Monaco Radio |
| 616 |
| Stern Law Enforcement Center |
| Wet Pipe |
| Monaco Radio |
| 620 * |
| MP Barracks |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 621 |
| Command Group HQ |
| Wet Pipe |
| Monaco Radio |
| 624 * |
| MEDDAC Dorm |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 626 |
| Thomas Hall |
| Wet Pipe |
| Monaco Radio |
| 635 |
| Cadet 1st Class Club |
| Dry Pipe |
| Monaco Radio |
| 646 |
| Denfense Automated Printing Building |
| Wet Pipe |
| Monaco Radio |
| 648 |
| Auto Craft Shop |
| Wet Pipe |
| Monaco Radio |
| 652 |
| Transit Billeting |
| Wet Pipe [13R] |
| Monaco Radio |
| 654 |
| Transit Billeting |
| Wet Pipe [13R] |
| Monaco Radio |
| Wet Pipe, Dry Pipe, Deluge |
| Monaco Radio |
| 656 |
| Transit Billeting |
| Wet Pipe |
| Monaco Radio |
| 662 |
| Transit Billeting |
| Dry Pipe |
| Monaco Radio |
| 664 |
| DES-Fire HQ |
| Dry Pipe |
| Monaco Radio |
| 665 |
| Rifle/Pistol Range |
| Wet Pipe |
| Monaco Radio |
| 667 * |
| DHPW – Engineering Serves 667A & 667B |
| Wet Pipe, Dry Pipe |
| Monaco Radio |
| 673 |
| Arvin Annex |
| Dry Pipe – Out of Service |
| Monaco Radio |
| 681 * |
| Garrison HQ |
| Wet Pipe |
| Monaco Radio |
| 683 |
| MWR Center |
| Wet Pipe |
| Monaco Radio |
| 693 |
| Craft Shop |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 700 |
| East Stands |
| Dry Pipe |
| Monaco Radio |
| 700A * |
| Randle Hall & Bridge |
| Wet Pipe |
| Monaco Radio |
| 700B * |
| Kimsey Athletic Center |
| Wet Pipe |
| Monaco Radio |
| 700C |
| Hoffman Press Box |
| Dry Pipe |
| Monaco Radio |
| Bldg. # |
| Building |
| Type of System |
| Alarm Transmitter |
| 708 |
| Lichtenberg Tennis Center |
| Wet Pipe |
| Monaco Radio |
| 714 * |
| Holleder Center |
| Wet Pipe |
| Monaco Radio |
| 717 A |
| Foley Athletic Center |
| Wet Pipe |
| Monaco Radio |
| 727 * |
| Arvin Gym |
| Wet Pipe & Pre Action [2] |
| Monaco Radio |
| 735 * |
| Scott Barracks |
| Wet Pipe |
| Monaco Radio |
| 738 * |
| Sherman Barracks |
| Wet Pipe |
| Monaco Radio |
| 740 * |
| Lee Barracks |
| Wet Pipe |
| Monaco Radio |
745 *
| Washington Hall |
| Wet Pipe covers basements in A/B/C/D |
Dry Pipe in B Monaco Radio
| 747 |
| Nininger Hall |
| Wet Pipe |
| Monaco Radio |
| 751 |
| Pershing Barracks |
| Wet Pipe [Basement only] |
| Monaco Radio |
| 752* |
| Mahan Hall |
| Wet Pipe, Dry System & Deluge |
| Monaco Radio |
| 753* |
| Science Center |
| Wet Pipe |
| Monaco Radio |
| 756 |
| Bradley Barracks |
| Wet Pipe [Basement Only] |
| Monaco Radio |
| 758 * |
| Thos. Jefferson Library |
| Wet Pipe |
| Monaco Radio |
| 806 |
| Crew & Sailing Center |
| Wet Pipe |
| Monaco Radio |
| 845 |
| Cadet Laundry |
| Wet Pipe |
| Monaco Radio |
| 854 |
| Anderson Rugby |
| Wet Pipe |
| Monaco Radio |
| 913 |
| DOL Warehouse |
| Wet Pipe |
| Monaco Radio |
| 917 |
| General Warehouse |
| Wet Pipe |
| Monaco Radio |
| 950 |
| USMAPS |
| Wet & Dry Pipe |
| Monaco Radio |
| 1202 |
| Shoppette |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 1203 |
| Fire Station #2 |
| Wet Pipe |
| Monaco Radio |
| 1204 |
| Post Exchange |
| Wet Pipe & Dry Pipe |
| Monaco Radio |
| 1207 |
| Child Dev Center |
| Wet Pipe |
| Monaco Radio |
| 1585 |
| Camp Buckner Mess |
| Dry Pipe [Seasonal] |
| Monaco Radio |
| 2101 * |
| Spellman Hall |
| Wet Pipe & Pre-Action |
| Monaco Radio |
| 2107 * |
| Visitors Center |
| Wet Pipe & Pre-Action |
| Monaco Radio |
| Wet Pipe , Dry Pipe, Pre-Action |
| Monaco Radio |
| 108 * |
| Hanger STAS |
| Deluge & Wet Pipe |
| Central Monitor |
| 109 * |
| Hanger STAS |
| Deluge |
| Central Monitor |
| 1610 |
| Pump House |
| Wet Pipe |
| Monaco Radio |
| 1940 |
| TMP Motor Pool |
| Wet Pipe |
| Monaco Radio |
| 1944 |
| Water Treatment |
| Wet Pipe |
| Monaco Radio |
| 1946 |
| TMP Dispatch |
| Wet Pipe |
| Monaco Radio |
TECHNICAL EXHIBIT V
Building 2101 Spellman Hall Fire Protection Systems Information
Computer Center Pre Action Sprinkler System [Monitored by Monaco Fire Alarm Panel] Type: Fire Cycle III [Single Interlock] Modules: M2-12 - Alarm Manufacturer: Viking M2-13 - Trouble Model: E-1 4 inch Valve Type Sprinkler Heads: F1FR Quick Response [Recess Heads] Additional Sprinkler Heads: 6 heads located in south exterior Sprinkler Room System Static Water Pressure = 150psi System Air Pressure = 48psi Location: Sprinkler Riser located in Room G-5 inside Computer Center
· Butterfly valve to shut down this system located on the riser
· Fire Alarm Panel located at the Main Entrance to Computer Center [Key Notifier 17021]
· Manual Override Pull Station to release water into system is located by FACP inside a plastic encasement.
· Air Compressor located on the riser: Compressor set to come on at 45psi and go off at 48psi.
· Heat Detectors for System: 140F Resettable PN22723 Air Compressor: FAST Manufacturing Model: 2LAF-12-M200X
Wet Pipe Sprinkler System Floors G- 5th Main Riser Room: South End of Building Exterior Mechanical Room. This room will shut down entire sprinkler and standpipe feed for the building.
| Monaco Modules: | M3-20 – Flow | |
| | M3-21 – Tamper |
| | M3-22 – Tamper |
| | M3-23 – Tamper |
| | M3-27 – Flow |
| | M3-28 – Tamper |
Ground Floor Room G-19 – Standpipe Isolation Valve @ ceiling level of Metal Storage room south entrance.
[Monaco Modules: M3-15 = Flow M3-26 = Tamper] 1st Floor North Stairwell – Sprinkler Isolation Valve located under the stair.
[Monaco Modules: M4-01 = flow M4-02 = Tamper M4-03 = Tamper] 2nd Floor North Stairwell – Sprinkler Isolation Valve inside stairwell
| Monaco Modules: | M4-07 = Flow | |
| | M4-08 = Tamper |
3rd Floor North Stairwell – Sprinkler Isolation Valve inside stairwell
| Monaco Modules: | M4-09 = Flow | |
| | M4-10 = Tamper |
4th Floor North Stairwell – Sprinkler Isolation Valve inside stairwell Monaco Modules: M4-12 = Flow M4-13 = Tamper 5th Floor North Stairwell – Sprinkler Isolation Valve inside stairwell Monaco Modules: M4-15 = Flow M4-16 = Tamper Hydraulic Plate for Sprinkler located at each Riser in the stairwells at each floor.
Fire Department Connection - Combination Auto Sprinkler & Standpipe – South Mechanical Room *System is connected to Fire Pumps in North Exterior Mechanical Room