FIRE SUPPRESSION INSPECTION TESTING AND MAINTENANCE
Solicitation number
W911SD20R0053
Issued by

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment

FIRE SUPPRESSION – POST WIDE

10/1/2020-9/30/2021 + 4 OPT YRS.

Table Of Contents.

1.0 General Information1
1.1Overview1
2.0 Description of Services1

2.1 Scope.

2.2 Fire Alarm/Suppression Systems

2.3 Sprinkler and Hood Suppression Systems

2.4 Special Requirements.

3.0 Work Capabilitiy Levels (Technical Exhibits).

1.0 General Information.

1.1 Overview. The Contractor shall inspect, repair and maintain all existing buildings, structures, and their components listed in real property records and other associated work as directed by the Contracting Officer Representative (COR) or the Contracting Officer (KO). The Contractor shall provide sustainment of vertical facilities such as buildings and all utilities plant structures within the five (5) foot demarcation line, excluding Army Family Housing.

2.0 Description of Services.

2.1 Scope. The Contractor shall provide all certification, labor, equipment, materials and supervision necessary to perform Inspection, Testing and Maintenance (ITM) on fire protection (suppression) and detection systems and ensure appropriate communications with alarm systems located at the United States Military Academy and Reservation, West Point, NY 10996 and Stewart Army Sub-post (STAS) at New Windsor, NY 12553, (see Technical Exhibits), in accordance with the manufacturer's recommendations and Unified Facilities Criteria (UFC) 3-600-02.

The Contractor shall also provide remote offsite monitoring compatible with the fire suppression system at STAS Buildings 107, 108 and 109.

2.2 Fire Alarm/Suppression Systems. (Local requirements).

2.3 Sprinkler and Hood Suppressuin Systems. Sprinkler and Hood Suppression Systems. The Contractor shall perform PM services on sprinkler systems and components listed at TE I IAW the latest edition NFPA 25, Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems and on hood suppression systems listed in TE I IAW the latest edition NFPA 17, Standard for Dry Chemical Extinguishing Systems for dry chemical systems and NFPA 17A, Standard for Wet Chemical Extinguishing Systems for wet fire extinguishing systems. The Contractor shall coordinate with the fire department and perform inspection, maintenance, and testing of fire protection systems. The fire protection systems shall comply with applicable NFPA Codes and TM 5-695, Maintenance of Fire Protection Systems

2.4 Special Requirements.

2.4.1. The Unified Facilities Criteria (UFC 3 -600-02, dated 1 January 2001, (as modified or updated) shall be incorporated in its entirety and shall constitute the scope of work/work statement and shall identify tasks not specifically identified in Contract Section C.5 SPECIFIC TASKS, to be performed under this contract.

2.4.2. The Contractor shall perform “5 year and 2 year” ITM tasks in the base year as stated in the UFC Tables. This will establish an ITM base line.

2.4.3. First option year will encompass those tasks through Annual ITM Service. Other option years will resume ITM tasks as scheduled.

2.4.4. Monthly tasks will be considered part of Annual Service for pricing.

2.4.5. The Contractor shall follow guidance found in the associated NFPA Code for tasks not specifically covered under the UFC. (UFC 1-7.1 and 1.7.2)

2.4.6. The UFC may be accessed on line in PDF format. The online address is: http://www.wbdg.org/ccb/DOD/UFC/ufc_3_600_02.pdf

2.4.7. ALARM SYSTEMS associated with this work statement are located in STAS bldg 108 & 109 and Pershing Center Building 2110 (West Point Museum).

2.4.8. The Contractor shall perform ITM on the Fire Control Instruments (FCI) fire alarm system located in Building 2110, West Point Museum, West Point, NY 10996.

2.4.9. The alarm system in Bldg 2110 (Museum) is included, because the fire alarm and fire suppression systems interact and each system depends on the other for initiation.

2.4.10 Applicable Documents

2.4.10.1 Documents applicable to the services to be performed under this work statement are listed below, and are not intended to be a complete listing.

All documents are mandatory (M) unless noted as Advisory (A)

Unified facilities criteria, UFC 3-600-02

National Fire Protection Association (NFPA): (M)* (M)* Mandatory while performing work beyond the scope of the UFC NFPA 25 Standard for ITM of Water-based Fire Protection Systems NFPA 72 National Fire Alarm Code NFPA 1221 Standard for ITM and Use of emergency Services Communication Systems NFPA 12 Carbon Dioxide Systems NFPA 13 Sprinkler Systems NFPA 17 Dry Chemical Systems NFPA 17A Wet Chemical Systems NFPA 20 Fire Pumps NFPA 96 Commercial Cooking Operations Occupational Safety and Health Act (OSHA) 029 CFR 1910 Corp of Engineers Safety and Health Requirements Manual EM 385-1-1 (Latest edition) Manual of installation, operation and maintenance of the automatic control for engine driven fire pumps published by the King-Knight Company (A) Installation and operating instructions for King-Knight engine driven fire pump control panel Model # FP68d (A) Automatic sprinkler pre-action or deluge sprinkler system (with automatic valve-model c) published by Automatic Sprinkler Corp. Of America (A) Peerless multi-stage pumps – types TMUA & TMUAH published by Peerless Pumps, Indiana (A) Automatic Sprinkler wet pipe sprinkler system (with automatic alarm valve – Model 153 and automatic retarding chamber – Model A-2 automatic valves published by Automatic Sprinkler Corp. Of America (A) Clayton automatic valves instruction manual, published by Cla-Val co, Newport Beach, CA. (A).

3.0 Work Capability Levels (Technical Exhibits).

TECHNICAL EXHIBIT I

SYSTEM LISTING

Kitchen hood systems
Sprinkler systems
Co2 systems
Fire pumps
Building
Kitchen hood system
Wet, dry, deluge pre-action systems
Co2 systems
Number of cylinders
Electric fire pumps
Diesel fire pumps
Cylinder removal
Back

Flow Prev.

UFC Table
2-15

2-16 2-2, 2-3 2-4, 2-5

2-19
N/A
2-13
2-13

(2-14 Water Tank)

N/A
Approx

Building 107

Building 108
-
3
-
-
-
-
-
-
Building 109
-
1
-
-
-
-
-
-
Building 140
2
1
-
-
-
-
-
1
Building 500
1
1
-
-
-
-
-
1
Building 600
-
2
-
-
-
-
-
-
Building 601
-
3
-
-
-
-
-
-
Building 602
2
1
-
-
1
-
-
-
Building 603
2
1
-
-
1
-
-
1
Building 604
1
1
-
-
-
-
-
-
Building 606
-
1
-
-
-
-
-
2
Building 607
-
1
-
-
1
-
-
-

Building 609

Building 613
-
1
-
-
-
-
-
-
Building 616
-
1
-
-
-
-
-
-
Building 620
2
5
-
-
1
-
-
-
Building 621
-
1
-
-
-
-
-
-
Building 622
1
-
-
-
-
-
-
-
Building 624
1
5
-
-
1
-
-
-
Building 626
-
3
-
-
-
-
-
-
Building 635
2
1
-
-
-
-
-
1
Building 646
-
1
-
-
-
-
-
-
Building 648
-
1
-
-
-
-
-
-
Building 652
-
1
-
-
-
-
-
1
Building 654
-
1
-
-
-
-
-
1
Building 655
2
4
-
-
1
-
-
1
Building 656
-
1
-
-
-
-
-
1
Building 662
-
1
-
-
-
-
-
1
Building 664
-
1
-
-
-
-
-
1
Building 665
-
1
-
-
-
-
-
1
Building 667
-
5
-
-
1
-
-
1
Building 673
-
1
-
-
-
-
-
-
Building 681
-
1
-
-
1
-
-
-
Building 683
-
1
-
-
-
-
-
-

Building 687

Building 693
1
2
Building 700A
2
Bldg 700B
1
2
-
-
1
-
x
2
Building 707
-
1
-
-
-
-
-
1
Building 708
-
1
-
-
-
-
-
1
Building 714
1
1
-
-
1
-
-
1

Building 717A

Building 718
1
-
-
-
-
-
-
-
Building 721
1
Building 727
-
1
-
-
1
-
-
-
Building 735
-
1
-
-
1
-
-
1
Building 738
-
1
-
-
-
1
-
1
Building 740
-
1
-
-
-
-
-
-
Building 745
7
2
2
4
2
-
-
2
Building 747
-
1
-
-
-
-
-
1
Building 750
1
Building 751
-
1
-
-
-
-
-
-
Building 752
-
2
1
12
1
-
-
1
Building 753
-
3
1
-
-
1
Building 756
-
1
-
-
-
-
-
-

Building 758

Building 785
-
3
-
-
-
-
-
-

Building 793

Building 795

Building 806
-
1
-
-
-
-
-
2
Building 813
-
1
-
-
-
-
-
-

Building 854

Building 905
1

Building 913

Building 917
-
1
-
-
-
-
-
-
Building 950
2
4
-
-
-
-
-
6
Bldg 1200
1
2
-
-
-
-
-
-
Bldg 1202
5
2
-
-
-
-
-
2
Bldg 1203
1
1
-
-
-
-
-
-
Bldg 1204
2
4
-
-
-
-
-
1
Bldg 1207
1
1
-
-
-
-
-
Bldg 1207A
-
1
-
-
-
-
-
1
Bldg 1224
1
-
-
-
-
1
-
-
Bldg 1230
1
-
-
-
-
-
-
-
Bldg 1534
1
1
-
-
-
-
X
-
Bldg 1940
1
1
-
-
-
-
-
-
Bldg 1944
-
1
-
-
-
-
-
-
Bldg 1946
1
-
-
-
-
-
-
-
Bldg 1950
1
-
-
-
-
-
-
-
Bldg 1585
2
1
-
-
-
-
X
Bldg 1701
4
-
-
-
-
-
X
Bldg 2101
-
2
1
4
-
2
-
Bldg 2107
-
2
-
-
-
-
-
1
Bldg 2110
-
22
-
-
-
-
-
TOTAL SYSTEMS
63
143
7
32
17
6
4
50

NOTE: Although every effort has been made to ensure inventory accuracy, the equipment listed in the following Technical Exhibits are to be considered as general information only and may or may not reflect actual conditions or equipment encountered during the performance of this work statement. Equipment differing from this inventory will be considered to be included. Upgrade and renovation projects are ongoing. As systems or system conditions change, they will be incorporated under the intent of this work statement. An example of this might be a system that is currently under warrantee and will be out of warrantee sometime during the period of performance of this contract. Another example of this is the King-Knight controller panel at STAS Bldg 107. Although the controller panel is in place, it is not serving its design function as a system or component controller, but is being utilized as a power source for an associated system.

NOTE: Systems under warrantee will have ITM services performed under this work statement. The obvious distinction is that repair work will not be performed.

TECHNICAL EXHIBIT II

Fire Pump Information Building / Location:

STAS 107

Storage Tank200,000 gal.
Storage Tank Cathodic Protection:Penwalt Model 1087
System #16.962
Backflow Preventer:1 ea Clayton model RP
Jockey Pump:1 ea 5HP Peerless Size 1-1/4
TMUA 4, 26 GPM
Deluge Pumps:2 ea Peerless Model 8AF20B
2000 GPM
Engines:2 ea Detroit Diesel Model 6061AZ
Fire Pump Controllers2 ea King-Knight Model FP6812PCRD
Master Controller:1 ea King-Knight Unit #2633
Power inverter:1 ea King-Knight Model 26-926

Battery Charger and Transfer Switch: Goulds Model GRF48S3

STAS 108/109 (Quantities are per building)

Deluge Valves:2 ea Automatic Sprinkler Corp of America
Model “C,” electrically operated
Heat detectors:28 ea Notifier Model WPB502
Sprinkler Heads”235 ea.

Bldg. 602 Grant Barracks Pump:

Manufacturer: Aurura Model: 481-SF Serial #: 84-66856 Rated GPM: 750 Rated RPM: 1770

Driver:

Electric Manufacturer:

Model:

Serial #:

Rated HP: Rated RPM

Controller:

Manufacturer: Firetrol Serial #: FTA 750-AA30H

Bldg. 603 West Point Club Pump:

Manufacturer:Aurora
Model or Type:483BF
Serial Number:97-66-48
Rated GPM:750Rated RPM:1770

Driver:

Electric
Manufacturer:U.S. Motors
Model or Type:AV DP
Serial Number: H19252/A08A1890461F
Rated HP: 25Rated RMP:1760
Electric Drivers:Rated Volts:208
Operating Volts:
Rated PL Amps:69

Controller:

Manufacturer:Joslyn Clark
Model or Type:C8B142-4
Serial Number:73452 62-01

Building 607 Lincoln Hall Pump:

Manufacturer:Peerless
Model or Type:5AEF8
Serial Number:451357
Rated GPM:750 Rated RPM:3550

Driver:

Electric:
Manufacturer:LincGvard
Model or Type:324RS
Serial Number:3340012
Rated HP: 50Rated RMP:3490
Electric Drivers:Rated Volts:60
Operating Volts:440
Rated PL Amps:60

Controller:

Manufacturer:Joslyn Clark
Model or Type:680174-4
Serial Number:72442760-1-1

Building 620 1st of First Dorm

Pump:

Manufacturer:Patterson
Model or Type:4X3ME
Serial Number:FP-69589
Rated GPM:500Rated RPM:1770

Driver:

Electric:
Manufacturer:U.S. Electric
Model or Type:G213A
Serial Number:A04A035R122R-13
Rated HP:50Rated RPM:1775
Electric Drivers:Rated Volts:460
Operating Volts:440
Rated PL Amps:64

Controller:

Manufacturer:Hubbell
Model or Type:LX1800
Serial Number:A714118-1-1

Building 624 Meddac Enlisted Dormitory Pump:

Manufacturer:Patterson
Model or Type:4X3
Serial Number:FP-C3010
Rated GPM:500Rated RPM:1770

Driver:

Electric
Manufacturer:Continental
Model or Type:LF184200C
Serial Number:FRM-258T
Rated HP:20Rated RMP:1755
Electric Drivers:Rated Volts:460
Operating Volts:440
Rated PL Amps:23

Controller:

Manufacturer:Hubbell
Model or Type:LX1800
Serial Number:A529088-1-1

Bldg. 655 Eisenhower Hall Pump:

Manufacturer: AC Fire Pumps Model: 8100 Serial #: 12-063079-01-01/QKP660 Rated GPM: 1000 Rated RPM: 1765 Driver:

Electric Manufacturer: WEG Model: 050180P3EFP326TS Serial #:

Rated HP: 50 Rated RPM: 1770 Operating volts: 460 Rated APMS: 120 Controller:

Manufacturer: Joslyn Clark Model: G2C174-53RT4 Serial #: 344983

Building 681 Garrison Headquarters Pump:

Manufacturer:Fairbanks Morse
Model or Type:28230-F
Serial Number:K4C1-024558
Rated GPM: 750Rated RPM:1775

Driver:

Electric:
Manufacturer:U.S. Motors
Model or Type:G215A
Serial Number:W07W174R018R-2
Rated HP: 50Rated RMP:
Electric Drivers:Rated Volts:460
Operating Volts:440
Rated PL Amps:64

Controller:

Manufacturer:Firetrol
Model or Type:FTA1800-AB50B
Serial Number:

Bldg 693 Craft Shop Pump:

Manufacturer: AC Fire Pump Model: 7L83 1580 Serial #: 06-046645-01-01/QKS66 Rated GPM: 500 Rated RPM: 3550 Driver:

Electric Manufacturer: US Electric motors Model: AD23 Serial #: J05 3013066OP H-019 Rated HP: 30 Rated RPM: 3530 Rated Volts: 200/400 Rated AMPS: 80/40 Controller:

Manufacturer: Metron Model: MP435H-30-208C Serial #: MA-06N22559-11

700B Kimsey Athletic Center

Manufacturer:Sterling Peerless Pump
Model or Type:6AFF16
Serial Number:573816
Rated GPM: 1250 @ 125psiRated RPM: 1780

Driver:

Electric:
Manufacturer:U.S. Electric Motors
Model or Type:ADO6A
Serial Number:006-ADO6A-H
Rated HP: 150Rated RMP: 1785
Electric Drivers:Rated Volts:460
Operating Volts:380
Rated PL Amps:172

Controller:

Manufacturer:Firetrol Inc.
Model or Type:
Serial Number:FTA1900-AE150B

Building 714 Holleder Sports Complex

Manufacturer:Aurora Pump
Model or Type:481-SF
Serial Number:83-66230
Rated GPM: 1000Rated RPM:1770

Driver:

Electric:
Manufacturer:Lincguard
Model or Type:326T
Serial Number:2854608
Rated HP: 50Rated RMP:1770
Electric Drivers:Rated Volts:460
Operating Volts:480
Rated PL Amps:62.5

Controller:

Manufacturer:Sylvania
Model or Type:C3B174-4F
Serial Number:391610-1-1

Bldg 727 Arvin Gym Pump:

Manufacturer: Aurora Model: 481BF Serial #: 95-6617 Rated GPM: 2000 Rated RPM: 1770 Driver:

Electric;

Manufacturer: Marathon Model: 1L 445TSTDS7936AN W Serial #: 09180960-10/19-01 Rated HP: 250 Rated RPM: 1780 Operating volts:460 Rated AMPS: 278 Controller;

Manufacturer: Joslyn Clark Model: C4E244-4TBV Serial #: 7298750-1-1

Bldg. 735 Scott Barracks Pump:

Manufacturer:Aurora
Model or Type:481-BF
Serial Number:
Rated GPM:500Rated RPM:3560

Driver:

Diesel:
Manufacturer:Marathon
Model or Type:
Serial Number:No Serial Number
Rated HP:Rated RMP:3560
Electric Drivers:Rated Volts:440
Operating Volts:
Rated PL Amps:34.5

Controller:

Manufacturer:Unknown
Model or Type:Unknown
Serial Number:Unknown

Bldg. 738 Sherman Barracks Pump:

Manufacturer:Aurora
Model or Type:99-65987
Serial Number:2565981
Rated GPM:750 gpmRated RPM:1750

Driver:

Diesel:
Manufacturer:Clark Detroit Diesel
Model or Type:PDFP-L4YN 2500F
Serial Number:1108850F
Rated HP: 60-67Rated RMP:1750/2100
Electric Drivers:Rated Volts:
Operating Volts:
Rated PL Amps:

Controller:

Manufacturer:Joslyn Clark Diesel
Model or Type:A10710
Serial Number:#4018850F

Bldg. 745 Washington Hall Sprinkler System Fire Pump Pump:

Manufacturer:Aurora
Model or Type:
Serial Number:9765695-483 BF
Rated GPM:1000Rated RPM:3550

Driver:

Electric:
Manufacturer:Marathon
Model or Type:
Serial Number:YE364TT05820Ann
Rated HP: 75Rated RMP: 3550
Electric Drivers:Rated Volts: 480/440
Operating Volts:
Rated PL Amps: 184/92

Controller:

Manufacturer:Joslyn Clarke
Model or Type:
Serial Number: C8 B 194-473403 364HPVTOS

745 Washington Hall Standpipe Fire Pump Pump:

Manufacturer:
Model or Type:
Serial Number:
Rated GPM:Rated RPM:

Driver:

Electric:
Manufacturer:U.S. Motors
Model or Type:445 TS-CW181-0550
Serial Number:
Rated HP: 250Rated RMP: 1780
Electric Drivers:Rated Volts: 480/460
Operating Volts:
Rated PL Amps: 284

Controller:

Manufacturer:Firetrol
Model or Type:FTA 1000
Serial Number:AA250B-ACR

Bldg. 752 Mahan Hall Pump:

Manufacturer:Patterson
Model or Type:5x4M
Serial Number:#FP-C013173-001
Rated GPM: 750 gpmRated RPM:1800

Driver:

Electric:
Manufacturer:Westinghouse
Model or Type:6213A
Serial Number:#A06A121R214R-12
Rated HP: 50Rated RMP:1770
Electric Drivers:Rated Volts230/460:
Operating Volts:480
Rated PL Amps:128

Controller:

Manufacturer:Hubbell
Model or Type:LX2200
Serial Number:A820108-1-1

Bldg. 753N Science Center Pump:

Manufacturer:Patterson Fire Pump
Model or Type:6x5x17
Serial Number:FP-C017440-001
Rated GPM:1000 gpmRated RPM:1800

Driver:

Electric:
Manufacturer:U.S. Electric Motor
Model or Type:A SF1.15
Serial Number:003-5777A-M
Rated HP: 75Rated RMP:1775
Electric Drivers:Rated Volts:230/460
Operating Volts:480
Rated PL Amps: 185.4/92.7

Controller:

Manufacturer:Master
Model or Type:ECA-75-46FHJKNO
Serial Number:82649

Building 758 Thomas Jefferson Library

Manufacturer:Armstrong
Model or Type:series 4600F
Rated GPM:1000 gpmRated RPM:3500

Driver:

Electric:

Manufacturer: Emerson Model: AC93A Serial #: J03-AC93A-M Rated HP: 100 Rated RPM: 3565 Electric Driver:

Operating Volts:480 (3PH)
Rated PL Amps: 185.4/92.7

Controller:

Manufacturer:Metron
Model or Type MP700

Serial #: MA-06N22607-11

Bldg 1610 TMP pump house

Manufacturer: AC Pumps Model: VIT Serial #: 10-568884-01-01/QKK320 Rated GPM: 1500 Rated RPM: 1770 Driver;

Manufacturer: US Electric Motors Model: H0200S2SLG-C Serial #: R01-30717705-6T-01 Rated HP: 200 Rated RPM: 1775 Rated Volts: 460 Rated AMPS: 225 Controller:

Manufacturer: Metron Model: MP450-200-480C MTS Serial #PA-10N43552-11

Building 2101 Spellman Hall Pump #1

Manufacturer:Aurora Pump
Model or Type:5-481-15
Serial Number:90N69943
Rated GPM: 1000Rated RPM:1750

Driver:

Diesel:
Manufacturer:Caterpillar
Model or Type:3208
Serial Number:90N69943
Rated HP: 121Rated RMP:1750
Electric Drivers:Rated Volts:
Operating Volts:
Rated PL Amps:

Controller:

Manufacturer:Firetrol
Model or Type:
Serial Number:FTA1100-AA24LN-AA

Building 2101 Spellman Hall Pump #2 Pump:

Manufacturer:Aurora Pump
Model or Type:5-481-18
Serial Number:87-66707
Rated GPM: 1000Rated RPM:1750

Driver:

Diesel:
Manufacturer:Caterpillar
Model or Type:3208
Serial Number:90N69908
Rated HP: 121Rated RMP:1750
Electric Drivers:Rated Volts:
Operating Volts:
Rated PL Amps:

Controller:

Manufacturer:Firetrol
Model or Type:
Serial Number:FTA1100-AA24LN-AA

Building 667-B DHPW Pump:

Manufacturer:Aurora
Model or Type:4x481x11lFP PKG 481BF
Serial Number:98-67380
Rated GPM: 750Rated RPM:3560

Driver:

Electric:
Manufacturer:US Electrical Motors
Model or Type:D
Serial Number:304-1000726-016R-10
Rated HP: 60Rated RMP:3545
Electric Drivers:Rated Volts:230/460
Operating Volts:440/480
Rated PL Amps:146/73

Controller:

Manufacturer:Fire Trol
Model or Type:
Serial Number:FTA1350-AE60B

Building 1224 Golf Facilities Pump House

Manufacturer:Armstrong
Model or Type:4600F
Rated GPM: 1000

Driver:

Diesel:
Manufacturer: Clarke
Model or Type: JU4H-UF30 Serial #: PE4045D471368

Rated HP: 60 Rated RPM: 1760 Controller:

Manufacturer:Torna
Model or Type: GPD

Serial #: Z 20506025 1/2

TECHNICAL EXHIBIT IV

West Point Sprinkler Systems

REPLACE WITH THE UPDATED TABLE THAT FOLLOWS

Bldg. #
Building
Type of System
Alarm Transmitter
140
New CDC
Wet Pipe
Monaco Radio
500
Youth Activity Center
Wet Pipe
Monaco Radio
600
Taylor Hall [2]
Pre-Action & Wet Pipe
Monaco Radio
601
Thayer Hall [3]
Wet Pipe
Monaco Radio
602 *
Grant Barracks
Wet Pipe
Monaco Radio
603 *
West Point Club
Wet Pipe
Gamewell 249
604
Power House
Pre-Action – Generator
Local
606
Cadet Clinics
Wet Pipe [Partial]
Monaco Radio
607 *
Lincoln Hall
Wet Pipe
Monaco Radio
613
Johnson Stadium
Wet Pipe
Monaco Radio
616
Stern Law Enforcement Center
Wet Pipe
Monaco Radio
620 *
First of 1st Dorm [2]
Wet Pipe & Dry Pipe
Gamewell 113
621
Command Group HQ
Wet Pipe
Gamewell 138
624 *
Meddac Dorm [2]
Wet Pipe & Dry Pipe
Gamewell 135
626
Thomas Hall [3]
Wet Pipe
Gamewell 136
635
Cadet 1st Class Club
Dry Pipe
Monaco Radio
646
Defense Automated Printing Building
Wet Pipe
Gamewell 137
648
Auto Craft Shop
Wet Pipe
Monaco Radio
652
Transit Billeting
Wet Pipe [13R]
Monaco Radio
654
Transit Billeting
Wet Pipe [13R]
Monaco Radio
655
Eisenhower Hall

[4]

Wet Pipe, Dry Pipe, Deluge
Gamewell 324
656
Transit Billeting
Wet Pipe
Monaco Radio
662
Transit Billeting
Dry Pipe
Monaco Radio
664
Transit Billeting
Dry Pipe
Monaco Radio
665
Rifle/Pistol Range
Wet Pipe
Monaco Radio
667 *
DHPW A & B

[4]

Wet Pipe, Dry Pipe
Gamewell 334

& 335

673
Arvin Annex
Dry Pipe – Attic Only
Monaco Radio
681 *
Garrison HQ
Wet Pipe
Gamewell 333
683
MWR Fitness & Education Center
Wet Pipe
Monaco Radio
700B *
Kimsey Athletic Center
Wet Pipe
Monaco Radio
700C *
Hoffman Press Box
Dry Pipe
Monaco Radio
707
Gross Sports Complex
Wet Pipe
Monaco Radio
708
Lichtenberg Tennis Center
Wet Pipe
Monaco Radio
714 *
Holleder Center
Wet Pipe
Monaco Radio
727 *
Arvin Gym
Wet Pipe
Monaco Radio
Bldg. #
Building
Type of System
Alarm Transmitter
735 *
Scott Barracks
Wet Pipe
Monaco Radio
738 *
Sherman Barracks
Wet Pipe
Monaco Radio
740 *
Lee Barracks
Wet Pipe
Monaco Radio
745 A/B *
Washington Hall

[2] Wet Pipe & Dry Pipe [Partial Protection] Gamewell 211 & 212

747
Nininger Hall
Wet Pipe
Monaco Radio
751
Pershing Barracks
Wet Pipe [Basement only]
Gamewell 243
753
Bartlett Hall

[2]

Wet Pipe & Pre Action [Partial Coverage]
Monaco Radio
756
Bradley Barracks
Wet Pipe [Basement Only]
Gamewell 216 – 219
757 *
Cadet Library [6]
Wet Pipe & Pre-Action
Gamewell 241
806
Crew & Sailing Center
Wet Pipe
Monaco Radio
913
DOL Warehouse
Wet Pipe
Monaco Radio
917
General Warehouse
Wet Pipe
Gamewell 437
1202
Shoppette [2]
Wet Pipe & Dry Pipe
Monaco Radio
1203
Fire Station #2
Wet Pipe
Monaco Radio
1204
Post Exchange [3]
Wet Pipe & Dry Pipe
Monaco Radio
1207
Child Dev Center
Wet Pipe
Monaco Radio
1207A
CDC Annex
Dry Pipe
Monaco Radio
1585
Camp Buckner Mess
Dry Pipe [Seasonal]
Monaco Radio
2101 *
Spellman Hall [2]
Wet Pipe & Pre-Action
Monaco Radio
2107 *
Visitors Center
Wet Pipe & Pre-Action
Monaco Radio
2110 *
West Point Museum

[22]

Wet Pipe , Dry Pipe, Pre-Action & Deluge
Monaco Radio

* - denotes building has a fire pump supplements domestic pressure for fire protection.

West Point Sprinkler Systems Updated 03/01/09

* Systems with fire pump

Bldg. #
Name
Type of System
Alarm Transmitter
140
New CDC
Wet Pipe
Monaco Radio
500
Youth Activity Ctr.
Wet Pipe
Monaco Radio
600
Taylor Hall
Pre-Action & Wet Pipe
Monaco Radio
601
Thayer Hall
Wet Standpipe Only
Monaco Radio
602 *
Grant Barracks
Wet Pipe
Monaco Radio
603 *
West Point Club
Wet Pipe
Monaco Radio
604
Power House
Pre-Action – Generator
Local
606
Cadet Clinics
Wet Pipe [Partial]
Monaco Radio
607 *
Lincoln Hall
Wet Pipe
Monaco Radio
609
ODIA Locker Rooms
Wet Pipe
Monaco Radio
613
Johnson Stadium
Wet Pipe
Monaco Radio
616
Stern Law Enforcement Center
Wet Pipe
Monaco Radio
620 *
MP Barracks
Wet Pipe & Dry Pipe
Monaco Radio
621
Command Group HQ
Wet Pipe
Monaco Radio
624 *
MEDDAC Dorm
Wet Pipe & Dry Pipe
Monaco Radio
626
Thomas Hall
Wet Pipe
Monaco Radio
635
Cadet 1st Class Club
Dry Pipe
Monaco Radio
646
Denfense Automated Printing Building
Wet Pipe
Monaco Radio
648
Auto Craft Shop
Wet Pipe
Monaco Radio
652
Transit Billeting
Wet Pipe [13R]
Monaco Radio
654
Transit Billeting
Wet Pipe [13R]
Monaco Radio
655*
Eisenhower Hall
Wet Pipe, Dry Pipe, Deluge
Monaco Radio
656
Transit Billeting
Wet Pipe
Monaco Radio
662
Transit Billeting
Dry Pipe
Monaco Radio
664
DES-Fire HQ
Dry Pipe
Monaco Radio
665
Rifle/Pistol Range
Wet Pipe
Monaco Radio
667 *
DHPW – Engineering Serves 667A & 667B
Wet Pipe, Dry Pipe
Monaco Radio
673
Arvin Annex
Dry Pipe – Out of Service
Monaco Radio
681 *
Garrison HQ
Wet Pipe
Monaco Radio
683
MWR Center
Wet Pipe
Monaco Radio
693
Craft Shop
Wet Pipe & Dry Pipe
Monaco Radio
700
East Stands
Dry Pipe
Monaco Radio
700A *
Randle Hall & Bridge
Wet Pipe
Monaco Radio
700B *
Kimsey Athletic Center
Wet Pipe
Monaco Radio
700C
Hoffman Press Box
Dry Pipe
Monaco Radio
Bldg. #
Building
Type of System
Alarm Transmitter
708
Lichtenberg Tennis Center
Wet Pipe
Monaco Radio
714 *
Holleder Center
Wet Pipe
Monaco Radio
717 A
Foley Athletic Center
Wet Pipe
Monaco Radio
727 *
Arvin Gym
Wet Pipe & Pre Action [2]
Monaco Radio
735 *
Scott Barracks
Wet Pipe
Monaco Radio
738 *
Sherman Barracks
Wet Pipe
Monaco Radio
740 *
Lee Barracks
Wet Pipe
Monaco Radio

745 *

Washington Hall
Wet Pipe covers basements in A/B/C/D

Dry Pipe in B Monaco Radio

747
Nininger Hall
Wet Pipe
Monaco Radio
751
Pershing Barracks
Wet Pipe [Basement only]
Monaco Radio
752*
Mahan Hall
Wet Pipe, Dry System & Deluge
Monaco Radio
753*
Science Center
Wet Pipe
Monaco Radio
756
Bradley Barracks
Wet Pipe [Basement Only]
Monaco Radio
758 *
Thos. Jefferson Library
Wet Pipe
Monaco Radio
806
Crew & Sailing Center
Wet Pipe
Monaco Radio
845
Cadet Laundry
Wet Pipe
Monaco Radio
854
Anderson Rugby
Wet Pipe
Monaco Radio
913
DOL Warehouse
Wet Pipe
Monaco Radio
917
General Warehouse
Wet Pipe
Monaco Radio
950
USMAPS
Wet & Dry Pipe
Monaco Radio
1202
Shoppette
Wet Pipe & Dry Pipe
Monaco Radio
1203
Fire Station #2
Wet Pipe
Monaco Radio
1204
Post Exchange
Wet Pipe & Dry Pipe
Monaco Radio
1207
Child Dev Center
Wet Pipe
Monaco Radio
1585
Camp Buckner Mess
Dry Pipe [Seasonal]
Monaco Radio
2101 *
Spellman Hall
Wet Pipe & Pre-Action
Monaco Radio
2107 *
Visitors Center
Wet Pipe & Pre-Action
Monaco Radio
2110 *
West Point Museum
Wet Pipe , Dry Pipe, Pre-Action
Monaco Radio
108 *
Hanger STAS
Deluge & Wet Pipe
Central Monitor
109 *
Hanger STAS
Deluge
Central Monitor
1610
Pump House
Wet Pipe
Monaco Radio
1940
TMP Motor Pool
Wet Pipe
Monaco Radio
1944
Water Treatment
Wet Pipe
Monaco Radio
1946
TMP Dispatch
Wet Pipe
Monaco Radio

TECHNICAL EXHIBIT V

Building 2101 Spellman Hall Fire Protection Systems Information

Computer Center Pre Action Sprinkler System [Monitored by Monaco Fire Alarm Panel] Type: Fire Cycle III [Single Interlock] Modules: M2-12 - Alarm Manufacturer: Viking M2-13 - Trouble Model: E-1 4 inch Valve Type Sprinkler Heads: F1FR Quick Response [Recess Heads] Additional Sprinkler Heads: 6 heads located in south exterior Sprinkler Room System Static Water Pressure = 150psi System Air Pressure = 48psi Location: Sprinkler Riser located in Room G-5 inside Computer Center

· Butterfly valve to shut down this system located on the riser

· Fire Alarm Panel located at the Main Entrance to Computer Center [Key Notifier 17021]

· Manual Override Pull Station to release water into system is located by FACP inside a plastic encasement.

· Air Compressor located on the riser: Compressor set to come on at 45psi and go off at 48psi.

· Heat Detectors for System: 140F Resettable PN22723 Air Compressor: FAST Manufacturing Model: 2LAF-12-M200X

Wet Pipe Sprinkler System Floors G- 5th Main Riser Room: South End of Building Exterior Mechanical Room. This room will shut down entire sprinkler and standpipe feed for the building.

Monaco Modules:M3-20 – Flow
M3-21 – Tamper
M3-22 – Tamper
M3-23 – Tamper
M3-27 – Flow
M3-28 – Tamper

Ground Floor Room G-19 – Standpipe Isolation Valve @ ceiling level of Metal Storage room south entrance.

[Monaco Modules: M3-15 = Flow M3-26 = Tamper] 1st Floor North Stairwell – Sprinkler Isolation Valve located under the stair.

[Monaco Modules: M4-01 = flow M4-02 = Tamper M4-03 = Tamper] 2nd Floor North Stairwell – Sprinkler Isolation Valve inside stairwell

Monaco Modules:M4-07 = Flow
M4-08 = Tamper

3rd Floor North Stairwell – Sprinkler Isolation Valve inside stairwell

Monaco Modules:M4-09 = Flow
M4-10 = Tamper

4th Floor North Stairwell – Sprinkler Isolation Valve inside stairwell Monaco Modules: M4-12 = Flow M4-13 = Tamper 5th Floor North Stairwell – Sprinkler Isolation Valve inside stairwell Monaco Modules: M4-15 = Flow M4-16 = Tamper Hydraulic Plate for Sprinkler located at each Riser in the stairwells at each floor.

Fire Department Connection - Combination Auto Sprinkler & Standpipe – South Mechanical Room *System is connected to Fire Pumps in North Exterior Mechanical Room