1. SITE SURVEYS ARE AUTHORIZED AT BOTH GOVERNMENT SITES.
2. OTU-4 SERVICE MUST BE TERMINATED TO THE LINE SIDE OF THE FIBER TERMINATING
PATCH PANEL INSTALLED IN THE DISA IE1 PROVIDED TERMINATING EQUIPMENT AT BOTH
SERVICE DELIVERY POINTS.
3. THE TELECOM PROVIDER MUST CONTACT DISA GOC TIER-II ENGINEERING UPON
RECEIPT OF A VALID TSO TO ESTABLISH THE COORDINATION AND ACTIVATION PROCESS.
PRI POC: DISA GLOBAL CASA INFRASTRUCTURE INTEGRATION LEASE BB TEAM PHONE:
(C) 618-418-9813, (D) 418-9813 EMAIL: DISA.SCOTT.GLOBAL.MBX.CASA-INFRASTRUCTURE-
INTEGRATION-L EASE-BB-T@MAIL.MIL ALT POC: ORGANIZATIONAL NUMBER (CASA RF
CIRCUIT ACTIVATIONS) PHONE: (C) 618-418-8691, (D) 418-8691 EMAIL:
DISA.SCOTT.GLOBAL.MBX.RF-CIRCUIT-ACTIVATIONS@MAIL.MIL.
4. ONCE THE TELECOM PROVIDER HAS COMPLETED INSIDE WIRING FROM THE DWDM
EQUIPMENT SUITE TO THE GOVERNMENT SERVICE DELIVERY POINT (SDP) AT EACH
LOCATION, THEY MUST ENSURE THE LIGHT LEVEL READINGS (DB LOSS) ARE ADJUSTED
TO READ -3 TO -9 LOSS. ADDITIONALLY, THESE LEVELS MUST BE DOCUMENTED ON THE
NOTICE OF COMPLETION (NOC) SENT TO DITCO.
5. THE VENDOR MUST TERMINATE OTU-4 SERVICE AT BOTH LOCATIONS IAW UNIQUE
INSTALLATION FACTORS.
6. OTU-4 SERVICE MUST PASS A DOCUMENTED SATISFACTORY 72 HOUR END TO END
TEST IAW ITU STANDARD M.2401 PRIOR TO TURN UP TO THE GOVERNMENT.
1. VENDOR MUST MEET SVC DATE.
2. CIRCUIT REQUIRES THE FOLLOWING PARAMETERS:
(A) FIBER TERMINATION: SINGLE-MODE INTERFACE REQUIREMENT/INTERFACE DATA
RATE: LINE CODING, FRAME FORMAT, PHYSICAL CONNECTOR, OTU-4, PM-QPSK (G.709
COMPLIANT LR4 BASED OTU4 SIGNAL). ALL OPTIONS DEFINED SC CONNECTOR, SINGLE-
MODE FIBER PER ANSI T1.105.06-2002 (SR-0, SR-1, IR-1, IR-2, LR-1, LR-2, LR-3).
(B) LINE MUST REMAIN FULLY OPERATIONAL AND AVAILABLE TO USERS 24 HOURS A DAY,
SEVEN DAYS PER WEEK, AT LEAST 99.5% OR BETTER.
(C) ONE-HOUR RESPONSE TIME TURN-AROUND MUST OCCUR TO REPAIR ONCE TROUBLE-
CALL HAS BEEN REPORTED.
(D) GFE CLOCKING: VENDOR ESFU (OR EQUIVALENT) NOT TO BE ENGINEERED INTO
CIRCUIT.
(E) SINGLE MODE FIBER TERMINATIONS "SC" CONNECTORS.
(F) NO NETWORK INTERFACE UNIT.
(G) DEDICATED PATH.
(H) CARRIER REQUIRED TO HAVE CIRCUIT VISIBILITY TO ASSIST IN ANY CIRCUIT
OUTAGES.
mailto:DISA.SCOTT.GLOBAL.MBX.RF-CIRCUIT-ACTIVATIONS@MAIL.MIL
(I) THE VENDOR MUST CONDUCT A 72 HOUR SATISFACTORY END TO END TEST ON THE
OTU-4 SERVICE IAW ITU STANDARD M.2401. ADDITIONALLY, THE VENDOR TEST SET/SETS
MUST HAVE THE ABILITY TO PRINT THE TEST RESULTS AND THOSE RESULTS MUST BE
EMAILED TO THE ACCEPTING AUTHORITY FOR REVIEW.
(J) VENDOR MUST HAVE A 24X7 NETWORK OPERATIONAL CENTER FOR THIS OTU-4
SERVICE.
(K) THE COMMERCIAL CIRCUIT WILL BE ACCEPTED ON BEHALF OF THE GOVERNMENT BY
THE DGOC: PRI POC: DISA GLOBAL CASA INFRASTRUCTURE INTEGRATION LEASE BB
TEAM PHONE: (C) 618-418-9813, (D) 418-9813 EMAIL: DISA.SCOTT.GLOBAL.MBX.CASA-
INFRASTRUCTURE-INTEGRATION-L EASE-BB-T@MAIL.MIL ALT POC: ORGANIZATIONAL
NUMBER (CASA RF CIRCUIT ACTIVATIONS) PHONE: (C) 618-418-8691, (D) 418-8691 EMAIL:
DISA.SCOTT.GLOBAL.MBX.RF-CIRCUIT-ACTIVATIONS@MAIL.MIL
(L) THE VENDOR MUST PROVIDE THE LONG HAUL CIRCUIT NUMBER AND THE 1-800
TROUBLE REPORT NUMBER TO THE ACCEPTING AUTHORITY PRIOR TO THE
GOVERNMENT ACCEPTING SERVICE. INSIDE WIRING MUST BE COMPLETED AND TESTED
PROPERLY IAW THE ORDER PRIOR TO TURN-UP TO THE GOVERNMENT.
3. VENDOR IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE OF OTU-4 SERVICE
IAW UNIQUE INSTALLATION FACTORS.
4. INSIDE WIRING IS AUTHORIZED IAW WITH THE UNIQUE INSTALLATION FACTORS.
5. VENDOR MUST COORDINATE SITE VISIT WITH POC'S 72 HOURS IN ADVANCE PRIOR TO
REQUIRING ACCESS TO FACILITIES AT BOTH USER LOCATIONS.
6. FOR UNSATISFACTORY SERVICE OR TO REPORT EQUIPMENT AND/OR CIRCUIT
PROBLEMS INVOLVING DISA PROVIDED TRANSPORT AND/OR EQUIPMENT, PLEASE
CONTACT THE DISN CUSTOMER CONTACT CENTER (DCCC) SCOTT AFB, IL. TOLL FREE: 1-
855-868-9500, COML: 618-418-9500, DSN: 312-418-9500.
7. DD FORM 1368 WILL BE SUBMITTED ON THIS TRUNK IAW DISAC-DITCO 350-135-1 BY
RNSOC, SCOTT AFB, IL. GUIDANCE ON SUBMISSION IS AVAILABLE AT
<HTTP://WWW.DITCO.DISA.MIL/ASP/PUBLICATIONS.ASP>. CLICK ON "DISA-DITCO
CIRCULAR, 350-135-1, DEFENSE COMMERCIAL COMMUNICATIONS ACQUISITION
PROCEDURES."
MINIMUM TECHNICAL SPECIFICATIONS: SPECIFIC FORMAT TO BE USED IS: LINE RATE:
OTU-4 LINE CODE: PM-QPSK (G.709 COMPLIANT LR4 BASED OTU4 SIGNAL)
1. TEST AND ACCEPTANCE: OTU-4 CIRCUITS SHALL PASS A FULLY DOCUMENTED
SATISFACTORY SOAK TEST BY THE CONUS GNOSC AT SCOTT AFB, IL. PRIMARY: (C) 618-
220-8691 (D) 770-8691.
2. OTU-4 SERVICE PROVIDED SHALL MEET THE FOLLOWING PERFORMANCE
REQUIREMENTS ON A MONTHLY BASIS. PERFORMANCE REQUIREMENT/PERFORMANCE
SPECIFICATION: NON-DIVERSE/NON-PROTECTED AVAILABILITY: GREATER THAN OR
EQUAL TO 99.5% OR BETTER. MONTHLY SHORT INTERRUPTION EVENT COUNT (SEIC):
LESS THAN OR EQUAL TO 9%. ERRORED SECONDS (ES): LESS THAN OR EQUAL TO
0.005%. SEVERELY ERRORED SECONDS (SES): LESS THAN OR EQUAL TO 0.00035.
BACKGROUND BLOCK ERROR RATIO (BBER): LESS THAN OR EQUAL TO 5 X 10-6. BIT
mailto:DISA.SCOTT.GLOBAL.MBX.RF-CIRCUIT-ACTIVATIONS@MAIL.MIL
COUNT INTEGRITY (BCI)/PATTERN SLIP (PAT SLIP): LESS THAN OR EQUAL TO 1 PER 72
HOURS. BER: LESS THAN OR EQUAL TO 1X10-12. DELAY (ONE WAY): * LESSER OF 10 MSEC
OR (0.01 X D MSEC) * WHERE "D" IS THE SDP-TO-SDP TRANSMISSION DISTANCE,
MEASURED SHORTEST GREAT CIRCLE, IN KILOMETERS.
3. ROUND TRIP DELAY (RTD) FOR THIS DISA TRANSPORT TRUNK WILL BE MEASURED IN
MILLISECONDS FROM THE CUSTOMER'S SERVICE DELIVERY POINT (SDP) SITE-A TO THE
CUSTOMER'S SERVICE DELIVERY POINT (SDP) SITE-Z. THE RTD SHALL BE LESS THAN OR
EQUAL TO 10 MILLISECONDS TO EFFECTIVELY SUPPORT THE GOVERNMENT'S MISSION.
THE GOVERNMENT ACCEPTING AUTHORITY WILL CONFIRM THE RTD DURING THE TURN-
UP AND TEST PHASE AND IF IT DOES NOT ALIGN WITH THE CONTRACTOR’S PROPOSAL,
DISA IE161 WILL NOTIFY DITCO IMMEDIATELY IN WRITING. (**UNIQ INSTALL FACTORS**)
(SP A) TERMINATING PATCH PANEL BLDG 777, ROOM 207A TO THE LINE SIDE OF THE SITE
PROVIDED FIBER TERMINATING PATCH PANEL BLDG 10, ROOM 23, USING EXISTING ON-
BASE SINGLE-MODE FIBER. (** ADDITIONAL PROVISIONING INFORMATION **) (ORG ACCT)
DISN FIBER OPTIC BACKBONE & O/W CONTROL
DIVERSITY/AVOIDANCE INSTRUCTIONS: DIVERSITY OPTION #3: PWS 6.2.2.3C) II - PHYSICAL
DIVERSITY UTILIZING TWO DIFFERENT DEMARKS AT THE CUSTOMER ACCESS SITE R.
DIVERSITY/AVOIDANCE COMMERCIAL CIRCUIT:
1. THIS REQUIREMENT MUST BE ENGINEERED AND PROVISIONED TOTALLY DIVERSE END
TO END TO THE GOVERNMENT'S SERVICE DELIVERY POINTS (SDP'S) FROM TSR
SG11APR227346
2. THIS REQUIREMENT MUST BE WORKED IN CONJUNCTION WITH TSR SG11APR227346
AND AWARDED AS A PAIR TO A SINGLE VENDOR TO ENSURE DIVERSITY
3. THIS REQUIREMENT MUST BE ENGINEERED AND PROVISIONED TOTALLY DIVERSE END
TO END TO GOVERNMENT'S SERVICE DELIVERY POINTS (SDP'S) FROM TSR
SG11APR227346, MEANING THAT PHYSICAL PATHS ARE TOTALLY SEPARATE INCLUDING
MANHOLES, CONDUIT, (CENTRAL OFFICE LOCATIONS), AND FIBER BUILDS. ADDITIONALLY,
AS A MINIMUM THERE MUST BE A 50 METER PHYSICAL SEPARATION FROM TSR
SG11APR227346.
4. THE TELECOM PROVIDER MUST PROVIDE DITCO COLOR POWERPOINT DRAWI NGS FOR
TECHNICAL REVIEW SHOWING THE ROUTES FROM THE COMMERCIAL D EMARCS TO THE
SUPPORTING CENTRAL OFFICES AND/OR WIRING CENTERS. DRAWINGS MUST INCLUDE
SEPARATION DISTANCES BETWEEN DIVERSE REQUIRE MENTS, TOTAL FIBER MILES AND
ROUND-TRIP DELAY (RTD), AND FIBER ROUTES RED LINED END TO END SO THE
GOVERNMENT CAN CONFIRM PHYSICAL END TO END DIVERSITY REQUIREMENTS ARE
MET. ADDITIONALLY, THE VEND OR IS TO PROVIDE DITCO WITH DETAILED CIRCUIT/PATH
CONNECTIVITY DI AGRAMS, IN KMZ OR KML FORMAT, IDENTIFYING ALL POINTS OF
PRESENCE (POP) FOR EVALUATION AND AS A FINAL RECORD OF THE INSTALLED PATH.
THESE DIAGRAMS MUST BE PROVIDED TO DISA HQ IE16 (DISA.MEADE.IE. MBX.IE16-
PROVISIONING-TEAM@MAIL.MIL) FOR HISTORICAL PURPOSES.