TESTING REQUIREMENTS HC101321QA485
THE VENDOR MUST PROVIDE LIGHT LEVEL READINGS (SIGNAL STRENGTH IN DBM) ON
THE EXTENSION FROM COMMERCIAL POP TO THE GOVERNMENT SERVICE DELIVERY
POINT (SDP) AT THE "A" AND "Z" LOCATION PRIOR TO CIRCUIT TURN OVER TO THE
GOVERNMENT ENSURING LEVELS ARE WITHIN SPECS. LIGHT LEVELS MUST BE
ADJUSTED TO -3 TO -9 DBM.
THE PROVIDER MUST CONDUCT A SATISFACTORY 24-HOUR TEST FROM THE DROP
SIDE OF THEIR OR LOCAL EXCHANGE CARRIERS FDP INSTALLED IN THEIR
EQUIPMENT SUITE AT THE "A" LOCATION TO THEIR OR LOCAL EXCHANGE CARRIERS
FDP INSTALLED IN THEIR EQUIPMENT SUITE AT THE "Z" LOCATION AND MUST
INCLUDE THE EXTENSION BETWEEN THE COMMERCIAL DEMARC AND THE
GOVERNMENT'S SDP. VENDOR MUST ENSURE TEST SETS ARE PLACED AT THE DROP
SIDE AT THE "A" LOCATION AND AT THE "Z" LOCATION. TESTING MUST BE
SATISFACTORY PRIOR TO TURN OVER TO THE GOVERNMENT FOR ACCEPTANCE
TESTING. THE VENDOR MUST TEST THE CIRCUIT FOR 24 HOURS IAW THE FULL ITU-
T.Y.1564 BENCH MARKING METHODOLOGY FOR NETWORK INTERCONNECT DEVICES
STANDARD, AND AT THE COMMITTED INFORMATION RATE (CIR) IAW ITU-T-Y.1564.
DIVERSITY INFO: NETWORK DIVERSITY REQUIRED: PATH DIVERSITY; COMMERCIAL
DIVERSITY: ADDITIONAL PROVISIONING INFORMATION: (ORG ACCT) DISA (DISN IP ROUTER
NETWORK BACKBONE AND BACKBONE HOSTS) (CONUS AND OCONUS) L. REMARKS
CONTINUED: (** REMARKS **) ***CONTINUED FROM PURPOSE - TSR LI 401/TSO PARA 1.
ATTENTION PORTSMOUTH VA LOCATION*** THIS REQUIREMENT MUST BE ENGINEERED
AND PROVISIONED TOTALLY DIVERSE END TO END TO GOVERNMENT'S SERVICE
DELIVERY POINTS (SDP'S), MEANING THAT PHYSICAL PATHS ARE TOTALLY SEPARATE
INCLUDING MANHOLES, CONDUIT, (CENTRAL OFFICE LOCATIONS), AND FIBER BUILDS.
ADDITIONALLY, AS A MINIMUM THERE MUST BE A 50 METER PHYSICAL SEPARATION. THE
50 METER SEPARATION IS WAIVED INSIDE BLDG 250 FOR 214 PORTSMOUTH LOCATION.
THE TELECOM PROVIDER MUST PROVIDE DITCO COLOR POWERPOINT DRAWINGS FOR
TECHNICAL REVIEW SHOWING M. REMARKS CONTINUED: THE ROUTES FROM THE
COMMERCIAL DEMARCS TO THE SUPPORTING CENTRAL OFFICES AND/OR WIRING
CENTERS. DRAWINGS MUST INCLUDE SEPARATION DISTANCES BETWEEN DIVERSE
REQUIREMENTS, TOTAL FIBER MILES AND ROUND-TRIP DELAY (RTD), AND FIBER ROUTES
RED LINED END TO END SO THE GOVERNMENT CAN CONFIRM PHYSICAL END TO END
DIVERSITY REQUIREMENTS ARE MET. ADDITIONALLY, THE VENDOR IS TO PROVIDE DITCO
WITH DETAILED CIRCUIT/PATH CONNECTIVITY DIAGRAMS, IN KMZ OR KML FORMAT,
IDENTIFYING ALL POINTS OF PRESENCE (POP) FOR EVALUATION AND AS A FINAL RECORD
OF THE INSTALLED PATH. THESE DIAGRAMS MUST BE PROVIDED TO DISA HQ IE16
(DISA.MEADE.IE.MBX.IE16-PROVISIONING-TEA M@MAIL.MIL) FOR HISTORICAL PURPOSES.
THE VENDOR MUST PROVIDE LIGHT LEVEL READINGS (SIGNAL STRENGTH IN DBM) ON
THE EXTENSION FROM COMMERCIAL POP TO THE GOVERNMENT SERVICE DELIVERY
POINT (SDP) AT THE "A" AND "Z" LOCATION PRIOR TO CIRCUIT TURN OVER TO THE
GOVERNMENT ENSURING LEVELS ARE WITHIN SPECS. LIGHT LEVELS MUST BE ADJUSTED
TO -3 TO -9 DBM. THE VENDOR MUST TERMINATE 10GB ETHERNET SERVICE AT SERVICE
DELIVERY LOCATIONS, IAW UNIQUE INSTALLATION FACTORS. THE VENDOR MUST
CONDUCT WALK-THROUGH SITE SURVEY PRIOR TO INSTALLATION AT BOTH LOCATIONS.
THE VENDOR MUST CONTACT DISA GOC IP BACKBONE ENGINEERING AND
IMPLEMENTATION GROUP UPON RECEIPT OF A VALID TSO TO ESTABLISH THE
COORDINATION AND ACTIVATION PROCESS. PHONE: (C) 618-418-8627, (D) 418-8627. THE
VENDOR MUST CONTACT DISA GOC TIER-II ENGINEERING 48 HOURS PRIOR TO
BEGINNING THEIR END-TO-END TESTING. PHONE: (C) 618-418-8627, (D) 418-8627. 13. THE
PROVIDER MUST CONDUCT A SATISFACTORY 24-HOUR TEST FROM THE DROP SIDE OF
THEIR OR LOCAL EXCHANGE CARRIERS FDP INSTALLED IN THEIR EQUIPMENT SUITE AT
THE "A" LOCATION TO THEIR OR LOCAL EXCHANGE CARRIERS FDP INSTALLED IN THEIR
EQUIPMENT SUITE AT THE "Z" LOCATION AND MUST INCLUDE THE EXTENSION BETWEEN
THE COMMERCIAL DEMARC AND THE GOVERNMENT'S SDP. VENDOR MUST N. REMARKS
CONTINUED: ENSURE TEST SETS ARE PLACED AT THE DROP SIDE AT THE "A" LOCATION
AND AT THE "Z" LOCATION. TESTING MUST BE SATISFACTORY PRIOR TO TURN OVER TO
THE GOVERNMENT FOR ACCEPTANCE TESTING. THE VENDOR MUST TEST THE CIRCUIT
FOR 24 HOURS IAW THE FULL ITU-T.Y.1564 BENCH MARKING METHODOLOGY FOR
NETWORK INTERCONNECT DEVICES STANDARD, AND AT THE COMMITTED INFORMATION
RATE (CIR) IAW ITU-T-Y.1564.
REMARKS: 1. CIRCUIT REQUIRES THE FOLLOWING PARAMETERS:
(A) FIBER TERMINATION: FRAME FORMAT: 10GB ETHERNET (OPTICAL HANDOFF-10GB
ETHERNET-LAN-PHY-SINGLE MODE FIBER), 1310NM. "SC" OR "LC" CONNECTORS AS
DETERMINED BY SITE SURVEY. NOTE: WHEN EXTENDED REACH OPTICS ARE USED THAT
CHANGE THE TX/RX WAVELENGTH OF THE OPTIC, THE VENDOR WILL NOTIFY THE
GOVERNMENT 30 DAYS PRIOR TO DELIVERY.
(B) COMMITTED INFORMATION RATE (CIR): 10GB.
(C) ETHERNET FRAME SIZE WILL BE CONFIGURED TO SUPPORT MAXIMUM TRANSMISSION
UNIT (MTU) OF 9000 OCTETS (BYTES) JUMBO FRAMES.
(D) NO NETWORK INTERFACE UNIT, DEDICATED PATH.
(E) GFE CLOCKING: VENDOR ESFU (OR EQUIVALENT) NOT TO BE ENGINEERED INTO
CIRCUIT.
(F) TESTING CRITERIA: VENDOR MUST TEST THE CIRCUIT FOR 24 HOURS IAW THE FULL
ITU-T.Y.1564 BENCH MARKING METHODOLOGY FOR NETWORK INTERCONNECT DEVICES
STANDARD, AND AT THE COMMITTED INFORMATION RATE (CIR) IAW ITU-T-Y.1564. NOTE:
FRAME SIZE DESIGNATOR 'H' (MTU) IS EQUAL TO 9000 BYTES.
(G) LINE MUST REMAIN FULLY OPERATIONAL AND AVAILABLE TO USERS 24 HOURS A DAY,
SEVEN DAYS PER WEEK, MONTHLY PERFORMANCE OF 99.5% AVAILABILITY OR BETTER.
(H) 1 HOUR RESPONSE TIME TO RESPOND TO CUSTOMER UPON RECEIPT OF TROUBLE.
(I) VENDOR REQUIRED TO HAVE CIRCUIT VISIBILITY TO ASSIST IN ANY CIRCUIT OUTAGES.
(J) VENDOR MUST HAVE A 24X7 NETWORK OPERATIONS CENTER.
(K) TELECOM PROVIDER MUST MAINTAIN OPERATIONS, MAINTENANCE AND
ADMINISTRATION MONITORING OF ETHERNET CIRCUIT.
O. REMARKS CONTINUED: (L) THE COMMERCIAL CIRCUIT WILL BE ACCEPTED ON BEHALF
OF THE GOVERNMENT BY THE DISA GOC IP BACKBONE ENGINEERING AND
IMPLEMENTATION GROUP, SCOTT AFB, IL. (C) 618-418-8627, (D) 418-8627. VENDOR
WINNING AWARD IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE OF THE
SERVICE IAW THE UNIQUE INSTALLATION FACTORS. INSIDE WIRING IS AUTHORIZED IAW
THE UNIQUE INSTALLATION FACTORS. VENDOR MUST COORDINATE SITE VISIT WITH
POC'S 72 HOURS IN ADVANCE PRIOR TO REQUIRING ACCESS TO FACILITIES AT BOTH
USER LOCATIONS. 5. VENDOR MUST CONTACT DISA GOC TIER-II ENGINEERING 48 HOURS
PRIOR TO BEGINNING THEIR END-TO-END TESTING. ALL EQUIPMENT AND CIRCUIT
PROBLEMS WILL BE REPORTED BY PHONE TO THE DISA GOC IP BACKBONE ENGINEERING
AND IMPLEMENTATION GROUP, SCOTT AFB, IL. PRIMARY: (C) 618-418-9950, (D) 418-9950
TOLL FREE: 855-868-9950. DD FORM 1368 WILL BE SUBMITTED ON THIS TRUNK IAW DISAC-
DITCO 350-135-1 BY RNSOC, SCOTT AFB, IL. GUIDANCE ON SUBMISSION IS AVAILABLE AT
<HTTP://WWW.DITCO.DISA.MIL/ASP/PUBLICATIONS.ASP>. CLICK ON "DISA-DITCO
CIRCULAR, 350-135-1, DEFENSE COMMERCIAL COMMUNICATIONS ACQUISITION
PROCEDURES.
MINIMUM TECHNICAL SPECIFICATIONS: SPECIFIC FORMAT TO BE USED IS: LINE RATE:
10.3125 GIGABITS/S, +- 100 PPM LINE CODE: OPTICAL 1. TEST AND ACCEPTANCE: THIS
CIRCUIT SHALL PASS A FULLY DOCUMENTED, SATISFACTORY, 72 HOUR SOAK TEST BY
DISA GOC AT SCOTT AFB, IL. PRIMARY: (C) 618-418-8627 (D) 418-8627. 2. ERROR
PERFORMANCE: ERROR PERFORMANCE SHALL BE BETTER THAN THE FOLLOWING
PARAMETER THRESHOLDS TO BE ACCEPTABLE: AVAILABILITY SHALL BE GREATER THAN
99.5% OR BETTER. FRAME LOSS SHALL BE EQUAL TO ZERO WHEN TESTING AT 10 GIGABIT
HIGHEST FRAME RATE AND SHALL MEET ITU-T-Y.1564 STANDARDS. JITTER SHALL BE
LESS THAN 3 MSEC. DELAY SHALL BE BETTER THAN 10 MSEC. 3. MEAN TIME TO LOSS OF
BIT COUNT INTEGRITY (MTTLBCI) SHALL P. REMARKS CONTINUED: BE GREATER THAN 24
HOURS. 4. ROUND TRIP DELAY (RTD) FOR THIS DISA TRANSPORT TRUNK WILL BE
MEASURED IN MILLISECONDS FROM THE CUSTOMER'S SERVICE DELIVERY POINT (SDP)
SITE-A TO THE CUSTOMER'S SERVICE DELIVERY POINT (SDP) SITE-Z. THE RTD SHALL BE
LESS THAN OR EQUAL TO 10 (10MS (<450)/15MS (450-1000)/ 20MS (1000-1500)/ 29MS
(>1500)) MILLISECONDS TO EFFECTIVELY SUPPORT THE GOVERNMENT'S MISSION. THE
GOVERNMENT ACCEPTING AUTHORITY WILL CONFIRM THE RTD DURING THE TURN-UP
AND TEST PHASE AND IF IT DOES NOT ALIGN WITH THE CONTRACTOR’S PROPOSAL, DISA
IE161 WILL NOTIFY DITCO IMMEDIATELY IN WRITING. Q. REMARKS CONTINUED: ANY
ADDRESSEE ON THE (TSO) WILL NOTIFY ALL ADDRESSEES IMMEDIATELY BY MESSAGE
IDENTIFYING ANY ISSUES, PROBLEMS, OR SITUATIONS WHICH MAY PREVENT OR DELAY
THE IMPLEMENTATION OF THIS TELECOMMUNICATIONS SERVICE ORDER (TSO). ALL
STATIONS WILL REVIEW THE CONFIGURATION, EQUIPMENT, CONTACT NUMBERS AND
ADDRESSES CONTAINED IN THIS (TSO) AND PROVIDE UPDATES TO ORIGINATOR OF (TSO)
ANY ERRORS SO THAT SUBSEQUENT (TSOS) MAY BE UPDATED. R. DD FORM 1368: DD
FORM 1368'S (MODIFIED USE OF LEASED COMMUNICATION FACILITIES), OR EMAIL
EQUIVALENT, WILL BE SUBMITTED, AS REQUIRED, ON THIS CIRCUIT IAW DISAC-DITCO 350-
135-1 BY THE STATION DESIGNATED IN PARAGRAPH 2H AS CCO/CMO. GUIDANCE ON
SUBMISSION IS AVAILABLE AT
HTTP://WWW.DITCO.DISA.MIL/CORPORATELIBRARY/HOME.ASP. CLICK ON "350-135-1,
DEFENSE COMMERCIAL COMMUNICATIONS ACQUISITION PROCEDURES." S.
DIVERSITY/AVOIDANCE INSTRUCTIONS: DIVERSITY IS REQUIRED. THE VENDORS MUST
PROVIDE MAPS AND DRAWINGS PER STANDARD PROVISIONS. DIVERSITY IS DEFINED AS
50 METER/164 FEET SEPARATION WITH NO COMMON CONDUITS, MANHOLES, FACILITY
ENTRANCES AND POWER. T. IMPLEMENTATION ASSISTANCE: IMPLEMENTATION
ASSISTANCE: FOR SERVICE ACTIVATION INQUIRIES/SCHEDULING/ASSISTANCE, NAVIGATE
TO THE DISA GLOBAL SERVICE ACTIVATIONS CUSTOMER ACCESS PORTAL:
HTTPS://DISA.DEPS.MIL/DISA/COP/GSM-O/BACKBONE/CUSTOMER%20ACCESS%2
0SITE/SITEPAGES/SAM%20CUSTOMER%20HOMEPAGE.ASPX, OR CONTACT DSN 312-418-
8627, CMCL 001-618-418-8627. FOR EMAIL SUPPORT, PLEASE CONTACT THE APPROPRIATE
TEAM BELOW: DEDICATED/NIPRNET/SIPRNET/VPN SERVICE ACTIVATIONS: EMAIL:
DISA.SCOTT.GLOBAL.MBX.RF-CIRCUIT-ACTIVATIONS@MAIL.MIL SIPRNET ACCESS
MIGRATION (SAM) PROJECTS (D508, D710, D806, D910): EMAIL:
DISA.SCOTT.GLOBAL.MBX.IMPACT-TEAM@MAIL.MIL FOR ALL OTHER PROJECT RELATED
EFFORTS: EMAIL:DISA.SCOTT.GLOBAL.MBX.RF-CIRCUIT-ACTIVATIONS@MAIL.MIL DISN
BACKBONE ACTIVATIONS: EMAIL: DISA.SCOTT.GLOBAL.MBX.CASA-INFRASTRUCTURE-
INTEGRATION-LEAS E-BB-T@MAIL.MIL U. IMPLEMENTATION ASSISTANCE CONTINUED: FOR
CIRCUIT INSTALLATION ASSISTANCE WITH THE COMMERCIAL LEASED PATH, CONTACT
DCP COMMERCIAL ACTIVATION TEAM (CAT) AT D312-850-0820, C614-692-0820. V.
UNSATISFACTORY SERVICE REPORTING INSTRUCTIONS: FOR UNSATISFACTORY SERVICE
OR TO REPORT EQUIPMENT AND/OR CIRCUIT PROBLEMS INVOLVING DISA PROVIDED
TRANSPORT AND/OR EQUIPMENT, PLEASE CONTACT THE DISN CUSTOMER CONTACT
CENTER (DCCC) TOLL FREE NUMBER IS 1-844-347-2457 (1-844-DISA HLP) OPTION 2, COML
1-614-692-0032 OPTION 2, DSN 312-850-0032 OPTION 2. W. COMPLETION REPORT: (1)
STATION DESIGNATED IN PARAGRAPH 2H AS CCO/CMO WILL SUBMIT COMPLETION
REPORT IAW DISAC 310-130-1, SUPP 1, 2, 3 FORMAT OR DISAC 310-70-1. REPORT WILL BE
ADDRESSED TO ORIGINATOR AND ALL ADDRESSEES OF THIS (TSO). (2) STATIONS IN
PARA 3 OF THIS (TSO) ARE RESPONSIBLE FOR VERIFYING IN-STATION DETAILS AND
FORWARDING THE CORRECT INFORMATION, IF ANY DISCREPANCIES ARE NOTED, TO THE
CCO/CMO DESIGNATED IN PARA 2H. THE CCO/CMO WILL SUBMIT CORRECTIONS TO DISA
VIA "EXCEPTION REPORT" IAW DISAC 310-130-1, CHAP 2.
File details come from the government source that posted it. Updated .