Technical performance specifications.DOCX.docx
DOCX document 15 KB Posted
- Solicitation number
- 36H79721R0007
About this file
This document includes technical performance specifications for a lint blowdown fan system and a related federal contract opportunity notice. The technical specifications call for a robotic high-velocity fan system to control lint accumulation in a textile facility and mechanical room. Requirements include a 1.5HP motor, sickle-type blades, 140 degree oscillation, 360 degree rotation, electrical enclosures rated NEMA 12, central control panel functions, and setup of a minimum of four zones.
The federal contract opportunity is a sources sought notice from the Department of Veterans Affairs seeking information on vendors capable of providing a lint blowdown system for the St. Albans, NY Community Living Center. Responses are required to include company information, assigned NAICS code 333318 and size standard of 1000 employees, commercial laundry equipment price list, and capability statement with past performance on commercial laundry contracts within the last five years. Responses must be submitted by December 19, 2020 to Jeanette Dyrek at the email provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36H79721R0007.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ITEM # 1 –INDUSTRIAL LINT BLOWDOWN FAN SYSTEM
Furnish, install and commission (Qty. 1) industrial robotic high-velocity, high mass-cleaning fan system consisting of 360-degree rotation and 140-degree oscillation fans to help create an overhead barrier in the laundry production area and mechanical room ceilings. By controlling the direction of the lint and forcing it to the floor by preventing upward currents and stagnant air, preventing significant accumulation of lint in overhead and hard-to-reach places when system is in operation. The system will be designed to cover the entire textile facility and textile mechanical room.
TECHNICAL PERFORMANCE SPECIFICATIONS
Multiple Zone Lint Cleaning Fan System – 360° Rotation & 140° Oscillation
1. Minimum 1.5HP, TEAO (Totally Enclosed, Air-Over), premium efficiency motor, inverter duty.
a. Electrical Specification: 208 volts/3phase/60hz
2. Sickle-type fan blade for high efficiency design.
3. Provide 140 degrees vertical cleaning oscillation.
a. Oscillation adjustments via quick drive/driven disc bolt changes.
b. Multiple oscillation settings to fit application.
c. Totally enclosed fan drive construction for safety.
4. Provide 360 degrees in rotational coverage.
5. Electrical enclosure(s) Shall be NEMA 12 rated
6. Terminal block enclosure for single point power connection.
7. Self-lubricating and sealed bearings.
8. UL Certified fan design.
9. All metal construction, with powder coated components.
10. Extended fan shroud for further cleaning distances
11. Provide reverse control kit(s) where limiting rotational coverage is present.
12. Provide central control panel with:
a. Emergency fire control interlocking to building fire alarm system.
b. Automatic control timer.
c. Lock-out-tag-out.
d. Motor starters with overload protection.
e. Variable frequency drive
f. Setup minimum three (4) zones for all fans