Technical Exhibit D - As-Builts.pdf

PDF 2 MB Posted

Attached to
Replace Chillers in Building 56055 Federal contract opportunity
Solicitation number
W91151-20-B-0008
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood

About this file

This solicitation is seeking bids to replace two boilers, two heating hot water pumps, heating hot water piping and associated accessories, as well as replacing existing HVAC controls with a new DDC control system, in Building 56055 at Fort Hood, Texas. The contract is set aside for Service Disabled Veteran Owned Small Businesses with a size standard of $16.5 million. Bids are due by July 15, 2020. The contract period of performance is 180 days from notice to proceed. An organized site visit will be held on June 10, 2020. The technical exhibits are available for review on betaSAMS. Interested parties must be registered in SAM to receive an award. The point of contact is Sonja Fields, who can be reached by email. The wage determination is TX20200230. The bid guarantee must be at least 20% but not exceed $3 million, and performance and payment bonds must equal 100% of the contract price. Except as provided, all work must comply with applicable laws, codes, standards, specifications and contract terms.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REFLECTED CEILING PLAN - FIRST FLOOR

1/16"=1’-0"

A-120

R E

F L

E C

T E

D

C

IL

IN

G

P L

A N

F

IR

S T

F

O O

R

A A

S W

S W

A A

B B

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t e u b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n t r

N o

R e v

A

B

C

D

2 3 4 5

C O

R

O

G

IN

E E

R

W

R T

H

T E

X

U .S

A R

M Y

G

IN

E

IS

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

A R

C H

IT

E C

T U

R

C T

IO

N

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

IL

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k in g d a t e c a d d f il e n a m e

H

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IO

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

B

Y L

E R .A

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G w/20 GAGE SHEET METAL BACKING

FRAMED GYP BD CEILING

SUSP. TEXTURED GYP. BD. CEILING EXHAUST GRILLE

SUPPLY GRILLE

RETURN GRILLE

CONCRETE

WIREMESH CEILING

1’ x 4’ FLUOR. LIGHT. FIXTURE

WALL MOUNTED LIGHT. FIXTURE.

WALL MOUNTED LIGHT. FIXTURE

2’ x 2’ FLUOR. LIGHT. FIXTURE

INCAND. OR FLUOR. FIXTURE

EXIT LIGHT FIXTURE

ACOUSTIC SUSPENDED CEILING

REFLECTED CEILING PLAN LEGEND

NORTH

PLAN

S S S SS S

S S

S

AREA DAREA E

AREA A AREA B AREA C

REFLECTED CEILING PLAN - AREA B

1/8"=1’-0"

A-123

E N

L A

R G

F L

E C

T

IL

A N

A R

AA A A

L-1 L-1

A A

S W

S W

A A

B B

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

A R

C H

IT

E C

T U

R

C T

IO

N

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

B

Y L

E R .A

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G w/20 GAGE SHEET METAL BACKING

FRAMED GYP BD CEILING

SUSP. TEXTURED GYP. BD. CEILING EXHAUST GRILLE

SUPPLY GRILLE

RETURN GRILLE

CONCRETE

1’ x 4’ FLUOR. LIGHT. FIXTURE

WALL MOUNTED LIGHT. FIXTURE.

WALL MOUNTED LIGHT. FIXTURE

2’ x 2’ FLUOR. LIGHT. FIXTURE

INCAND. OR FLUOR. FIXTURE

EXIT LIGHT FIXTURE

ACOUSTIC SUSPENDED CEILING

REFLECTED CEILING PLAN LEGEND

NORTH

PLAN

SS

S S

S

AREA DAREA E

AREA A AREA B AREA C

1/16"=1’-0"

FINISH FLOOR PLAN - FIRST FLOOR

I-116

I-112

I-113

I-114

I-115

I-110

AREA DAREA E

AREA A AREA B AREA C

H

K

IM

B R

O W

H

K

IM

B R

O W

F

IN

O

A N

F

IR

O O

R

155A

XO TRAINING ROOM

155C 156A

TRAINING ROOM

156B

1SG

155D

1SG

155E

STORAGE

CO CDR.

155B

STORAGE

157E

1SG

157B

TRAINING ROOM

157A156C

156D

CO CDR.

XO

STORAGE

156E

CO CDR.

157D

157C

XO PLATOON OFFICE

158A

PLATOON OFFICE

158B

STORAGE

158E

PLATOON OFFICE

158D

158C

PLATOON OFFICE

CONFERENCE ROOM

STORAGE

160A

STORAGE

159A

CONFERENCE ROOM

161A

STORAGE

VESTIBULE

100A

CONFERENCE ROOM

CORRIDOR

RECYC.

VENDING

JANITOR

VESTIBULE

103A

MECHANICAL

WOMEN

VESTIBULE

102A

MEN

VESTIBULE

102B

VESTIBULE

103B

COMM

SIPRNET

ELEC

VESTIBULE

100B

CORRIDOR

CONFERENCE ROOM

STORAGE

112A

112C

STORAGE

113A 114A

STORAGE

CONFERENCE ROOM

113C

CONFERENCE ROOM

114C

115A

CO CDR.

115B

115E

STORAGE

115D

1SG

TRAINING ROOM

115C

XO

116A

CO CDR.

116B

STORAGE

116E

116C

TRAINING ROOM XO

116D

1SG

117A

CO CDR.

117B

XO

117E

STORAGE

1SG

117D

TRAINING ROOM

117C

TRAINING ROOM

118A

1SG

118B

118E

STORAGE

118D

CO CDR.

118C

XO

VAULT

RM1-101

STOR.

COMM

RM1-102

NBC STOR

RM1-103

GEAR STORAGE

TA-50

RM1-100

UNIT STOR

RM1-104

STOR

NON-SENS

SECURE

RM1-105

VAULT

RM2-101

RM3-100

VAULT

RM3-101

STOR

NON-SENS

SECURE

RM2-105RM2-104

UNIT STOR

STOR.

COMM

RM2-102

NBC STOR

RM2-103

GEAR STORAGE

TA-50

RM2-100

STOR.

COMM

RM3-102

NBC STOR

RM3-103

GEAR STORAGE

TA-50

UNIT STOR

RM3-104

STOR

NON-SENS

SECURE

RM3-105

VAULT

RM4-101

STOR.

COMM

RM4-102

NBC STOR

RM4-103

GEAR STORAGE

TA-50

RM4-100

RM4-104

UNIT STOR STOR

NON-SENS

SECURE

RM4-105

VAULT

RM5-101

STOR

NON-SENS

SECURE

RM5-105

UNIT STOR

RM5-104

NBC STOR

STOR.

COMM

RM5-102

RM5-103

GEAR STORAGE

TA-50

RM5-100

HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

A R

C H

IT

E C

T U

R

C T

IO

N

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

B

Y L

E R .A

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G

AREA DAREA E

AREA A AREA B AREA C

HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8 HSS12X6X3/8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

HSS

12X

6X3 /8

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

VT-1

RB-1

REM

RB-1

VT-1

SC-1

SC-1

SC-1

CB-1

CT-1

CB-1

CT-1

RB-1

REM

RB-1

REM

CB-1

CT-1

RB-1

VT-1

RB-1

VT-1

CB-1

CT-1

CB-1

CT-1

RB-1

VT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

REM

RB-1

CPT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

CPT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

RB-1

VT-1

SC-1

SC-1

SC-1

SC-1

SC-1 SC-1 SC-1

SC-1

SC-1

SC-1

SC-1 SC-1 SC-1

SC-1

SC-1

SC-1

SC-1 SC-1 SC-1

SC-1

SC-1

SC-1

SC-1 SC-1 SC-1

SC-1

SC-1

SC-1 SC-1

SC-1

ENLARGED FINISH PLAN - AREA B

I-113

H

K

IM

B R

O W

H

K

IM

B R

O W

MATCH LINE

SEE I-115

M A

T

E

S E

E

I-

M A

T

E

S E

E

I-

M A

T

E

S E

E

I-

SEE I-116

MATCH LINE

S E

E

I-

M A

T

E

AREA DAREA E

AREA A AREA B AREA C

E N

L A

R G w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

A R

C H

IT

E C

T U

R

C T

IO

N

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

B

Y L

E R .A

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G

CONFERENCE ROOM

VESTIBULE

100A

CORRIDOR

RECYC.

VENDING

JANITOR

VESTIBULE

103A

MECHANICAL

WOMEN

VESTIBULE

102A

MEN

VESTIBULE

102B

VESTIBULE

103B

COMM

SIPRNET

ELEC

VESTIBULE

100B

CORRIDOR

CONFERENCE ROOM

STORAGE

112A

W18X35 W18X35 W18X35 W18X35

W18X35

W18X35

W18X35

W18X35

RB-1

CPT-1

RB-1

VT-1

RB-1

REM

RB-1

VT-1

SC-1

SC-1

SC-1

CB-1

CT-1

CB-1

CT-1

RB-1

REM

RB-1

REM

CB-1

CT-1

RB-1

VT-1

RB-1

VT-1

CB-1

CT-1

CB-1

CT-1

RB-1

VT-1

RB-1

REM

RB-1

CPT-1

INTERIOR FINISH SCHEDULE

NOT TO SCALE

WOMEN’S RESTROOM

WALL TILE ELEVATIONS

TYPICAL RESTROOM

MEN’S RESTROOM

I-601

IN

T

E R

H E

D U

L E

H

K

IM

B R

O W

H

K

IM

B R

O W

" 4

SCHEDULE FINISH AND MATERIALROOM

NORM NAMEROOM FLOOR BASE

CEILING

NOTES) (SEEREMARKS

NORTH EAST SOUTH WEST

MAT FIN TYPE HGT

FIN

WAINSCOT

FIN

WAINSCOT

FIN

WAINSCOT

FIN

WAINSCOT

FIN HGT FIN HGT FIN HGT FIN HGT

100A VESTIBULE PT -REM PB ACT 9’-0"

100B VESTIBULE PT -REM PB ACT 9’-0"

101 CORRIDOR PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

101A CORRIDOR PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-6"

101B CORRIDOR PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-6"

101C CORRIDOR PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-6"

101D CORRIDOR PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-6"

101E CORRIDOR PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-6"

102 RESTROOMMENS CT CB PNT-1 CWT-1,2,3 6’-2" PNT-1 CWT-1,2,3 6’-2" PNT-1 CWT-1,2,3 6’-2" PNT-1 CWT-1,2,3 6’-2" GWB PNT-4 9’-0"

102A VESTIBULE CT CB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

102B VESTIBULE CT CB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

103 RESTROOMWOMENS CT CB PNT-1 CWT-1,2,4 6’-2" PNT-1 CWT-1,2,4 6’-2" PNT-1 CWT-1,2,4 6’-2" PNT-1 CWT-1,2,4 6’-2" GWB PNT-4 9’-0"

103A VESTIBULE CT CB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

103B VESTIBULE CT CB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

104 RECYCLING VT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

105 VENDING PT PB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

106 JANITOR SC-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

107 MECHANICAL SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4

108 SIPRNET VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

109 COMMUNICATIONS VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 10’-0"

110 ELECTRICAL SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4 9’-0"

112A STORAGE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

112C ROOMCONFERENCE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

113A STORAGE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

113C ROOMCONFERENCE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

114A STORAGE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

114C ROOMCONFERENCE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

115A XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

115B CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

115C ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

115D 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

115E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

116A XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

116B CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

116C ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

116D 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

116E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

117A XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

117B CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

117C ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

117D 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

117E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

118A ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

118B 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

118C XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

118D CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

118E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

155A XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

155B CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

155C ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

155D 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

155E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

156A ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

156B 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

156C XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

156D CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

156E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

157A ROOMTRAINING VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

157B 1SG VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

157C XO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

157D CDR.CO VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

157E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

158A OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

158B OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

158C OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

158D OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

158E STORAGE VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

159 ROOMCONFERENCE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

159A STORAGE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

160 ROOMCONFERENCE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

160A STORAGE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

161 ROOMCONFERENCE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

161A STORAGE CPT RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

100 -RM1 STORAGE GEAR 50 -TA SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4 26’-6"

101 -RM1 VAULT SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

102 -RM1 COMMUNICATIONS SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

103 -RM1 STORAGENBC SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

104 -RM1 STORAGEUNIT SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

105 -RM1 STOR NON-SENSSECURE SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

100 -RM2 STORAGE GEAR 50 -TA SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4 26’-6"

101 -RM2 VAULT SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

202 -RM1 COMMUNICATIONS SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

203 -RM1 STORAGENBC SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

104 -RM2 STORAGEUNIT SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

105 -RM2 STOR NON-SENSSECURE SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

100 -RM3 STORAGE GEAR 50 -TA SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4 26’-6"

101 -RM3 VAULT SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

102 -RM3 COMMUNICATIONS SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

103 -RM3 STORAGENBC SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

104 -RM3 STORAGEUNIT SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

105 -RM3 STOR NON-SENSSECURE SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

100 -RM4 STORAGE GEAR 50 -TA SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4 26’-6"

101 -RM4 VAULT SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

102 -RM4 COMMUNICATIONS SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

103 -RM4 STORAGENBC SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

104RM4- STORAGEUNIT SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

105 -RM4 STOR NON-SENSSECURE SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

100 -RM5 STORAGE GEAR 50 -TA SC PNT-1 PNT-1 PNT-1 PNT-1 EXP PNT-4 26’-6"

101 -RM5 VAULT SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

102 -RM5 COMMUNICATIONS SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

103 -RM5 STORAGENBC SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

104 -RM5 STORAGEUNIT SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

105 -RM5 STOR NON-SENSSECURE SC PNT-1 PNT-1 PNT-1 PNT-1 GWB PNT-4 9’-0"

106 -RM1 OVEVT-1LOW/EXPANSION PNT-1 PNT-1 PNT-1 PNT-1 EXP 9’-0"

107 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

108 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

109 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

110 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

RM1-111 COMM SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

106 -RM2 OVEVT-1LOW/EXPANSION PNT-1 PNT-1 PNT-1 PNT-1 EXP 9’-0"

107 -RM2 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

108 -RM2 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

109 -RM2 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

110 -RM2 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

106 -RM1 OVEVT-1LOW/EXPANSION PNT-1 PNT-1 PNT-1 PNT-1 EXP 9’-0"

107 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

108 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

109 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

110 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

RM1-111 COMM SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

106 -RM1 OVEVT-1LOW/EXPANSION PNT-1 PNT-1 PNT-1 PNT-1 EXP 9’-0"

107 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

108 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

109 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

110 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

RM1-111 COMM SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

106 -RM1 OVEVT-1LOW/EXPANSION PNT-1 PNT-1 PNT-1 PNT-1 EXP 9’-0"

107 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

108 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

109 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

110 -RM1 OFFICEPLATOON VT-1 RB PNT-1 PNT-1 PNT-1 PNT-1 ACT 9’-0"

RM1-111 COMM SC PNT-1 PNT-1 PNT-1 PNT-1 EXP-CON 9’-0"

NOTES:

SCHEDULE. COLOR FOR I-603 SHEET TO REFER1.

VESTIBULES. AND LOBBIES CORRIDORS, ALL IN BE TO GUARDS CORNER2.

(SS). SURFACE SOLID BE SHALL SILLS WINDOW3.

FRONT. WATEVT-1ALL AND BACKSPLASH 4" HAVE TO COUNTERS ALL4.

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

A R

C H

IT

E C

T U

R

C T

IO

N

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

B

Y L

E R .A

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G

PNT-1

CWT-3

CWT-2

PNT-1

CWT-4

CWT-2

TB-1

TB-1

CWT-1

CWT-1

E P

H

IG

E P

H

IG

EL101

IG

H T

A N

F

IR

O

LIGHTING PLAN - FIRST FLOOR AREA A

155A

155B

155C

155D

155E

156A

156B

156E

156C

156D

157A

157B

157E

101E

157C

157D

158A

158B 158D

158C

158E

101D

100A

161A 160A

159A

RM2-100

RM2-101

RM2-103

RM2-102

RM2-104

RM2-105

RM1-101

RM1-102

RM1-104

RM1-103

RM1-105

RM1-100

RM3-101

RM3-100

S S S

NORTH

AREA PLAN

AREA A AREA B

0’8’ 8’ 16’

KEYED NOTES-THIS SHEET ONLY

GENERAL NOTES

SWITCHES SHALL OVERRIDE CONTROLLER OPERATIONS.

OVERRIDE OFF FOR PRESENTATIONS IN CONFERENCE ROOMS. DIMMER

SWITCH LEGS AND CONTROL CIRCUITING.). WALL SWITCH SHALL BE

50FC WHEN ROOM IS OCCUPIED (+/- 5FC. MAY REQUIRE ADDITIONAL

CONTROLLED OPERATION OF LAMPS TO MAINTAIN AN AVERAGE OF

TO FACILITATE OPERATION OF LIGHTING FIXTURES. PROVIDE

PROVIDE DAYLIGHT SENSING/HARVESTING AND OCCUPANCY SENSING

EMERGENCY BALLASTS.

PROVIDE 10AWG FOR EXTERIOR LIGHTING CIRCUITS AND ASSOCIATED

CANOPY

EQUIPED WITH EMERGENCY BATTERY BALLAST

VAULT DOOR LIGHTS SHALL OPERATE 24/7 AND SHALL BE

CIRCUITING) WHEN ROOM IS OCCUPIED.

30FC (+/- 5FC. MAY REQUIRE ADDITIONAL SWITCH LEGS AND CONTROL

CONTROLLED OPERATION OF LAMPS TO MAINTAIN AN AVERAGE OF

TO FACILITATE OPERATION OF LIGHTING FIXTURES. PROVIDE

PROVIDE DAYLIGHT SENSING/HARVESTING AND OCCUPANCY SENSING

MOUNTED LOWER THAN 9’ 0" AFF.

UNDER MEZZ. SHALL BE PENDANT STYLE AND SHALL nOT BE

COVERAGE FOR AREAS BELOW MEZZANINES. SENSORS

POSITION PHOTO/OCCUPANCY SENSORS AS TO PROVIDE UNIFORM

THAN 2’-0" BELOW NEAREST OP/OS CONTROLLED LIGHTING FIXTURE.

4. OP/OS IN ROOMS RM1-100 THRU RM5-100 SHALL BE MOUNTED NO LOWER

PROVIDED IN ACCORDANCE WITH SPECIFICATIONS.

TESTING AND ADJUSTMENTS OF SENSOR NETWORK SHALL BE

VARY IN ORDER TO ACHIEVE UNIFORM ROOM COVERAGE. FIELD

DESIGN PARAMETERS. LOCATION AND QUANTITY REQUIREMENTS MAY

APPROXIMATIONS AND MAY VARY DEPENDING ON MANUFACTURERS

3. LOCATIONS AND QUANTITIES OF OCCUPANCY/PHOTO SENSORS ARE

OF A POWER FAILURE.

BE WIRED SO EMERGENCY OPERATION OCCURS ONLY IN THE EVENT

ADDITIONALLY SUPPLIED WITH AN UNSWITCHED LEG. FIXTURE SHALL

2. ALL FIXTURES DESIGNATED FOR EMERGENCY OPERATION SHALL BE

1. ALL EXIT LIGHTS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

P A

IN

D E

L

M A

T C

H L I

MATCHLINE B

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

E L

E C

T R

IC

C T

IO

N

J A

K

S T

O

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

OS

OP

OP

OP

OP

OP

OS

OS OS OS

OS OS OS

OS

OS OS

OSOS

OS OS

OS

OP OP OP

OP

OP

OP

OS

OP

OS

OP

OS

OP

OS

OP

OS

OP

OS

OP

OS

OSOSOSOS

OP

OP

OP

OP

OP

a a a a b b b b c c c c d dd d e e eOS f f f f f g g g h h h

OS OS

OS

OP

1 1

D

HD-21

HD-14 HD-16

H D

H D

HD-23 HD-24

H C

2 2 2

2 2 2 2 2 2 2 2

J

J

J J

2 23 3

JJ JJ JJ

CIRCUIT CONTINUED ABOVE

EXTERIOR LIGHTING

CIRCUIT CONTINUED BELOW

EXTERIOR LIGHTING

x1 x1 x1 x1 x1 x1 x1x1x1x1x1 x1 x1 x1 x1x1

5 5 5 x1 x1 x2

OS

OS

OS

CONTROLLER

CANOPY TIMER

LIGHTING CONTROLLER

VIA EXTERIOR

H D

HC-3

HC-6

HC-4

OP OP

OP OP

OP

OP OP

OPOP

OP

JJJJJ

OP OP

OP OP OP OP OP OP OP OP

x2

OS

J J

OSOSOSOS

OS

OS

OS

OS

OS

OS

OS OS OS

OSOSOSOS

OS OS

OP

OP

OS

OP

OP

OS

OP

OP

E P

H

IG

E P

H

IG

EL102

IG

H T

A N

F

IR

O

LIGHTING PLAN - FIRST FLOOR AREA B

103A

103B

B

115C

115D

115A

115B

115E

C

C

C

112A 113A

114A

116A

116B

116E

116D

116C

117D

117E

117B

117A 118A

118B

118C

118D

118E

101B 101A

117C

RM5-101

RM5-103

RM5-102

RM5-104

RM5-105

RM5-100

RM4-101

RM4-102

RM4-103

RM4-100

RM4-104

RM4-105RM3-105RM3-102

RM3-103

RM3-104

RM3-100

S S S

NORTH

AREA PLAN

AREA A AREA B

0’8’ 8’ 16’

KEYED NOTES-THIS SHEET ONLY

GENERAL NOTES

CANOPY

ASSOCIATED EMERGENCY BALLAST.

PROVIDE 10AWG FOR EXTERIOR LIGHTING CIRCUITS AND

OCCUPIED.

SWITCH LEGS AND CONTROL CIRCUITING WHEN ROOM IS

AN AVERAGE OF 30FC(+/- 5FC). MAY REQUIRE ADDITIONAL

PROVIDE CONTROLLED OPERATION OF LAMPS TO MAINTAIN

SENSING TO FACILITATE OPERATION OF LIGHTING FIXTURES.

PROVIDE DAYLIGHT SENSING/HARVESTING AND OCCUPANCY

SWITCHES SHALL OVERRIDE CONTROLLER OPERATIONS.

PRESENTATIONS IN CONFERENCE ROOMS. DIMMER

OCCUPIED. WALL SWITCH SHALL BE OVERRIDE OFF FOR

SWITCH LEGS AND CONTROL CIRCUITING WHEN ROOM IS

AN AVERAGE OF 50FC (+/- 5FC). MAY REQUIRE ADDITIONAL

PROVIDE CONTROLLED OPERATION OF LAMPS TO MAINTAIN

SENSING TO FACILITATE OPERATION OF LIGHTING FIXTURES.

PROVIDE DAYLIGHT SENSING/HARVESTING AND OCCUPANCY

SHALL NOT BE MOUNTED LOWER THAN 9’-0" AFF.

AND SENSORS UNDER MEZZ. SHALL BE PENDANT STYLE AND

UNIFORM COVERAGE FOR AREAS BELOW MEZZANINES. LIGHTS

POSITION PHOTO/OCCUPANCY SENSORS AS TO PROVIDE

THAN 2’-0" BELOW NEAREST OP/OS CONTROLLED LIGHTING FIXTURE.

4. OP/OS IN ROOMS RM1-100 THRU RM5-100 SHALL BE MOUNTED NO LOWER

PROVIDED IN ACCORDANCE WITH SPECIFICATIONS.

TESTING AND ADJUSTMENTS OF SENSOR NETWORK SHALL BE

VARY IN ORDER TO ACHIEVE UNIFORM ROOM COVERAGE. FIELD

DESIGN PARAMETERS. LOCATION AND QUANTITY REQUIREMENTS MAY

APPROXIMATIONS AND MAY VARY DEPENDING ON MANUFACTURERS

3. LOCATIONS AND QUANTITIES OF OCCUPANCY/PHOTO SENSORS ARE

OF A POWER FAILURE.

BE WIRED SO EMERGENCY OPERATION OCCURS ONLY IN THE EVENT

ADDITIONALLY SUPPLIED WITH AN UNSWITCHED LEG. FIXTURE SHALL

2. ALL FIXTURES DESIGNATED FOR EMERGENCY OPERATION SHALL BE

1. ALL EXIT LIGHTS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

EQUIPPED WITH EMERGENCY BATTERY BALLAST

VAULT DOOR LIGHTS SHALL OPERATE 24/7 AND SHALL BE

P A

IN

D E

L

OS

OS

OS

OS OP

OP

OP

OP

OP

OP

OP

OP

OP

h h h i i i i ii j j k k k k l l m m m m n n n n

OP

OS

OP

OS

OP

1 1 1

HD-24 HE-18 HE-15

H E

HE-16

H C

HE-14

HC-5

2 2

2 2 2 2 2 2 2 2

J

JJJJJJ

23 3 3

JJ JJ JJ

CIRCUIT CONTINUED BELOW

EXTERIOR LIGHTING

CIRCUIT CONTINUED ABOVE

EXTERIOR LIGHTING

x1 x1 x1 x1 x1 x1 x1x1x1 x1 x1 x1 x1 x1 x1 x1 x1 x1 x1

CONTROLLER

CANOPY TIMER

CONTROLLER

EXTERIOR LIGHTING

SEE LIGHTING CONTROLS DETAIL SHEET EL503

HC-8 VIA EXTERIOR LIGHTING CONTROLLER

HC-14

H E l

M A

T C

H L I

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

E L

E C

T R

IC

C T

IO

N

J A

S T

O

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G

OP

OP

OP

OP OP

OP

OP

OP OP

LRM2

GFI

GFI

GFI

GFI

GFI

GFIGFI

GFIGFI

GFI

GFI

GFIGFI

GFI

GFI

WP GFI

WP GFI

WP GFI

WP GFI

WP GFI

WPGFI

WP GFI

WP GFI

T V T

V

TV TV

TV TV

TV TV

TV

TV TV

TV

TV TV

TV TV

TV TV

TV TV TV

LRM1 LRM3

GFI

HD

LD

GFI GFI GFI GFI GFI GFI

GFI

GFI

S SS

E P

H

IG

H T

S T

E P

H

IG

H T

P A

IN

D E

L

EP101

F

IR

O

RM1-101

RM1-103

RM1-102

RM1-104

RM1-105

RM2-101

RM1-100

RM2-103

RM2-104

RM2-100

RM2-102

RM2-105

RM3-101

RM3-100

155A

155B

155E 156E

155C 156A

155D 156B 156D

156C

101E

157A

157B 157D

157C 158A

158B

158E157E

159A 160A

101D

161A

158C

158D 159 160

100A

102 103

P O

W

A N

1/8"=1’-0"

NORTH

POWER PLAN - FIRST FLOOR AREA A

AREA PLAN

AREA A AREA B

KEYED NOTES-THIS SHEET ONLY

ABOVE ARMS VAULT.

SERVICE RECEPTACLE MOUNTED NEAR HVAC EQUIPMENT

1 1

6 6

FUTURE PODIUM LOCATION.

9 9

ADJACENT TO BOOTWASH WITH C.O.R..

COORDINATE MOUNTING HEIGHT OF GFI RECEPTACLE

5 5

0’8’ 8’ 16’

CANOPY

SM SM SM

10 10 10

SEE SERVICE MODULE DETAILS SHEET ET501.

EACH OTHER.

CAGED ROOMS. ADJACENT JBOXES SHALL BE SECURED TO

POSITION RECEPTACLES JBOXES BACK-TO-BACK IN MESH STEEL

MIN SLACK AND COIL IN JBOX.

IDS CAM JBOX. MOUNT 10’-0"AFF. PROVIDE 12" OF COAXIAL CABLE

OF A/V CONDUIT WITH C.O.R..

PROJECTOR AND PODIUM. COORDINATE EXACT TERMINATION

CONDUIT FOR A/V CONDUCTORS TO BE ROUTED BETWEEN

ACCESSIBLE LOCATION ABOVE CEILING GRID. PROVIDE 1-1/2"

RECEPTACLE FOR GFGI PROJECTOR. MOUNT SECURELY IN

PROVIDE PULL CABLES IN ALL CONDUIT.

EY501 FOR TYPICAL ARMS ROOM AND SIPR LAYOUT.

JBOX FOR IDS CONTROL PANEL POWER. REFER TO SHEET

MOUNT SWITCH AT 4’-0" AFF.

CONTROL. MOUNT RECEPTACLE SECURELY ABOVE CEILING TILES.

RECEPTACLE FOR MOTERIZED SCREEN AND SWITCH FOR POSITION

TO CATV OUTLET.

MOUNT CATV DUPLEX RECEPTACLES AT 7’-0" AFF AND ADJACENT

M A

T C

H L I

10HP

2ERV-R1

2OAL-R1 RM1-100B

2EAL-R1

2CRACO-R1

2WSHP-R1

2WH-R1

2OAL-R2

RM2-100B

2EAL-R2

2ERV-R2

2WSHP-R2

2WH-R2

2OAL-R3

RM3-100B

2ERV-R3

2WSHP-R3

2WH-R3

FLWS-RM2FLWS-RM1

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

E L

E C

T R

IC

C T

IO

N

J A

S T

O

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

LRM1-13,15,17

LRM1-19,21,23

LRM1-10,12

LRM2-13,15,17

LRM2-14,16,18

LRM2-20,22,24

LRM2-10,12

LRM1-2,4,6

L R

M

L R

M

L R

M

LRM2-2,4,6

L R

M

L R

M

L R

M

LRM3-2,4,6

L R

M

LRM3-19,21,23

LRM3-25,27,29

LD-1,3,5

LRM1-14,16,18

LRM1-25,27,29

M

1,3

1,3

1,3

4,6

4,6

4,6

13,15

25,27

16,1816

22,2422

13,15

16,18

13 21,23

27,29

LRM3-13,15

LRM1-31

LRM1-33

HF-2

HF-7

HD-1

HD-2

HF-13

HF-14

LD-2 LD-4

LD-6

LC2-2

J J J

H C

H C

C

LD-13LD-8

TM

LC1

LRM5

GFI

GFI

GFI

GFI

GFI

WPGFI

WP GFI

WP GFI WP GFI

WP GFI

WP GFI

WP GFI

WP GFI

T V

T V

T V

TV TV

TV TV

TV TV

TV TV

TV TV

TV TV

TV TV

TV TV

TV TVTV

LRM3 LRM4

GFI

LA

HA

H B

HC

HE

L B

SPD

-H

LD HF

M

A T

C H

L

GFI

GFI

GFI

GFIGFI GFI GFI GFI GFI

S S S

E P

H

IG

E P

H

IG

EP102

O

W

A N

F

IR

O

POWER PLAN - FIRST FLOOR AREA B

RM3-102

RM3-103

RM3-104

RM3-105 RM4-101

RM3-100 RM4-100

RM4-103

RM4-102

RM4-104

RM4-105

RM5-101

RM5-103

RM5-104

RM5-102

RM5-105

RM5-100

118C

118D

118E117E116E

117D 118B

118A117C

101A

116C 117A

117B 116D

115C

116A

116B

115D115B

115A

114C113C112C

112A 113A 114A

101B

103A

103B

100B

1/8"=1’-0"

NORTH

AREA PLAN

AREA A AREA B

KEYED NOTES-THIS SHEET ONLY

ABOVE ARMS VAULT.

SERVICE RECEPTACLE MOUNTED NEAR HVAC EQUIPMENT

QUADRAPLEX RECEPTACLE LOCATED AT EACH EQUIPMENT RACK.

5 5 5

FUTURE PODIUM LOCATION.

9 9 9 4 4

1 11

10 10

7 7

7 7

ADJACENT TO BOOTWASH WITH C.O.R..

COORDINATE MOUNTING HEIGHT OF GFI RECEPTACLE

0’8’ 8’ 16’

CANOPY

SM SM SM

13 13 13

RM3-100B

P A

IN

D E

L

OF A/V CONDUIT WITH C.O.R..

PROJECTOR AND PODIUM. COORDINATE EXACT TERMINATION

CONDUIT FOR A/V CONDUCTORS TO BE ROUTED BETWEEN

ACCESSIBLE LOCATION ABOVE CEILING GRID. PROVIDE 1-1/2"

RECEPTACLE FOR GFGI PROJECTOR. MOUNT SECURELY IN

TO CATV OUTLET.

MOUNT CATV DUPLEX RECEPTACLES AT 9’-0" AFF AND ADJACENT

EACH OTHER.

CAGED ROOMS. ADJACENT J-BOXES SHALL BE SECURED TO

POSITION RECEPTACLE JBOXES BACK-TO-BACK IN MESH STEEL

SEE SERVICE MODULES DETAILS SHEET ET501.

NEMA 1, 12"x12"x4".

ILON 600 SMARTSERVER EQUIPMENT ENCLOSURE.

PROVIDE PULL CABLES IN ALL CONDUIT.

EY501 FOR TYPICAL ARMS ROOM AND SIPR LAYOUT.

JBOX FOR IDS CONTROL PANEL POWER. REFER TO SHEET

OF COAXIAL CABLE AND COIL IN JBOX.

IDS CAM JBOX. MOUNT 10’-0" AFF. PROVIDE 12" MIN SLACK

EQUIPMENT ENCLOSURE.

NEMA 1, 8"x10"x4". PROVIDE 1" C TO ILON 600

WATTNODE ELECTRIC METER ENCLOSURES.

CEILING TILES. MOUNT SWITCH AT 4’-0" AFF.

POSITION CONTROL. MOUNT RECEPTACLE SECURELY ABOVE

RECEPTACLE FOR MOTERIZED SCREEN AND SWITCH FOR

LRM3-2,4,6

L R

M

L R

M

LRM4-2,4,6

L R

M

L R

M

L R

M

LRM5-2,4,6

L R

M

L R

M

L R

M

LRM3-25,27,29

LRM4-10,12

LB-2

L R

M

LRM4-20,22,24

LRM5-10,12

LRM5-13,15

LRM5-19,21,23

LRM5-14,16,18

LRM5-25,27

LRM4-19,21,23

M

1,3

1,3

1,3

4,6

4,6

27,29

LRM3-13,15

L C

16,18

22,24 24

21,23

14 18

LRM5-29

LD-11 LRM5-31

HE-1

HE-2

HF-19

LD-7 LD-9

LC3-2

LC1-1,3,5

J J J

LC1-7

PLAN SHEET EP401

SEE ENLARGED MECH.

S P

D

H H

B

HA HC

LB

LA

TM

L C

3,5

H C

H C

2CRACO2

2OAL-R3

RM3-100B

2EAL-R3

2OAL-R4

RM4-100B

2EAL-R4

2WSHP-R4

2ERV-R4

2WH-R4

2OAL-R5

RM5-100B

2WSHP-R5

2EAL-R5

2WH-R5

LC1-11

2,4

2ERV-R5

2CRACO-R5

HF-8

LD-14 LD-19 LD-20

FLWS-RM5FLWS-RM4FLWS-RM3

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

E L

E C

T R

IC

C T

IO

N

J A

S T

O

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

IN

G

M A

T C

H L I

LRM3-2,4,6

L R

M

L R

M

LRM4-2,4,6

L R

M

L R

M

L R

M

LRM5-2,4,6

L R

M

L R

M

L R

M

LRM3-25,27,29

LRM4-10,12

LB-2

L R

M

LRM4-20,22,24

LRM5-10,12

LRM5-13,15

LRM5-19,21,23

LRM5-14,16,18

LRM5-25,27

LRM4-19,21,23

M

1,3

1,3

1,3

4,6

4,6

27,29

LRM3-13,15

L C

16,18

22,24 24

21,23

14 18

LRM5-29

LD-11 LRM5-31

HE-1

HE-2

HF-19

LD-7 LD-9

LC3-2

LC1-1,3,5

J J J

LC1-7

PLAN SHEET EP401

SEE ENLARGED MECH.

S P

D

H H

B

HA HC

LB

LA

TM

L C

3,5

H C

H C

2CRACO2

2OAL-R3

RM3-100B

2EAL-R3

2OAL-R4

RM4-100B

2EAL-R4

2WSHP-R4

2ERV-R4

2WH-R4

2OAL-R5

RM5-100B

2WSHP-R5

2EAL-R5

2WH-R5

LC1-11

2,4

2ERV-R5

2CRACO-R5

HF-8

LD-14 LD-19 LD-20

FLWS-RM5FLWS-RM4FLWS-RM3

E P

H

IG

H T

S T

E P

H

IG

H T

P A

IN

D E

L

EP701

P A

N E

L B

O A

H E

D U

L

O

W

HBPANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts277/480 Only Lugs Main225A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

80 3 2WWHP-1 WATER TOWATER 13169 2

13169 2WWHP-2 WATER TOWATER 80 3

3 - - - 13169 4 13169 - - -

5 - - - 13169 6 13169 - - -

7 20 3 2CWP- BOO WATERCONDENDER 942 8

942 2CWP- BOO WATERCONDENDER 20 3

9 - - - 942 10 942 - - -

11 - - - 942 12 942 - - -

13 25 3 2AHU-1AIR 3104 14

3104 2AHU-2AIR 25 3

15 - - - 3104 16 3104 - - -

17 - - - 3104 18 3104 - - -

19 20 3 2CHP- COOLING ANDHEATING 721 20

721 2CHP- COOLING ANDHEATING 20 3

21 - - - 721 22 721 - - -

23 - - - 721 24 721 - - -

25 15 3 2ERV- REC ENERGY SIDEAIR 2550 26

2550 2ERV- REC ENERGY SIDEAIR 15 3

27 - - - 2550 28 2550 - - -

29 - - - 2550 30 2550 - - -

31 20 3 2EF-1 FANEXHAUST 277 32

0 3P) - (20A ONLYSPACE - 3

33 - - - 277 34

35 - - - 277 36

TOTAL 41249 41249 41249

KVA 123.7 LOAD CONNECTEDTOTAL

148.8 AMPSDEMAND

KVA 123.7 LOAD DEMANDTOTAL

HCPANEL

RATING INTERRUPTING MINIMUM AMPS 14599

Wire 4 Phase 3 Volts277/480 Only Lugs Main225A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 ROOMS CONFLIGHTING 1464 2

1464 ROOMS CONFLIGHTING 20 1

3 20 1 RESTROOMSLIGHTING 456 4

704 CORIDOORLIGHTING 20 1

5 20 1 SIPR TR ELEC MECHLIGHTING 1156 6

736 CORIDOORLIGHTING 20 1

7 30 3 2WH-R1 8000 8

828 EXTERIORLIGHTING 20 1

9 - - - 8000 10

1000 SPARE 20 1

11 - - - 8000 12

1000 SPARE 20 1

13 30 3 2WH-R2 8000 14

1000 CONTROLLERLIGHTING 20 1

15 - - - 8000 16

1000 SPARE 20 1

17 - - - 8000 18

1000 SPARE 20 1

19 30 3 2WH-R3 8000 20

8000 2WH-R5 30 3

21 - - - 8000 22 8000 - - -

23 - - - 8000 24 8000 - - -

25 30 3 2WH-R4 8000 26

2000 SPARE 20 3

27 20 - - 8000 28 2000 - - -

29 - - - 8000 30 2000 - - -

TOTAL 46756 45160 45892

KVA 137.8 LOAD CONNECTEDTOTAL

165.8 AMPSDEMAND

KVA 137.8 LOAD DEMANDTOTAL

HFPANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts277/480 Breaker Circuit Main125A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 300 2

2550 2ERV-R2 RE ENERGY SIDEAIR 15 3

3 20 1 300 4 2550 - - -

5 20 1 SPARE 1000 6

2550 - - -

7 40 3 2WSHP-R2 HEAT SOURCEWATER 7316 8

7316 2WSHP-R4 HEAT SOURCEWATER 40 3

9 - - - 7316 10 7316 - - -

11 - - - 7316 12 7316 - - -

13 15 3 2ERV-R3 RE ENERGY SIDEAIR 2550 14

7316 2WSHP-R3 HEAT SOURCEWATER 40 3

15 - - - 2550 16 7316 - - -

17 - - - 2550 18 7316 - - -

19 15 3 2550 20 1000 15 3

21 - - - 2550 22 1000 - - -

23 - - - 2550 24 1000 - - -

25 20 1 LIGHTSCANOPY 500 26

0 1P) - (20A ONLYSPACE - 1

27 20 1 CONTROLLER LIGHTINGCANOPY 100 28

0 1P) - (20A ONLYSPACE - 1

29 - 1 1P) - (20A ONLYSPACE 0 30

0 1P) - (20A ONLYSPACE - 1

TOTAL 31398 30998 31598

KVA 94 LOAD CONNECTEDTOTAL

113.1 AMPSDEMAND

KVA 94 LOAD DEMANDTOTAL

LAPANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Breaker Circuit Main800A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

70 3 LBPANEL 2504 2

11696 LRM1PANEL 110 3

3 - - - 2696 4 11932 - - -

5 - - - 2776 6 10888 - - -

7 110 3 LC1PANEL 4000 8

11380 LRM2PANEL 110 3

9 - - - 4270 10 10696 - - -

11 - - - 2720 12 10888 - - -

13 110 3 LC2PANEL 3915 14

11120 LRM3PANEL 110 3

15 - - - 3455 16 9884 - - -

17 - - - 2000 18 10860 - - -

19 110 3 LC3PANEL 3915 20

10728 LRM4PANEL 110 3

21 - - - 3455 22 10516 - - -

23 - - - 4000 24 11440 - - -

25 450 3 LDPANEL 37807 26

12360 LRM5PANEL 110 3

27 - - - 37807 28 11596 - - -

29 - - - 38807 30 11380 - - -

31 - 3 3P) - (20A ONLYSPACE 0 32

0 3P) - (20A ONLYSPACE - 3

33 - - - 0 34 0 - - -

35 - - - 0 36 0 - - -

TOTAL 10942 106307 105759

KVA 321.5 LOAD CONNECTEDTOTAL

728.6 AMPSDEMAND

KVA 262.5 LOAD DEMANDTOTAL

LBPANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 ALARMFIRE 1000 2

1000 SPARE 20 1

3 20 1 MNS 1000 4

1000 20 1

5 20 1 RECEPTACLESDUPLEX 1080 6

1000 SPARE 20 1

7 15 1 2B-1 BOILERCONDENSING 504 8

0 1P) - (20A ONLYSPACE - 1

9 20 1 2EAL-1EXHAUST 696 10

0 1P) - (20A ONLYSPACE - 1

11 20 1 2OAL-1 AIROUTSID 696

TOTAL 2504 2696 2776

KVA 8 LOAD CONNECTEDTOTAL

22.1 AMPSDEMAND

KVA 8 LOAD DEMANDTOTAL

LC1PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Breaker Circuit Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RECEPTACLESDUPLEX 720 2

450 RECEPTACLESDUPLEX 20 1

3 20 1 RECEPTACLESDUPLEX 720 4

720 RECEPTACLESDUPLEX 20 1

5 20 1 RECEPTACLESDUPLEX 720 6

1000 IDSSIPR 20 1

7 25 2 2CRACO1 RO0 COMPUTERSIPER 915 8

915 2CRACO2 COND RO0MCOMPUTER 25 2

9 - - - 915 10 915 - - -

11 - 1 1P) - (20A ONLYSPACE 0 12

0 1P) - (20A ONLYSPACE - 1

13 20 1 SPARE 1000 14

0 1P) - (20A ONLYSPACE - 1

15 20 1 SPARE 1000 16

0 1P) - (20A ONLYSPACE - 1

17 20 1 SPARE 1000

TOTAL 4000 4270 2720

KVA 11 LOAD CONNECTEDTOTAL

30.5 AMPSDEMAND

KVA 11 LOAD DEMANDTOTAL

HEPANEL

RATING INTERRUPTING MINIMUM AMPS 10557

Wire 4 Phase 3 Volts277/480 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

15 3 2ERV-R RE ENERGY SIDEAIR 2550 2

7316 2WSHP-R HEAT SOURCEWATER 40 3

3 - - - 2550 4 7316 - - -

5 - - - 2550 6 7316 - - -

7 20 3 2WSHP-R4 HEA SOURCEWATER 277 8

277 2WSHP-R5 HEA SOURCEWATER 20 3

9 - - - 277 10 277 - - -

11 - - - 277 12 277 - - -

13 20 1 LIGHTING 1088 14

1152 LIGHTING 20 1

15 20 1 LIGHTING 3548 16

1152 LIGHTING 20 1

17 20 1 LIGHTING 1088 18

3548 LIGHTING 20 1

19 20 3 1000 20 1000 20 3

21 - - - 1000 22 1000 - - -

23 - - - 1000 24 1000 - -

TOTAL 14660 17120 17056

KVA 48.8 LOAD CONNECTEDTOTAL

58.7 AMPSDEMAND

KVA 48.8 LOAD DEMANDTOTAL

HDPANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts277/480 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

15 3 2ERV-R RE ENERGY SIDEAIR 2550 2

7316 2WSHP-R HEAT SOURCEWATER 40 3

3 - - - 2550 4 7316 - - -

5 - - - 2550 6 7316 - - -

7 20 3 2WSHP-R1 HEA SOURCEWATER 277 8

277 2WSHP-R3 HEA SOURCEWATER 20 3

9 - - - 277 10 277 - - -

11 - - - 277 12 277 - - -

13 20 3 2WSHP-R2 HEA SOURCEWATER 277 14

1152 LIGHTING 20 1

15 - - - 277 16

1152 LIGHTING 20 1

17 - - - 277 18

1088 LIGHTING 20 1

19 20 1 LIGHTING 1088 20

1088 LIGHTING 20 1

21 20 1 LIGHTING 3548 22

1000 SPARE 20 1

23 20 1 LIGHTING 3548 24

3548 LIGHTING 20 1

25 20 1 SPARE 1000 26

1000 SPARE 20 1

27 20 1 1000 28

1000 SPARE 20 1

29 - 1 1P) - (20A ONLYSPACE 0 30

1000 SPARE 20 1

TOTAL 16025 18397 19881

KVA 54.3 LOAD CONNECTEDTOTAL

65.3 AMPSDEMAND

KVA 54.3 LOAD DEMANDTOTAL

HAPANEL

RATING INTERRUPTING MINIMUM AMPS 16055

Wire 4 Phase 3 Volts277/480 Breaker Circuit Main1000A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

200 3 HBPANEL 41249 2

46756 HCPANEL 175 3

3 - - - 41249 4 45160 - - -

5 - - - 41249 6 45892 - - -

7 110 3 HDPANEL 16025 8

14660 HEPANEL 110 3

9 - - - 18397 10 17120 - - -

11 - - - 19881 12 17056 - - -

13 150 3 HFPANEL 31398 14

0 SPD 100 3

15 - - - 30998 16 0 - - -

17 - - - 31598 18 0 - - -

19 350 3 TMTRANSFORMER 109425 20

0 1P) - (20A ONLYSPACE - 1

21 - - - 106307 22

0 1P) - (20A ONLYSPACE - 1

23 - - - 105759 24

0 1P) - (20A ONLYSPACE 350 1

25 - 1 1P) - (20A ONLYSPACE 0 26

0 1P) - (20A ONLYSPACE - 1

27 - 1 1P) - (20A ONLYSPACE 0 28

0 1P) - (20A ONLYSPACE - 1

29 - 1 1P) - (20A ONLYSPACE 0 30

0 1P) - (20A ONLYSPACE - 1

TOTAL 26544 265161267365

KVA 798 LOAD CONNECTEDTOTAL

888.8 AMPSDEMAND

KVA 739 LOAD DEMANDTOTAL

LIGHTING

WH

LIGHTING

LIGHTING SITE

LIGHTING SITE

20 2

20 2

AIR SIDE ENERGY RE 2ERV-R4

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

E L

E C

T R

IC

C T

IO

N

J A

S T

O

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

EP702

T

E P

H

IG

H T

S T

E P

H

IG

H T

P A

IN

D E

L

P A

N E

L B

O A

H E

D U

L

O

W

LC2PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Breaker Circuit Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RECEPTACLESDUPLEX 1000 2

915 2CRACO-R1 CO RO0MCOMPUTER 25 2

3 20 1 RECEPTACLESDUPLEX 540 4

915 - - -

5 30 1 SPARE 1000 6

1000 SPARE 20 1

7 20 1 SPARE 1000 8

1000 SPARE 20 1

9 20 1 SPARE 1000 10

1000 SPARE 20 1

TOTAL 3915 3455 2000

KVA 9.4 LOAD CONNECTEDTOTAL

26 AMPSDEMAND

KVA 9.4 LOAD DEMANDTOTAL

LC3PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Breaker Circuit Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RECEPTACLESDUPLEX 1000 2

915 2CRACO-R5 CO RO0MCOMPUTER 25 2

3 20 1 RECEPTACLESDUPLEX 540 4

915 - - -

5 20 1 SPARE 1000 6

1000 SPARE 20 1

7 20 1 SPARE 1000 8

1000 SPARE 20 1

9 20 1 SPARE 1000 10

1000 SPARE 20 1

11 20 1 SPARE 1000 12

1000 SPARE 20 1

TOTAL 3915 3455 4000

KVA 11.4 LOAD CONNECTEDTOTAL

31.6 AMPSDEMAND

KVA 11.4 LOAD DEMANDTOTAL

LDPANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Breaker Circuit Main400A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 CANOPY RECEPTACLESDUPLEX 1080 2

696 2OAL-R2 AIROUTSIDE 20 1

3 20 1 CANOPY RECEPTACLESDUPLEX 1080 4

696 2EAL-R2EXHAUST 20 1

5 20 1 CANOPY RECEPTACLESDUPLEX 1080 6

696 2OAL-R3 AIROUTSIDE 20 1

7 20 1 2EAL-R3EXHAUST 696 8

6667 FLWS-RM1 70 3

9 20 1 2OAL-R4 AIROUTSID 696 10

6667 - - -

11 20 1 2EAL-R4EXHAUST 696 12

6667 - - -

13 70 3 FLWS-RM2 6667 14

6667 FLWS-RM3 70 3

15 - - - 6667 16 6667 - - -

17 - - - 6667 18 6667 - - -

19 70 3 FLWS-RM4 6667 20

6667 FLWS-RM5 70 3

21 - - - 6667 22 6667 - - -

23 - - - 6667 24 6667 - - -

25 20 1 SPARE 1000 26

1000 SPARE 20 1

27 20 1 SPARE 1000 28

1000 SPARE 20 1

29 20 1 SPARE 1000 30

1000 SPARE 20 1

TOTAL 37807 37807 38807

KVA 114.4 LOAD CONNECTEDTOTAL

317.6 AMPSDEMAND

KVA 114.4 LOAD DEMANDTOTAL

LRM1PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 JBOXIDS 1000 2

1080 RECEPTACLESDUPLEX 20 1

3 20 1 RM1-100B DOOR UPROLL 696 4

1080 RECEPTACLESDUPLEX 20 1

5 20 1 CAMRM1 1260 6

1260 RECEPTACLESDUPLEX 20 1

7 20 1 RECEPTACLESDUPLEX 1080 8

540 RECEPTACLESDUPLEX 20 1

9 20 1 RECEPTACLESDUPLEX 1080 10

1080 RECEPTACLESDUPLEX 20 1

11 20 1 RECEPTACLESDUPLEX 1260 12

1080 RECEPTACLESDUPLEX 20 1

13 20 1 RECEPTACLESDUPLEX 1080 14

1080 RECEPTACLESDUPLEX 20 1

15 20 1 RECEPTACLESDUPLEX 1080 16

1080 RECEPTACLESDUPLEX 20 1

17 20 1 RECEPTACLESDUPLEX 900 18

720 RECEPTACLESDUPLEX 20 1

19 20 1 RECEPTACLESDUPLEX 900 20

1080 RECEPTACLESDUPLEX 20 1

21 20 1 RECEPTACLESDUPLEX 1080 22

1080 RECEPTACLESDUPLEX 20 1

23 20 1 RECEPTACLESDUPLEX 1080 24

1080 RECEPTACLESDUPLEX 20 1

25 20 1 RECEPTACLESDUPLEX 1080 26

1080 RECEPTACLESDUPLEX 20 1

27 20 1 RECEPTACLESDUPLEX 900 28

1080 RECEPTACLESDUPLEX 20 1

29 20 1 RECEPTACLESDUPLEX 720 30

528 2EF-R1 VAULT FANEXHAUST 20 1

31 20 1 2OAL-R1 AIROUTSID 696 32

1000 SPARE 20 1

33 20 1 2EAL-R1EXHAUST 696 34

1000 SPARE 20 1

35 20 1 SPARE 1000

TOTAL 11696 11932 10888

KVA 34.5 LOAD CONNECTEDTOTAL

72.9 AMPSDEMAND

KVA 26.3 LOAD DEMANDTOTAL

LRM2PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RM2 CONTROLIDS 1000 2

1080 RECEPTACLESDUPLEX 30 1

3 20 1 RM2-100B DOOR UPROLL 696 4

1080 RECEPTACLESDUPLEX 20 1

5 20 1 RM2 CAMIDS 1260 6

1260 RECEPTACLESDUPLEX 20 1

7 20 1 RECEPTACLESDUPLEX 1260 8

540 RECEPTACLESDUPLEX 20 1

9 20 1 RECEPTACLESDUPLEX 1260 10

1260 RECEPTACLESDUPLEX 20 1

11 20 1 RECEPTACLESDUPLEX 1080 12

1260 RECEPTACLESDUPLEX 20 1

13 20 1 RECEPTACLESDUPLEX 1080 14

1000 20 1

15 20 1 RECEPTACLESDUPLEX 1080 16

1080 20 1

17 20 1 RECEPTACLESDUPLEX 1260 18

1080 PROJECTOR 20 1

19 20 1 RECEPTACLESDUPLEX 1080 20

1260 161 RM 1 + MODULESERVICE 20 1

21 20 1 RECEPTACLESDUPLEX 1080 22

1080 159 RM 1 + MODULESERVICE 20 1

23 20 1 2EF-R2 VAULT FANEXHAUST 528 24

1080 160 RM MODULESERVICE 20 1

25 20 1 RECEPTACLESDUPLEX 1080 26

1000 SPARE 20 1

27 20 1 RECEPTACLESDUPLEX 1080 28

1000 SPARE 20 1

29 20 1 RECEPTACLESDUPLEX 1080 30

1000 SPARE 20 1

31 20 1 SPARE 1000 32

0 1P) - (20A ONLYSPACE - 1

33 - 1 1P) - (20A ONLYSPACE 0 34

0 1P) - (20A ONLYSPACE - 1

35 - 1 1P) - (20A ONLYSPACE 0 36

0 1P) - (20A ONLYSPACE - 1

37 - 1 1P) - (20A ONLYSPACE 0 38

0 1P) - (20A ONLYSPACE - 1

39 - 1 1P) - (20A ONLYSPACE 0 40

0 1P) - (20A ONLYSPACE - 1

41 - 1 1P) - (20A ONLYSPACE 0 42

0 1P) - (20A ONLYSPACE - 1

TOTAL 11380 10696 10888

KVA 33 LOAD CONNECTEDTOTAL

78.9 AMPSDEMAND

KVA 28.4 LOAD DEMANDTOTAL

LRM3PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RM3 CONTROLIDS 1000 2

1080 RECEPTACLESDUPLEX 20 1

3 20 1 RM3-100B DOOR UPROLL 696 4

1080 RECEPTACLESDUPLEX 20 1

5 20 1 RM3 CAMIDS 1260 6

1260 RECEPTACLESDUPLEX 20 1

7 20 1 RECEPTACLESDUPLEX 1080 8

540 RECEPTACLESDUPLEX 20 1

9 20 1 RECEPTACLESDUPLEX 1080 10

528 2EF-R3 VAULT FANEXHAUST 20 1

11 20 1 RECEPTACLESDUPLEX 1260 12

1000 SPARE 20 1

13 20 1 RECEPTACLESDUPLEX 1260 14

1080 RECEPTACLESDUPLEX 20 1

15 20 1 RECEPTACLESDUPLEX 1260 16

1080 RECEPTACLESDUPLEX 20 1

17 20 1 SPARE 1000 18

1080 RECEPTACLESDUPLEX 20 1

19 20 1 VENDING RECEPTACLESDUPLEX 1000 20

1080 20 1

21 20 1 VENDING RECEPTACLESDUPLEX 1080 22

1080 LIGHTING 20 1

23 20 1 COOLER H20 RECEPTACLESDUPLEX 1000 24

1000 20 1

25 20 1 VENDING 1000 26

1000 SPARE 20 1

27 20 1 VENDING 1000 28

1000 SPARE 20 1

29 20 1 VENDING 1000 30

1000 SPARE 20 1

TOTAL 11120 9884 10860

KVA 31.9 LOAD CONNECTEDTOTAL

74.4 AMPSDEMAND

KVA 26.8 LOAD DEMANDTOTAL

LRM4PANEL

RATING INTERRUPTING MINIMUM AMPS 10000

Wire 4 Phase 3 Volts120/208 Only Lugs Main100A

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RM4 CONTROLIDS 1000 2

1080 RECEPTACLESDUPLEX 20 1

3 20 1 RM4-100B DOOR UPROLL 696 4

1080 RECEPTACLESDUPLEX 20 1

5 20 1 RM4 CAMIDS 1260 6

1260 RECEPTACLESDUPLEX 20 1

7 20 1 RECEPTACLESDUPLEX 1080 8

540 RECEPTACLESDUPLEX 20 1

9 20 1 RECEPTACLESDUPLEX 1080 10

1080 RECEPTACLESDUPLEX 20 1

11 20 1 RECEPTACLESDUPLEX 1080 12

1260 RECEPTACLESDUPLEX 20 1

13 20 1 2EF-R4 VAULT FANEXHAUST 528 14

1080 PROJECTOR RECEPTACLESDUPLEX 20 1

15 - 1 RECEPTACLESDUPLEX 1080 16

1080 PROJECTOR RECEPTACLESDUPLEX 20 1

17 - 1 RECEPTACLESDUPLEX 1080 18

1080 PROJECTOR RECEPTACLESDUPLEX 20 1

19 20 1 RECEPTACLESDUPLEX 1260 20

1080 112C RM SM RECEPTACLESDUPLEX 20 1

21 20 1 RECEPTACLESDUPLEX 1260 22

1080 113C RM SM RECEPTACLESDUPLEX 20 1

23 20 1 RECEPTACLESDUPLEX 1260 24

1080 114C RM SM RECEPTACLESDUPLEX 20 1

25 20 1 SPARE 1000 26

1080 RECEPTACLESDUPLEX 20 1

27 20 1 SPARE 1000 28

1080 RECEPTACLESDUPLEX 20 1

29 20 1 SPARE 1000 30

1080 RECEPTACLESDUPLEX 20 1

31 20 3 SPARE 1000

TOTAL 10728 10516 11440

KVA 32.7 LOAD CONNECTEDTOTAL

69.7 AMPSDEMAND

KVA 25.1 LOAD DEMANDTOTAL

LRM5PANEL

Wire 4 Phase 3 Volts120/208

CK TRIP NO.

SERVEDLOAD

VA LOADPHASE

SERVEDLOAD

CK TRIP NO.

NO.AMP POLES A B C NO.AMP POLES

20 1 RM5 CONTROLIDS 1000 2

1080 RECEPTACLESDUPLEX 30 1

3 20 1 RM5-100B DOOR UPROLL 696 4

1080 RECEPTACLESDUPLEX 20 1

5 20 1 RM5 CAMIDS 1260 6

1260 RECEPTACLESDUPLEX 20 1

7 20 1 RECEPTACLESDUPLEX 1080 8

540 RECEPTACLESDUPLEX 20 1

9 20 1 RECEPTACLESDUPLEX 1080 10

900 RECEPTACLESDUPLEX 20 1

11 20 1 RECEPTACLESDUPLEX 1260 12

1080 RECEPTACLESDUPLEX 20 1

13 20 1 RECEPTACLESDUPLEX 1080 14

1080 RECEPTACLESDUPLEX 20 1

15 20 1 RECEPTACLESDUPLEX 1080 16

1260 RECEPTACLESDUPLEX 20 1

17 20 1 2EF-R5 VAULT FANEXHAUST 528 18

1260 RECEPTACLESDUPLEX 20 1

19 20 1 RECEPTACLESDUPLEX 1260 20

1080 RECEPTACLESDUPLEX 20 1

21 20 1 RECEPTACLESDUPLEX 1260 22

1080 RECEPTACLESDUPLEX 20 1

23 20 1 RECEPTACLESDUPLEX 1260 24

1080 RECEPTACLESDUPLEX 20 1

25 20 1 RECEPTACLESDUPLEX 1080 26

1080 RECEPTACLESDUPLEX 20 1

27 20 1 RECEPTACLESDUPLEX 1260 28

900 RECEPTACLESDUPLEX 20 1

29 20 1 2OAL-R5 AIROUTSID 696 30

696 20 1

31 20 1 1000 32

1000 SPARE 20 1

33 15 1 SPARE 1000 34

0 1P) - (20A ONLYSPACE - 1

35 20 1 SPARE 1000 36

0 1P) - (20A ONLYSPACE 20 1

37 20 1 SPARE 1000 38

0 1P) - (20A ONLYSPACE - 1

39 20 1 SPARE 1000 40

0 1P) - (20A ONLYSPACE - 1

41 20 1 SPARE 1000 42

0 1P) - (20A ONLYSPACE - 1

TOTAL 12360 11596 11380

KVA 35.3 LOAD CONNECTEDTOTAL

75.3 AMPSDEMAND

KVA 27.1 LOAD DEMANDTOTAL

10000 AMPS MINIMUM INTERRUPTING RATING

100A Main Lugs Only

EXHAUST 2EAL-R5

PROJECTOR

PROJECTOR

DUPLEX RECEPTACLES

DUPLEX RECEPTACLES

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a t b m it t e d b y

D e s c r ip t io n D a t e

A c t io n

S o l N o

C o n

R e

C

D

2 3 4 5

C O

R

G

IN

E E

R T

H

T E

X

A R

G

IN

E

T R

IC

T

F il e n a m e

P lo t d a t e

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

C H

IE

F

E L

E C

T R

IC

C T

IO

N

J A

S T

O

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N C

E F

IL

E

R E

F E

R E

N

E S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e t im e d a t e u s e r

T r a c k d a t e c a d d f il e n a m e

O D

T E

X A

S

C O

M P

A

E R

A T

IO

C

IL

IT

Y

E N

G

IN

E E

R

A N

C H

C O

N S

T R

U C

T

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SEQUENCE

SHEET

P N

P N

P N

W

H N

R

F S

R E

V

IS

E D R

E C

O R

D D

R A

W

20141029085917
20141029085933
20141029075200
20141029075117
20141029080047
20141029080435
20141029080217