TECHNICAL PROPOSAL EVALUATION-CRITICAL FACTOR LIST
SPECIFIC REQUIREMENT
ACCEPTA
BLE
NON-
ACCEPT
ABLE
REMARKS
One (1) Dedicated Outdoor Air System (DOAS) with
Energy Recovery
1) Energy Recovery Type shall be: Static plate, total energy transfer
2) Equipment shall be configured as follows:
a) Installation Location: Indoor unit
b) Supply air fan location: before cooling coil
c) Electrical Service:
i) 460 volt/ 3 phase/ 60 hertz
ii) Motors: Qty 2, Direct Drive motorized impeller
iii) Fan Control: ECM
d) Cooling:
i) Chilled water cooling coil, 100% water
e) Heating:
i) Integrated Gas Heat Module
ii) Heater Size: 75 MBH
iii) Heater Fuel type: Natural Gas, 5.0 –
13.5 inches water column (wc)
iv) Modulating 5:1
v) Separated combustion inlet
vi) Horizontal airflow
vii) Direct Spark ignition
f) BACnet Communication Compatibility
g) Drain Overflow switch
h) Recirculation Damper
i) Integrated Programmable controls
j) Fused Disconnect
k) 1” insulation
3) Airside Cooling Conditions shall be:
a) Airflow: 1850 standard cubic feet per minute (scfm)
b) Altitude: 1299 feet
c) Entering dry bulb temperature: 81.7 degrees
Fahrenheit
d) Entering wet bulb temperature: 70 degrees
Fahrenheit
e) Leaving dry bulb temperature: 52 degrees
Fahrenheit
f) Leaving wet bulb temperature: 52 degrees
4) Internal Fluid Cooling Conditions shall be:
a) Fluid: Water, 100%
b) Entering Fluid Temperature: 45 degrees
c) Fluid Flow Rate: ~22 gallons per minute
5) Cooling Performance shall be:
a) Total Capacity: 110550 Btu/hr
b) Sensible Capacity: 60890 Btu/hr
c) Leaving Air dry bulb temperature: 51.8 degrees Fahrenheit
d) Leaving Air wet bulb temperature: 51.4 degrees Fahrenheit
e) Face Velocity: 222 feet/minute
f) Leaving Fluid Temperature: 55.1 degrees
Fahrenheit
g) Air Pressure Drop: 0.15 inches water column (wc max)
6) Filters shall be: MERV 8, 20”x20”x2”
7) Inlets/Outlets dimensions shall be:
a) Outside Air / Return air Inlets: 36” x 16”
b) Supply Air Outlet: 24” x 16”
c) Exhaust Air Outlet: 20” x 16”
8) Unit Dimensions shall be:
a) Maximum Length: 150”
b) Maximum Width: 95”
c) Maximum Height: 72”
d) Maximum Weight: 3400 pounds
9) Heat Exchanger shall be:
a) Summer Supply Air Entering Air dry/wet bult temperatures: 99.5/73.9 degrees
Fahrenheit
b) Summer Supply Air Leaving Air dry/wet bult temperatures: 81.7/67.7 degrees
10) Airflow Orientation shall be configured as illustrated below: