This document is an ABS Global Engineering review letter for a Monitor & Alarm System Profinet Upgrade for two NOAA research vessels: "OSCAR ELTON SETTE" (Class No. 8801905) and "GORDON GUNTER" (Class No. 9000291), built by Halter Marine Inc. (Hull nos. 1123 and 1128). The review was conducted in accordance with ABS Rules for Building and Classing Marine Vessel, 2020, and addressed to Mr. Tim Langdon at the National Oceanic & Atmospheric Administration.
The letter includes three technical comments requiring resolution: (1) Alarm system access controls must be modified to require keyswitch, keycard, or password methods, (2) The system, classified as a Category II Computer Based System, requires ABS Surveyor witnessing of on-board system tests and maintenance of development documentation, and (3) The centralized control station must be equipped with at least two computers capable of displaying monitoring information. The documents were reviewed with comments, and electronic copies are available in the ABS Client Portal. The review was electronically published by ABS Houston on 19-JAN-2021, with contact information provided for clarifications.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WARNING – This document may contain technical data whose export is restricted by the Arms Export Control Act (Title 22, U.S.C., Sec. 2751, et seq.) or the Export Administration Act of 1979 (Title 50, U.S.C., App. 2401, et seq.), as amended. Violations of these export laws are subject to severe criminal or civil penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.
ABS Global Engineering 1701 City Plaza Drive | Spring, TX 77389 USA
Task No. T2070057
“OSCAR ELTON SETTE”, Class No. 8801905
“GORDON GUNTER”, Class No. 9000291
Halter Marine Inc. Hull nos. 1123 and 1128
Flag: United States of America
Monitor & Alarm System Profinet Upgrade
Attention: Mr. Tim Langdon National Oceanic & Atmospheric Administration (WCN: 615875)
The documents shown in the attached list were reviewed in accordance with the applicable requirements of the following:
• ABS Rules for Building and Classing Marine Vessel, 2020
Please note our review is based on the following conditions:
1. The work is to be completed to the satisfaction of the attending ABS Surveyor.
2. The submitted documentation reviewed only for ABS Class requirements. Please submit the documentation to the USCG as soon as possible so that their comments can be incorporated in the vessels design.
Please see attached comments list for the comments generated as a result of this review.
For any clarifications, Mr. Emil Shtaygrud at 281-877-6952 (eshtaygrud@eagle.org).
Very truly yours, Roy H. Bleiberg
Vice President of Engineering
Electronically Signed by: Anju Valookkaran
Electronically published by ABS Houston.
Reference T2070057, dated 19-JAN-2021.
mailto:eshtaygrud@eagle.org
WARNING – This document may contain technical data whose export is restricted by the Arms Export Control Act (Title 22, U.S.C., Sec. 2751, et seq.) or the Export Administration Act of 1979 (Title 50, U.S.C., App. 2401, et seq.), as amended. Violations of these export laws are subject to severe criminal or civil penalties. Disseminate in accordance with provisions of DoD Directive 5230.25.
ABS Global Engineering 1701 City Plaza Drive | Spring, TX 77389 USA
Documents List
Drawing No. Rev. No. Title Status
Gunter/Sette Overview 1 Monitor & Alarm System Profinet
Upgrade Overview
Reviewed with
Comments
Drawing 1 Monitor System Profinet Upgrade Reviewed with
Comment
ALARM INPUTS 1 NOAA SETTE - NOAA GUNTER ALARM
INPUTS
Reviewed
Gunter PSTP 1 Gunter PSTP Filed by ABS for
Reference only
Gunter FMEA 1 FMEA GUNTER & SETTE Reviewed
Electronic copies of the documents, appropriately stamped, are available in the ABS Client Portal.
Comments List
Comment No Comment Text Facilities Action
E-001 Gunter/Sette Overview - Monitor & Alarm System
Profinet Upgrade Overview
1128[Open] Technical
We note that an operator may adjust alarm set points and disable any alarm and advise that this is not acceptable in accordance with 4-9-3/5.1.1 of the Rules, which require keyswitch, keycard, password or other approved methods. Please resolve.
E-002 Gunter/Sette Overview - Monitor & Alarm System
Profinet Upgrade Overview
1128[Open] Surveyor
The subject system is classified as a Category II Computer Based System as per 4-9-
3/Table 1 of the Rules. The on Board Complete System Test and On-Board Integration
Test are required to be witnessed by the ABS Surveyors as per 4-9-3/Table 2 and 4-9-
3/9.3.4 (a) of the Rules. Further, the development procedures, software quality plan, evidence of software testing, and software version record are to be maintained and be made available to the Surveyor upon request as per 4-9-3/7.1 and 4-9-3/Table 2 of the Rules.
E-003 Drawing - Monitor System Profinet Upgrade 1128[Open], 1123[Open]
Technical
As per MVR 4-9-5/9.3, where a computer is used as the operator interface to display monitoring information, the centralized control station is to be provided with at least two computers, including keyboards and monitors, unless other means of display are provided capable of displaying the same information. Please resolve.
Electronically published by ABS Houston.
Reference T2070057, dated 19-JAN-2021.