Scope of Work - SAS Upgrade in Kuwait.pdf

PDF 858 KB Posted

Attached to
SAS Upgrade Support in Kuwait
Solicitation number
T001-27-IQ-00002
Issued by

About this file

This is a Scope of Work (Draft) document for the U.S. Agency for Global Media (USAGM) detailing modernization requirements for the Station Automation System (SAS) currently operating at the Kuwait transmitting station. The primary objective is to migrate the existing Visual Basic 6 (VB6) solution—consisting of Audio.exe and Opcon.exe applications—to a modern platform, preferably the latest .NET framework, while implementing architectural improvements to enhance reliability, maintainability, scalability, and cybersecurity. The current system operates on legacy technology requiring development and testing within virtual machines due to unsupported operating systems, creates a single point of failure, and demands extensive software modifications for equipment integration.

The modernization approach encompasses ten key architectural and technical initiatives: (1) implementation of a client-server architecture to separate backend services from user interface components and support multiple concurrent operator workstations; (2) modular service-based design isolating schedule management, equipment communication, alarm processing, event logging, system monitoring, and reporting into independent services; (3) configuration-driven system management replacing hardcoded definitions with administrative tools; (4) adoption of MQTT Sparkplug B as the primary data exchange mechanism; (5) IoT Edge platform integration at transmitting stations for standardized equipment interfaces and local automation; (6) secure cloud-to-station command and control with authentication, authorization, and audit trails; (7) unified telemetry and operational data models for consistent equipment status visibility; (8) centralized operational data and analytics for historical analysis and reporting; (9) distributed edge processing with critical functions executing locally while synchronizing with cloud services; and (10) containerized service deployment enabling independent component upgrades and standardized deployments across stations. Expected benefits include improved reliability and fault tolerance, simplified equipment integration, removal of obsolete technology dependencies, enhanced cybersecurity, support for modern monitoring tools, and long-term platform sustainability.

View the file

Other files

File Type Posted
Sources Sought - SAS Updgrade.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 | P a g e

SCOPE OF WORK (DRAFT)

Background

The USAGM has a requirement to modernize the current Station Automation System (SAS) in use at the Kuwait transmitting station. USAGM is looking for assistance in designing and implementing the basic SAS replacement as well as design and implementation of value-added features such as those used on other USAGM radio broadcast platforms, leveraging the tools and technology already established. Operational support of the new system and expansion elsewhere in the network be required.

Modernization Objectives

The primary objective of the upgrade project is to migrate the existing VB6 solution to a modern platform, preferably the latest .NET framework, while implementing architectural improvements to enhance reliability, maintainability, scalability, and cybersecurity.

Station Automation System (SAS) Modernization

Current System Overview

The Station Automation System (SAS) currently operating at the Kuwait station consists of a combination of hardware and software components responsible for the automatic control and monitoring of broadcast equipment.

Refer to the attached system overview diagram for reference.

The existing SAS architecture is centered around a single PC running two Visual Basic 6 (VB6) applications:

• Audio.exe

• Opcon.exe

Both applications combine backend processing and user interface functionality within the same executable process. An overview of the current architecture is provided in the Current Opcon Block Diagram.

Audio Application (Audio.exe)

The Audio application is responsible for:

2 | P a g e

• Editing the broadcast schedule database, allowing operators to enter and modify schedule changes.

• Processing broadcast schedules in real time and generating broadcast chain events.

• Transmitting schedule events to the Opcon application using Dynamic Data Exchange (DDE).

• Performing automatic audio switching to transmitters according to the active schedule by issuing serial commands to the audio switcher.

• Providing a user interface for manual audio switching operations.

• Logging audio-related events and alarms to text files.

Operation Control Application (Opcon.exe)

The Opcon application is responsible for the remaining station control and monitoring functions, including:

• Providing operators with a user interface for monitoring and manual control of broadcast equipment.

• Executing operational commands such as:

o Transmitter ON/OFF o Antenna switching o Transmitter tuning o Other equipment control functions

• Receiving schedule events from Audio.exe via DDE and translating them into real-time commands for the broadcast chain equipment.

• Recording operational events and alarms in text-based log files.

Equipment Interfaces

Both applications communicate with field equipment through serial communication ports using equipment-specific protocols.

3 | P a g e

In addition, each transmitter is equipped with a Panasonic FP2 PLC, which executes ladder logic programs responsible for low-level control functions, including:

• Switching sequences

• Automatic tuning

• Safety interlocks

• Alarm handling

The Opcon application communicates with these PLCs using the MEWNET protocol, a message-based RS-232 communication protocol.

Other station equipment also provides remote-control capabilities through integrated serial interfaces or PLCs. These devices exchange control commands and status information with the SAS applications.

For remote access and monitoring, operators currently use TeamViewer to connect to the SAS workstation through the Internet.

Current Challenges

Although the system has operated reliably for many years, it has become increasingly difficult to maintain, enhance, and integrate with modern equipment.

Key challenges include:

• The software is based on legacy Visual Basic 6 technology.

• The source code relies on third-party components that can only be installed on unsupported operating systems such as Windows XP and earlier versions.

• Development, debugging, and testing must therefore be performed inside virtual machines, making maintenance inefficient and time-consuming.

• Most equipment interfaces, alarm logic, and logging functionality are implemented directly in application code, requiring software changes for even minor system modifications.

• The architecture depends on a single workstation and process, creating a significant single point of failure.

• Integration of new transmitter models and replacement equipment requires extensive software modifications.

4 | P a g e

Refer to the attached New Opcon Block Diagram for the proposed architecture.

1. Client-Server Architecture

Redesign the system using a client-server architecture by separating backend services from user interface components.

Benefits include:

• Improved system reliability

• Elimination of a single process dependency

• Support for multiple concurrent operator workstations

• Secure remote access

• Support for various client platforms such as PCs, tablets, and mobile devices

In the current implementation, a failure of either application can render the entire automation system unavailable. The proposed architecture reduces this risk by isolating critical services.

2. Modular Service-Based Design

Implement a modular architecture where core functions are separated into independent services, including:

• Schedule management

• Equipment communication

• Alarm processing

• Event logging

• System monitoring

• Reporting

This approach will simplify maintenance and allow individual services to be upgraded independently.

3. Configuration-Driven System Management

Replace hardcoded equipment definitions, alarm rules, and logging configurations with configuration-based management.

This will enable administrators to:

5 | P a g e

• Add or modify equipment without software changes

• Configure alarms through administrative tools

• Adjust logging behavior without recompilation

• Reduce deployment and maintenance effort

4. MQTT Sparkplug B Integration

Adopt the MQTT Sparkplug B open standard as the primary data exchange mechanism.

Advantages include:

• Standardized communication between system components

• Simplified integration with third-party applications

• Real-time data distribution

• Native support for dashboards, analytics, historians, and web-based user interfaces

• Improved interoperability with modern industrial automation tools

5. IoT Edge Platform Integration

Implement an IoT Edge platform at each transmitting station to provide a secure and standardized interface between broadcast equipment and cloud-based services. The edge platform shall host the core automation services responsible for equipment communication, telemetry collection, local control, and data processing.

Benefits include:

• Local execution of automation services with minimal latency

• Standardized integration of serial, SNMP, PLC, and IP-based equipment

• Continued station operation during temporary network outages

• Secure communication with cloud services

• Simplified deployment of new automation capabilities

• A common architecture that can be replicated across multiple transmitting stations

6 | P a g e

6. Secure Cloud-to-Station Command and Control

Provide secure bidirectional communication between cloud applications and the station automation platform to allow authorized operators to initiate operational commands remotely while maintaining local operational safety.

Capabilities include:

• Remote execution of operational commands through secure cloud services

• Acknowledgement of command acceptance and execution status

• User authentication and authorization

• Complete audit trail of all remotely initiated operations

• Local validation of commands before execution

• Support for scheduled and on-demand operational activities

This architecture shall support modern cloud command mechanisms while ensuring that all critical operational logic remains under local station control.

7. Unified Telemetry and Operational Data Model

Implement a standardized telemetry framework that provides a consistent operational view of all station equipment regardless of manufacturer or communication protocol.

The telemetry framework should support collection of:

• Equipment operational status

• Broadcast chain parameters

• Power and environmental measurements

• Alarm conditions

• Network and communication health

• Audio status

• PLC operational data

• System performance metrics

7 | P a g e

A standardized telemetry model will simplify dashboard development, reporting, analytics, and integration with enterprise monitoring systems.

8. Centralized Operational Data and Analytics

Provide centralized collection and storage of operational telemetry, alarms, and system events to support historical analysis, reporting, and operational decision making.

Capabilities include:

• Long-term telemetry storage

• Historical trend analysis

• Equipment performance reporting

• Alarm frequency and root cause analysis

• Availability and reliability reporting

• Predictive maintenance analysis

• Operational KPI reporting

• Integration with enterprise visualization platforms

Historical operational data will improve troubleshooting, maintenance planning, and long-term system optimization.

9. Distributed Edge Processing and Local Automation

Design the automation platform so that critical operational functions execute locally at each transmitting station while synchronizing operational data with centralized cloud services.

Local processing should include:

• Equipment communication

• Schedule execution

• Alarm processing

• Event logging

8 | P a g e

• Local decision making

• Temporary data buffering during communication outages

This architecture ensures uninterrupted station operation while taking advantage of cloud-based monitoring, reporting, and centralized management.

10. Containerized Service Deployment and Platform Management

Deploy automation services as independently managed containerized applications to improve reliability, maintainability, and operational flexibility.

Benefits include:

• Independent deployment and upgrade of system components

• Simplified software maintenance

• Standardized deployments across all transmitting stations

• Automatic service recovery

• Centralized configuration management

• Remote diagnostics and log collection

• Version-controlled software releases

• Reduced operational downtime during software upgrades

This approach provides a scalable software platform that simplifies future expansion while allowing new functionality to be introduced with minimal disruption to station operations.

Expected Benefits

The proposed modernization will deliver:

• Improved reliability and fault tolerance

• Easier maintenance and future enhancements

• Simplified integration of new broadcast equipment

• Removal of dependencies on obsolete technologies

• Enhanced cybersecurity and remote accessibility

9 | P a g e

• Support for modern monitoring and visualization tools

• Long-term sustainability of the station automation platform

This modernization will ensure that the SAS remains maintainable, scalable, and adaptable to future operational and technological requirements.

Other Enhancements

IoT based monitoring Reference Architecture

IoT based monitoring reference Architecture

10 | P a g e

IoT edge device performing telemetry, reading logs from the module in the cloud From the Azure portal]

Grafana Dashboard showing Transmitter Forward power, Modulation Status, C-band and Ku-band C/N on a map.

11 | P a g e

Grafana Alerting showing 5 alarms out of a total of 13 rules for Alerting

IoT based monitoring Reference Architecture