T-85.00.pdf
PDF 12 KB Posted
- Attached to
- Single Phase Pad Mount Transformers
- Solicitation number
- ITB-E 2027-015
- Issued by
- Alachua County, Graceville City, Florida
About this file
This file is an Approved Materials Manual page from Gainesville Regional Utilities (GRU) Electric System in Florida, detailing specifications for single phase pad mounted transformers with dead front loop feed capability. The manual lists approved manufacturers including Central, Maloney, Cooper Power Systems, Ermco, General Electric, Howard, and ABB. The transformers specified have a high voltage rating of 12470 GRD Y/7200, low voltage of 240/120, and a basic insulation level (B.I.L.) of 95 kV, with KVA ratings of 25, 37.5, 50, 75, 100, and 167, with corresponding weights ranging from 694 to 1911 pounds. The manual was initially revised on January 30, 1991, with subsequent updates through May 22, 2013, and technical specifications are detailed on pages T-85.01 through T-85.04 of the manual.
GRU is soliciting competitive bids from qualified vendors for the supply and delivery of these single phase pad mount transformers to meet operational requirements. No specific quantities, response dates, due dates, site visits, bidders' meetings, award dates, or contract terms are identified in this materials manual excerpt. Pricing terms, set-asides, incumbent vendor information, and funding sources are not documented in this file. This document serves as a reference specification guide for approved transformer models and manufacturers that meet GRU's technical and operational standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Single_Phase_Pad_Mount_Transformers.pdf | ||
| T-85.01.pdf | ||
| T-85.03.pdf | ||
| T-85.04.pdf | ||
| T-85.02.pdf | ||
| T-85.05.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Stock No.Catalog No.ManufacturerDescription
ITEM NAME
Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y
SM
TM
Page T - 85.00
29753-4
14185-2
83367-3
45117-7
57999-8
06786-5
CENTRAL MALONEY
COOPER POWER SYS.
ERMCO
GENERAL ELECTRIC
HOWARD
ABB
SINGLE PHASE PAD MOUNTED TRANSFORMER,
DEAD FRONT LOOP FEED CAPABILITY
HIGH VOLTAGE: 12470 GRD Y/7200
LOW VOLTAGE: 240/120
B.I.L.: 95 kV
KVA RATING: (WEIGHT)
25 (694 LBS.)
37.5
50 (885 LBS.)
75 (1049 LBS.)
100 (1195 LBS.)
167 (1911 LBS.)
TRANSFORMER, SINGLE PHASE PAD MOUNTED
1-30-91 1-6-95
9-18-07 KLC
5-22-13 KLC
NOTE:
TECHNICAL SPECIFICATIONS ARE LISTED ON
PAGES T-85.01 THROUGH T-85.04, IN THIS MANUAL.