SWCo_VFD_Service_Flyer.pdf
PDF 394 KB Posted
- Solicitation number
- 26-X-00942
- Issued by
- Hillsborough County, Florida
About this file
This is a service flyer document supporting a single-source contract opportunity for Stan Weaver and Company to provide Variable Frequency Drive (VFD) products and maintenance services to the Tampa Convention Center in Hillsborough County, Florida. Stan Weaver and Company serves as the exclusive ABB manufacturer's Channel Partner for the ABB variable frequency product line in the HVAC market within Hillsborough County and Tampa. The company provides comprehensive services including VFD drive parts, complete drives (VFDs), and ongoing preventative maintenance services for ABB VFDs and other compatible equipment. The flyer outlines the company's recommended preventative maintenance program, which includes annual thorough maintenance consisting of unit cleaning, parts inspection, connection tightening, power supply checks, cable inspections, fan and cooling system functional testing, electrostatic discharge protected cleaning, emergency stop circuit inspection, fault logger inspection, thermal imaging analysis, and spare parts inventory review.
The preventative maintenance program emphasizes that regular annual maintenance is essential to extending VFD lifetime, ensuring maximum availability, and minimizing unplanned repair costs. The flyer notes that without preventive maintenance, VFD failure probability increases significantly, with common failures typically appearing after five to ten years of operation due to component aging, varying ambient temperatures, high humidity, and excessive loads. Stan Weaver and Company offers prospective clients a free walkthrough and analysis service to identify quantities, types, and ages of existing VFDs and motors. Contact information for scheduling this evaluation is provided at 407-790-4036 or service@stanweaver.com. The single-source intent reflects Tampa Convention Center's current reliance on Stan Weaver and Company for critical infrastructure support powering the facility.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Regular preventative maintenance helps all electronics run longer and provide more consistent perfor-mance. VFDs benefit from regular maintenance, especially if they have open side vents, that may allow for-eign objects or moisture to contaminate the inside of the housing. This, in turn, minimizes replacement costs and critical failures that lead to unexpected downtime.
Once a year, the VFDs should undergo thorough maintenance. This includes:
Cleaning the unit. Vacuum the vents and storage space, and clean or replace the filters. VFDs should not be cleaned with any solvents or water-based cleaning tools.
Inspecting the parts. Tighten the connections and terminal blocks, check the power supplies, and refer to the parts replacement schedule for any needed work. The DC bus should also be checked with an oscillo-scope to check the Vdc ripple, but only trained professionals should handle this step.
VFD preventive maintenance program
Without preventive maintenance, the probability of VFD failure increases drastically. The most common failures are due to component aging or operational conditions, such as varying ambient temperature, high humidity, excessive and heavy loads. Signs of these failures typically start showing up after five to 10 years of operation.
A regular preventive maintenance program of VFDs throughout their lifetime is an absolute requirement to ensure maximum availability and minimum unplanned repair costs. With an Annual preventive mainte-nance, reliability of VFDs can be ensured and their lifetime extended.
Scheduled tasks include:
• Visual inspection of the VFD and environmental conditions.
• Inspection of the connections.
• Inspection of the ribbon and fiber optic cables.
• Functional inspection of the fan and cooling system.
• Electrostatic Discharge protected cleaning of the VFD.
• Inspection of the 'emergency stop' circuit.
• Inspection for the prevention of unexpected start-up circuit.
• Inspection of the fault logger.
• Inspection and storage of the parameters.
• Functional testing of the VFD under normal conditions.
• Basic measurements with supply voltage.
• Thermal imagining to locate possible bad connections
• Inspection of the VFD spare part inventory.
• Reforming of the spare module capacitors.
Manufacturers of VFD technology can offer end users an extraordinary level of reliability, which can be compromised if end users neglect to embrace a lifecycle approach that includes annual maintenance
End users that recognize the importance of preventive maintenance can provide a valuable role in setting up a comprehensive preventive maintenance schedule that spans the life of the basic VFD
Call or Email to schedule a free walkthrough today and we will provide you our free analysis showing the quantities, types, and age of your VFD’s and motors.