This is a Statement of Work (SOW) for a backup cryogenic pump sled and vaporizer for the Naval Surface Warfare Center Indian Head (NSWC IHD). The SOW requires a contractor to provide and install specific equipment, including a CV 10/4 Cryogenic Filling Pump with 0.8-0.85 GPM capacity, capable of working up to 3500-3600 psi, featuring a 7.5 HP energy-efficient motor, and mounted on a heavy-duty steel skid. Additionally, the scope includes an electrical control wall-mounted system, pump inter-connecting piping kit, and a V08KSS Ambient Air Vaporizer with 8000 SCFH capacity and stainless steel construction rated for 4000 psi.
The associated federal contract opportunity is a sole-source notice intending to award a firm fixed-price contract to Cryovation LLC for these specific components. The contract is being pursued under FAR 13.106(b) for soliciting from a single source. Interested parties can submit their capabilities and potential competitive alternatives by August 20, 2025, at 10 AM EST, with responses to be emailed to Nicole Coleman. The contract falls under NAICS code 333912 and is being processed by the Department of the Navy Naval Sea Systems Command, with delivery specified to NSWC IHD in Indian Head, MD.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
for Backup Cryogenic Pump Sled & Vaporizer 3/13/2025 v2
1.0 SCOPE
The Naval Surface Warfare Center Indian Head (NSWC IHD) is upgrading and replacing Strand burn’s Cryogenic System. This statement of work requires a drop in place backup cryogenic pump sled and customer sized vaporizer to maintain mission tin order to prevent future downtime at strand burn because of failed cryogenic pump.
3.0 REQUIREMENTS
The Contractor shall provide fabrication, delivery and installation to specified requirement below.
3.1 CV 10/4 Cryogenic Filling Pump, (Inert) including:
· 0.8 - 0.85 GPM up to 3500-3600 psi maximum working pressure
· Includes a 7.5 HP Energy Efficient TEFC motor with adjustment rail
· 1.0" diameter vacuum-jacketed Cold End .8" stroke Drive End
· Surge chamber with pressure relief valve
· Heavy Duty steel skid and stainless-steel belt guard
3.2 Electrical Control, Wall Mounted (7.5 HP) standard, with manual disconnect, motor starter, hour meter, pressure gauge, over pressure switch and on-off button control, automatic rotation switch at each start-up.
3.3 Pump Inter-Connecting Piping Kit, Complete set of components to custom fit a typical horizontal cryogenic pump's Liquid Supply and Vent Return to the tank (No Valves).
3.4 V08KSS Ambient Air Vaporizer
· 8000 SCFH
· ½” FNPT Inlet & Outlet
· Stainless Steel to prevent corrosion
· 4000 psi or greater maximum allowable working pressure
4.0 INSPECTION, INSTALLATION, ACCEPTANCE, AND PAYMENT
The Contractor shall be responsible for the packaging, handling, and transportation to NSWC IHD of any/all components. The Government, upon delivery of products, will perform inspection and acceptance. The Contractor shall notify the Contracting Officer thirty (30) days in advance, if the delivery schedule cannot be met.
5.0 POINTS OF CONTACT
NSWC IHD
Cole McClure Indian Head, MD 20640 Phone: (301) 643-9395
6.0 DELIVERY
The Contractor shall drop ship equipment to NSWC IHD B890, ATTN.: Cole McClure,R33 301-643-9395, Indian Head MD 20640. The Contractor delivery driver must present US credentials to access NCWS IHD.