Statement of Work (SOW)
Automatic Door Maintenance
Syracuse VA Medical Center
B.3 SCOPE
Contractor shall furnish all parts and labor to provide two (2) preventive maintenance inspections per year, one in January and one in June, plus all emergency repairs required for the automatic doors described below in Table 1 and located at the Syracuse VA Medical Center, 800 Irving Avenue, Syracuse, NY 13210. The Period of Performance shall be January 1, 2021 to December 31, 2021 with provision of four (4) option years.
B.3.1 RESPONSIBILITY OF THE VETERAN AFFAIRS MEDICAL CENTER
The VA will maintain responsibility for any electrical failures between the power source and the control box of the door controls; any pneumatic failures between the pneumatic source and the control box of the door; and for the doors, frames, glass, locks, finger guards, crash bars, and rails unless damage is caused by the Contractor.
B.3.2 SERVICE
Service shall consist of two preventive maintenance inspections per year on all equipment contained within Table 1, below. Service shall be completed by AAADM (American Association of Automatic Door Manufacturers) certified professionals. Preventative Maintenance (PM) shall include, but not be limited to, inspecting the mechanical, electric, and electronic components of each automated door including its remote controls, i.e., floor mats, scanners, push plates, etc. Any worn or defective part will be replaced at no additional cost to the Government to maintain the equipment in first class operating condition, per the manufacturer’s specifications, including all intervening calls necessary between regular inspections, excepting services necessitated by accident, fire or abuse. The Contractor shall make thorough technical inspections of the equipment in accordance with the commercial practice governing maintenance of automatic door manufacturers. Preventive maintenance inspections shall be evenly spaced during the contract period, but in no event shall more than seven months elapse between inspections. PMs are to be performed in January and June of the contract period.
B.3.2.1
Table 1:
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA101 |
| √ |
| 021382 |
| BL24 |
| Single Door, Trash entrance |
| Besam |
| Swing |
| ECRBB-A/42 |
| Yes |
| BL18 |
| Single door, Morgue Employee Entrance, |
| Besam |
| Swing |
| ECRBB-A/40 |
| Yes |
| VA103 |
| √ |
| 023721 |
| AG15 |
| Single Door, Men's Restroom, Audiology |
| Horton Automatics |
| Swing |
| EGA-A/16 |
| VA104 |
| √ |
| 010220 |
| AG43 |
| Director's Suite |
| Horton Automatics |
| Sliding |
| GA-A/14 |
| Yes |
| VA105 |
| √ |
| 023706 |
| CG23 |
| Single Door, Women's Restroom, Canteen |
| Horton Automatics |
| Swing |
| EGC-A/9 |
| VA106 |
| √ |
| 003380 |
| 3 East |
| Nuclear Medicine - Internal |
| Horton Automatics |
| Sliding |
| VA107 |
| √ |
| 003381 |
| 3 East |
| Nuclear Medicine - External |
| Horton Automatics |
| Sliding |
Yes
| VA108 |
| √ |
| 015291 |
| 3 West |
| Double Doors, Interventional Radiology - Outer doors |
| Horton Automatics |
| Swing |
| E3B-C / 23 |
| VA109 |
| √ |
| 015292 |
| 3 West |
| Double Doors, Interventional Radiology - Inner Doors |
| Horton Automatics |
| Swing |
| E3B-C / 23 |
| VA110 |
| √ |
| 015295 |
| B314 |
| Single Door, Interventional Radiology |
| Horton Automatics |
| Swing |
| VA111 |
| √ |
| 023702 |
| C165A |
| Single Door, Unisex Bathroom, Team Red Waiting Room |
| Horton Automatics |
| Swing |
| E1C-C/31 |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA112 |
| √ |
| 006992 |
| BG38 |
| Single Door, Pedestrian exit, inner door Univ. Place |
| Horton Automatics |
| Swing |
| EG-EDCR-2/76 |
| VA113 |
| √ |
| 006993 |
| BG38 |
| Single Door, Pedestrian entrance, inner door Univ. Place |
| Horton Automatics |
| Swing |
| EG-EDCR-2/76 |
| Yes |
| VA114 |
| √ |
| 006990 |
| BG38 |
| Single Door, Pedestrian exit, middle door Univ. Place |
| Horton Automatics |
| Swing |
| EG-EDCR-2/72 |
| VA115 |
| √ |
| 006991 |
| BG38 |
| Single Door, Pedestrian entrance, middle door Univ. Place |
| Horton Automatics |
| Swing |
| EG-EDCR-2/72 |
| VA116 |
| √ |
| 021507 |
| BG37 |
| Single Door, Pedestrian, Univ. Place |
| Besam |
| Swing |
| EG-EDCR-2/72 |
| VA117 |
| √ |
| 021508 |
| BG37 |
| Revolving Door, Pedestrian entrance, Univ. Place |
| Boon Edam |
| Revolving |
| EG-EDLS/13-15 |
| VA119 |
| √ |
| 006997 |
| BG65 |
| Double Doors, Ambulance Entrance inner door Univ. Place |
| Horton Automatics |
| Swing |
| EG-EDCR-2/48 |
| VA120 |
| √ |
| 006996 |
| BG65 |
| Double Doors, Ambulance Entrance exterior door Univ. Place |
| Horton Automatics |
| Swing |
| EG-EDCR-2/48 |
| VA121 |
| √ |
| 006995 |
| Corr G20 |
| Double Doors, West Corridor to Service Elev. Lobby |
| Horton Automatics |
| Swing |
| EG-EDCR-2/74 |
| VA122 |
| √ |
| 006994 |
| Corr G20 |
| Double Doors, West Corridor to Pass Elev Lobby |
| Horton Automatics |
| Swing |
| EG-EDCR-2/74 |
| VA123 |
| √ |
| 006998 |
| Corr G06 |
| Double Doors, West Corridor to Emergency Department |
| Horton Automatics |
| Swing |
| EG-EDCR-2/44 |
| Yes |
| VA124 |
| √ |
| 010241 |
| Corr 133 by A166 |
| Single Sliding Door, Inner Entrance /Exit, Irving. Ave |
| Horton Automatics |
| Sliding |
| ELS1A-A/10 |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA125 |
| √ |
| 010242 |
| Corr 134 |
| Single Sliding Door, Exterior Entrance /Exit, Irving. Ave |
| Horton Automatics |
| Sliding |
| ELS1A-A/10 |
| VA126 |
| √ |
| no tag |
| C534 |
| Double Doors, Physical Therapy Suite |
| Horton Automatics |
| Swing |
| 5C-B/1 |
| Key Lock |
| VA127 |
| √ |
| 010610 |
| 6 East |
| Double Doors, East Corridor to ICU |
| Horton Automatics |
| Swing |
| ELS6AA/4 |
| VA128 |
| √ |
| 015215 |
| BL08 |
| Double Doors, North Loading Dock, |
| Stanley |
| Swing |
| LB-A/16 |
| VA129 |
| √ |
| 020772 |
| Corr. By CL09 |
| Double Doors, East Loading Dock, |
| Stanley |
| Swing |
| ELCB-1/17 |
| VA130 |
| √ |
| 010221 |
| NG |
| Single Sliding Door, Entrance/Exit to Smoking Patio |
| Stanley |
| Sliding |
| GC-A/29 |
| Yes |
| VA131 |
| √ |
| 020741 |
| Smoking Patio |
| Single Door, Entrance/Exit to Smoking Building off Patio |
| Nasco |
| Swing |
| EEQGE-C/3 |
| VA132 |
| √ |
| 020767 |
| C161 |
| Single Door, Women's Restroom |
| Stanley |
| Swing |
| 1C-D/17 |
| VA133 |
| √ |
| 015737 |
| C163 |
| Single Door, Men's Restroom |
| Stanley |
| Swing |
| 1C-D/13 |
| VA135 |
| √ |
| 021510 |
| 1 South |
| Single Door, Pedestrian, Irving Ave |
| Besam |
| Swing |
| E1C-A/37 |
| Yes |
| VA136 |
| √ |
| 021509 |
| 1 South |
| Revolving Door, Pedestrian entrance, Irving Ave |
| Boon Edam |
| Revolving |
| E1C-A/24-26 |
| VA137 |
| √ |
| 012079 |
| 1 South |
| Double Sliding Doors, Irving Ave Entrance/Exit to Lobby |
| Besam |
| Double Sliding |
| E1C-A/35 |
| VA138 |
| √ |
| 012080 |
| 1 South |
| Single Door, Pedestrian Entrance/Exit to Patio @ Irv. Ave |
| Besam |
| Swing |
| VA139 |
| √ |
| 012233 |
| M205 |
| Double Doors, Entrance/Exit to MRI Waiting Room |
| Stanley |
| Swing |
| Corr M250B |
| Double Sliding Doors, to MRI Procedure Area (near M215) |
| Stanley |
| Sliding |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA141 |
| √ |
| 021230 |
| C304 |
| Single Door, Women's Restroom |
| Besam |
| Swing |
| E3C-B/30 |
| VA142 |
| √ |
| 021229 |
| C306 |
| Single Door, Men's Restroom |
| Besam |
| Swing |
| E3C-B/30 |
| VA143 |
| √ |
| 012235 |
| M301 |
| Right Door, Corr. Entrance/Exit Ultrasound/recover area |
| Besam |
| Swing |
| E3C-B/30 |
| VA144 |
| √ |
| 012235 |
| M301 |
| Left Door, Corr. Entrance/Exit Ultrasound/recover area |
| Besam |
| Swing |
| E3C-B/30 |
| VA145 |
| √ |
| 020743 |
| M315 |
| Right Door, Corr. Entrance/Exit to Corridor |
| Besam |
| Swing |
| E3C-B/ |
| VA146 |
| √ |
| 020742 |
| M315 |
| Left Door, Corr. Entrance/Exit to Corridor |
| Besam |
| Swing |
| E3C-B/ |
| VA147 |
| √ |
| 012126 |
| 3 East |
| Right Door, 3 East Corr. Entrance/Exit to Corridor |
| Besam |
| Swing |
| E3C-B/ |
| 3 East |
| Left Door, 3 East Corr. Entrance/Exit to Corridor |
| Besam |
| Swing |
| E3C-B/ |
| VA149 |
| √ |
| 012127 |
| M321 |
| Right Door, Corr. Entrance/Exit to Cath Lab Recovery Room |
| Besam |
| Swing |
| E3C-B/32 |
| VA150 |
| √ |
| 012128 |
| M321 |
| Left Door, Corr. Entrance/Exit to Cath Lab Recovery Room |
| Besam |
| Swing |
| E3C-B/32 |
| VA151 |
| √ |
| 015528 |
| CG27 |
| Single Door, Men's Restroom |
| Stanley |
| Swing |
| GC-E/9 |
| VA152 |
| √ |
| 021275 |
| BG04 |
| Single Door, Women's Restroom |
| Stanley |
| Swing |
| GB-A/21 |
| VA153 |
| √ |
| 021272 |
| BG02 |
| Double Doors, TSS Breakdown |
| Dorma |
| Swing |
| ELSL2-G/6 |
| Yes |
| VA154 |
| √ |
| 021273 |
| CG12 |
| Single Door, Canteen Storage |
| Dorma |
| Swing |
| ELSL2-G/4 |
| Yes |
| VA155 |
| √ |
| 021274 |
| CG13 |
| Double Doors, TSS Supply |
| Dorma |
| Swing |
| ELSL2-G/6 |
| Yes |
| VA156 |
| √ |
| 020779 |
| A165 |
| Single Door, Men's Restroom |
| Stanley |
| Swing |
| E1A-B/7 |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA157 |
| √ |
| 020780 |
| A167 |
| Single Door, Women's Restroom |
| Stanley |
| Swing |
| E1A-B/12 |
VA158
| 020777 |
| A132 |
| Single Door, Women's Restroom |
| Stanley |
| Swing |
| 1A-B/14 |
| VA159 |
| √ |
| 020778 |
| A134 |
| Single Door, Men's Restroom |
| Stanley |
| Swing |
| 1A-B/16 |
| VA160 |
| √ |
| 020765 |
| A181 |
| Single Door, Corridor to Team Blue Annex |
| Besam |
| Swing |
| 1DA/18 |
| VA161 |
| √ |
| 020766 |
| A183 |
| Single Door, Corridor to Team Blue Annex |
| Besam |
| Swing |
| 1DA/18 |
| VA163 |
| √ |
| 020776 |
| C206 |
| Single Door, Women's Restroom, outside Kitchen |
| Stanley |
| Swing |
| VA164 |
| √ |
| 020775 |
| C204 |
| Single Door, Men's Restroom, outside Kitchen |
| Stanley |
| Swing |
| VA165 |
| √ |
| 021329 |
| 4 West |
| Double Doors, Service Elevator Lobby to West Corridor |
| Dorma |
| Swing |
| EQPL4-4/27 |
| VA166 |
| √ |
| 020774 |
| B506 |
| Single Door, Unisex Restroom |
| Stanley |
| Swing |
| E5S-S/15 |
| VA167 |
| √ |
| 020773 |
| A802 |
| Single Door, Kitchenette/Conference room |
| Horton Automatics |
| Swing |
| 8A-B/12 |
| VA168 |
| √ |
| 021260 |
| 8 East |
| Single Door, Corridor to Hospice |
| Horton Automatics |
| Swing |
| 8A-B/12 |
| VA169 |
| √ |
| 007524 |
| 9 East |
| Single Door, Corridor to VALOR Inn Guest Rooms |
| Horton Automatics |
| Swing |
| E9A-A/42 |
| VA170 |
| √ |
| 020768 |
| BG42 |
| Single Door, ED waiting rm. To Treatment Area |
| Horton Automatics |
| Swing |
| EG-EDCR-3/26 |
| Yes |
| VA172 |
| √ |
| 021283 |
| S101 |
| Double Doors, Service Elevator Lobby to SCI Waiting Rm |
| Besam |
| Swing |
| ELSL2-1/8 |
| VA173 |
| √ |
| 021283 |
| 1SCI |
| Double Doors, East Corridor by S107 |
| Besam |
| Swing |
| ELSL2-1/12 |
| VA174 |
| √ |
| 021278 |
| 1SCI |
| Double Doors, West Corridor by S157 |
| Besam |
| Swing |
| ELSL1-1/30 |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA175 |
| √ |
| 021277 |
| S161 |
| Single Door, Infusion |
| Besam |
| Swing |
| ELSL1-1/28 |
| VA176 |
| √ |
| 021276 |
| S176 |
| Single Door, Dialysis |
| Besam |
| Swing |
| ELSL1-1/26 |
| VA177 |
| √ |
| 021379 |
| S175A |
| Single Door, S110 to Treatment Area |
| Besam |
| Swing |
| ELSL2-1/10 |
| VA178 |
| √ |
| 021292 |
| C904 |
| Single Door, Entrance to Women’s Clinic |
| Besam |
| Swing |
| ELS9A-A/12 |
| Key Lock |
| VA179 |
| √ |
| 015943 |
| C904A |
| Single Door, Women’s Clinic Restroom |
| Horton Automatics |
| Swing |
| 9A-B/23 |
| VA180 |
| √ |
| 023705 |
| C904 |
| Single Door, Women's Clinic Exam Room Corridor |
| Horton Automatics |
| Swing |
| E9A-A/30 |
| VA181 |
| √ |
| 021297 |
| SL23 |
| Double Doors, Laundry Storage |
| Dorma |
| Swing |
| EQPL1-B/27 |
| Yes |
| VA182 |
| √ |
| 021298 |
| SL44 |
| Double Doors, Soiled Linen to Corridor L55 |
| Dorma |
| Swing |
| EQPL1-B/25 |
| Yes |
| VA183 |
| √ |
| 021398 |
| SL44 |
| Double Doors, Soiled Linen to Loading Dock SL55 |
| Dorma |
| Swing |
| EQPL1-B/25 |
| Yes |
| VA184 |
| √ |
| 021299 |
| SL55 |
| Double Doors, Loading Dock to Corridor SL56 |
| Dorma |
| Swing |
| EQPL1-B/25 |
| VA185 |
| √ |
| 021301 |
| SG92 |
| Double Doors, Elevator Lobby to Therapy Pool, SG93 |
| Dorma |
| Swing |
| ELSL1-G/9 |
| VA186 |
| √ |
| 021376 |
| SG30 |
| Double Doors, Recovery Room to West Corridor |
| Dorma |
| Swing |
| ELSL1-G/5 |
| VA187 |
| √ |
| 021377 |
| SG30 |
| Double Doors, Recovery Room to Elevator Lobby |
| Dorma |
| Swing |
| ELSL1-G/3 |
| VA188 |
| √ |
| 021327 |
| Corridor G60 |
| Double Doors, Elevator Lobby to West Corridor |
| Dorma |
| Swing |
| ELSL1-G/3 |
| Yes |
| VA189 |
| √ |
| 021334 |
| Corridor G57 |
| Double Doors, East Corridor to West Corridor |
| Dorma |
| Swing |
| ELSL2-G/1 |
| Yes |
| VA190 |
| √ |
| 021290 |
| SG88 |
| Double Doors, SPS Distribution |
| Dorma |
| Swing |
| ELSL2-G/7 |
| Yes |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA191 |
| √ |
| 021328 |
| SG88 |
| Double Doors, SPS Distribution Inner entrance/exit |
| Dorma |
| Swing |
| ELSL2-G/7 |
| VA192 |
| √ |
| 021305 |
| SG96 |
| Double Doors, SPS Distribution, Storage |
| Dorma |
| Swing |
| ELSL2-G/9 |
| Yes |
| VA193 |
| √ |
| 021306 |
| SG86 |
| Double Doors, SPS Decon, Outer entrance/exit |
| Dorma |
| Swing |
| ELSL2-G/3 |
| Yes |
| VA194 |
| √ |
| 021330 |
| SG86 |
| Double Doors, SPS Decon, Inner entrance/exit |
| Dorma |
| Swing |
| ELSL2-G/3 |
| VA195 |
| √ |
| 021284 |
| S146 |
| Double Doors, East Entrance to Same Day Surgery Area |
| Dorma |
| Swing |
| ELSL1-1/1 |
| VA196 |
| √ |
| 021285 |
| S146 |
| Double Doors. West Entrance to Same Day Surgery Area |
| Dorma |
| Swing |
| ELSL1-1/4 |
| VA197 |
| √ |
| 021340 |
| 2.5 SCI |
| Double Doors, East Corridor to Surgical Suite |
| Dorma |
| Swing |
| ELSL1-2/4 |
| Yes |
| VA198 |
| √ |
| 021341 |
| S220 |
| Double Doors, East Entrance to PACU |
| Dorma |
| Swing |
| ELSL1-2/2 |
| VA199 |
| √ |
| 021344 |
| S220 |
| Double Doors, West Entrance to PACU |
| Dorma |
| Swing |
| ELSL1-2/1 |
VA200
| Corr. 255 |
| Double Doors, Entrance to Sterile Corridor by OR1 |
| Dorma |
| Swing |
| ELSL1-2/12 |
VA201
| Corr. 260 |
| Double Doors, Entrance to Sterile Corridor by OR7 |
| Dorma |
| Swing |
| ELSL1-2/3 |
| VA202 |
| √ |
| 021342 |
| S241 |
| Double Doors, South Corr. To Pre-Op/ TURNED OFF 1/8/20 AT OR's REQUEST |
| Dorma |
| Swing |
| ELSL1-2/11 |
| VA203 |
| √ |
| 021343 |
| S241 |
| Double Doors, Pre-Op to Sterile Corridor by OR 1 |
| Dorma |
| Swing |
| ELSL1-2/10 |
| VA204 |
| √ |
| 023701 |
| S104 |
| Single Door, Men's Room, SDS Waiting Room |
| Horton Automatics |
| Swing |
| PP1-1A/56 |
VA205
| 2.5 SCI |
| Double Doors, Entrance to Sterile Corridor by OR 4 |
| Dorma |
| Swing |
| ELSL2-2/2 |
| Yes |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA206 |
| √ |
| 021286 |
| S413 |
| Double Doors, Entrance/Exit to Recreation Area |
| Dorma |
| Swing |
| ELSL2-4/5 |
| VA207 |
| √ |
| 021287 |
| S415 |
| Double Doors, Entrance/Exit to Dining Area |
| Dorma |
| Swing |
| ELSL2-4/6 |
| VA208 |
| √ |
| 021280 |
| S420A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/31 |
| VA209 |
| √ |
| 021307 |
| S422A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/31 |
VA210
| 021308 |
| S424A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/31 |
| VA211 |
| √ |
| 021309 |
| S426A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/31 |
| VA212 |
| √ |
| 021310 |
| S438A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/17 |
| VA213 |
| √ |
| 021381 |
| S440A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/17 |
VA214
| 021311 |
| S442A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/17 |
| VA215 |
| √ |
| 021314 |
| S444A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/17 |
| VA216 |
| √ |
| 021312 |
| S448A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/35 |
| VA217 |
| √ |
| 021313 |
| S450A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/35 |
| VA218 |
| √ |
| 021315 |
| S456A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/28 |
| VA219 |
| √ |
| 021316 |
| S458A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/28 |
| VA220 |
| √ |
| 021317 |
| S462A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/8 |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA221 |
| √ |
| 021318 |
| S464A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/8 |
| VA222 |
| √ |
| 021319 |
| S468A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/8 |
| VA223 |
| √ |
| 021320 |
| S470A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL1-4/8 |
| VA224 |
| √ |
| 021321 |
| S476A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL2-4/35 |
| VA225 |
| √ |
| 021322 |
| S478A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL2-4/35 |
| VA226 |
| √ |
| 021323 |
| S480A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL2-4/35 |
| VA227 |
| √ |
| 021331 |
| S482A |
| Double Sliding Door, Patient Restroom |
| Dorma |
| Double Sliding |
| EQPL2-4/35 |
| VA228 |
| √ |
| 021288 |
| 5 SCI |
| Single Sliding Door, Inner Entrance /Exit, Terrace |
| Dorma |
| Sliding |
| ELSL2-5/8 |
| VA229 |
| √ |
| 021289 |
| 5 SCI |
| Single Sliding Door, Outer Entrance /Exit, Terrace |
| Dorma |
| Sliding |
| ELSL2-5/8 |
| S110 |
| Single Door, Reception Area to Treatment Area |
| Dorma |
| Swing |
| EQPL1-1/32 |
| VA233 |
| √ |
| 021396 |
| SG10 |
| Single Door, ENDO Waiting Rm Main Entrance |
| Besam |
| Swing |
| EQPL1-G, SECT2/50 |
| Key Lock |
| VA234 |
| √ |
| 021397 |
| SG10 |
| Single Door, ENDO Waiting Rm to Elevator Lobby |
| Besam |
| Swing |
| EQPL1-G, SECT2/50 |
| SG10 |
| Single Door, ENDO Waiting Rm to Exam Rm Corridor |
| Besam |
| Swing |
| EQPL1-G, SECT2/50 |
| VA236 |
| √ |
| 021326 |
| S111 |
| Single Door, SDS Wait Rm to Back |
| Besam |
| Swing |
| ELSL2-1/14 |
| By S128 |
| Single Door, SDS Exam room from Main Corridor |
| Besam |
| Swing |
| ELSL2-1/6 |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| By S128 |
| Single Door, SDS Exam room from Main Corridor |
| Besam |
| Swing |
| ELSL2-1/6 |
| S180 |
| Single Door, Blood Draw Front Entrance |
| Besam |
| Swing |
| ELSL2-1/14 |
| S180 |
| Single Door, Blood Draw Rear Entrance |
| Besam |
| Swing |
| ELSL2-1/14 |
| S471 |
| Single Door, SCI Equipment Storage |
| Besam |
| Swing |
| ELSL1-4/9 |
| VA241 |
| √ |
| 023703 |
| A213 |
| Single Door, Women's Restroom |
| Horton Automatics |
| Swing |
| E2A-C/1 |
| VA242 |
| √ |
| 023704 |
| A215 |
| Single Door, Men's Restroom |
| Horton Automatics |
| Swing |
| E2A-C/1 |
| VA243 |
| √ |
| 023707 |
| A229 |
| Single Door, Men's Restroom |
| Horton Automatics |
| Swing |
| E2A-C/1 |
| VA244 |
| √ |
| 023711 |
| B204 |
| Single Door, Men's Restroom |
| Horton Automatics |
| Swing |
| E2A-A1/14 |
| VA245 |
| √ |
| 023710 |
| B208 |
| Single Door, Women's Restroom |
| Horton Automatics |
| Swing |
| E2A-A1/12 |
| VA246 |
| √ |
| 023709 |
| M200 |
| Single Door, Men's Restroom |
| Horton Automatics |
| Swing |
| E2A-B/9 |
| VA247 |
| √ |
| 023708 |
| M202 |
| Single Door, Women's Restroom |
| Horton Automatics |
| Swing |
| E2A-B/9 |
| VA248 |
| √ |
| 023718 |
| GND. Pass Elev Lobby |
| Single Door from Pass Elevator Lobby or Service Lobby |
| Horton Automatics |
| Swing |
| GA-B/39 |
| VA249 |
| √ |
| 021519 |
| S106 |
| Single Door, Women's Restroom |
| Horton Automatics |
| Swing |
| PP1-1A/51 |
| VA250 |
| √ |
| 023796 |
| 7A Entrance |
| Double Egress Entry to Suite 7A |
| Horton Automatics |
| Swing |
| E7A-A/ 19 |
| Yes |
| AM01 |
| Single Door, Entrance to Business Office/Vet Ser Cntr |
| Horton Automatics |
| Swing |
| 1AE/26 |
| Yes |
| VA # |
| LBL |
| S/N |
| Location |
| Description |
| Manufacture |
| Operator Type |
| Power Source |
| Card Read |
| VA252 |
| √ |
| 021520 |
| Corridor by NG45 |
| Double doors between main building and N wing |
| Horton Automatics |
| Swing |
| S280A |
| Entrance to Corridor 280A |
| Dorma |
| Swing |
| ELSL2-2/8 |
| Yes |
| 1 South |
| Main Lobby to Parking garage ramp |
| Besam |
| Swing |
| 1CNME/18 |
| VA255 |
| √ |
| 021557 |
| 4 SCI |
| Double Doors, Entrance Parking Garage to SCI |
| Norton |
| Swing |
| ELSL1-B/15 |
| Yes |
| VA256 |
| √ |
| 021558 |
| 4 SCI |
| Double Doors, Exit Parking Garage to SCI |
| Norton |
| Swing |
| ELSL1-B/15 |
| Yes |
| VA257 |
| √ |
| 021559 |
| 5 SCI |
| Double Doors, Entrance Parking Garage to SCI |
| Norton |
| Swing |
| ELSL1-B/15 |
| Yes |
| VA258 |
| √ |
| 021560 |
| 5 SCI |
| Double Doors, Exit Parking Garage to SCI |
| Norton |
| Swing |
| ELSL1-B/15 |
| Yes |
VA259
| C848 |
| Sliding Door from ramp to Enclosed Porch |
| Besam |
| Sliding |
| 8C-A/ |
| Key Lock |
VA260
| C848 |
| Single Door, Enclosed Porch to Open Court, East Side Exit |
| Besam |
| Swing |
| 8C-A/ |
VA261
| C848 |
| Single Door, Enclosed Porch to Open Court, South Side Exit |
| Besam |
| Swing |
| 8C-A/ |
VA262
| S243 |
| Single Door, Corridor 270 to Clean Core room |
| Horton Automatics |
| Swing |
VA263
| B135 |
| Single Door, Anteroom to Chemo Prep Room B135B |
| Norton |
| Swing |
| ECR1B-A/ |
VA264
| B135 |
| Single Door, Anteroom to IV Prep Room B135A |
| Norton |
| Swing |
| ECR1B-A/ |
B.3.3 REPORTS
All equipment shall be catalogued by the Contractor and the dates and types of service rendered shall be noted thereon. A legible, written report of each individual door inspection shall be furnished to the Contracting Officer’s Representative (COR). Such report shall advise of any repairs or repair parts, including those not required to be furnished under the contract that are necessary to maintain the equipment in perfect operating condition. A copy of all special codes and abbreviations used on the above furnished report shall be submitted to the COR. If the COR is not available, Contractor shall furnish reports to Syracuse VAMC Electrician’s prior to starting and after finishing all work.
B.3.4 PARTS
Only standard parts (functionally identical to those supplied by the original equipment manufacturer (OEM)) shall be furnished by the Contractor. All parts shall be of current manufacture and shall have full versatility with presently installed equipment. All components replaced shall become the property of the Contractor.
If, during this contract, the Contractor is unable to obtain parts due to manufacturer’s discontinuance of parts, the Contractor shall install at no additional charge any equivalent unit the VA provides, which may or may not be procured from the Contractor.
B.3.5 HOURS OF WORK
Work required in the performance of this contract shall normally be performed during the Medical Center’s regular administrative working hours, 8:00am to 4:30pm est., Monday through Friday, exclusive of Federal holidays.
Excluding Federal Holidays observed by the VAMC which are:
New Year’s Day
Martin Luther King Day
President’s Day
Memorial Day
Independence Day
Labor Day
Columbus Day
Veteran’s Day
Thanksgiving Day
Christmas Day Or any other day the President declares a holiday.
At the request of the Contractor, work at other times shall be scheduled, coordinated, and approved by the Contracting Officer’s Representative (COR) and performed at no additional cost to the government. Upon arriving at the installation to perform services, the Contractor shall report to the COR, Facility Management Service, Building No. 2, before and after performance of service, providing evidence of service performed. If COR is not available, Contractor shall report to Syracuse VAMC Electrician’s prior to starting and after finishing all work.
All work will commence within twenty-four (24) hours after receipt of telephonic, written or verbal notification (from the Contracting Officer or COR only), unless the COR determines it to be an emergency, in such case work shall commence within three (3) hours after receipt of notification and shall proceed progressively to accomplishment without undue delay. All work on this equipment shall be performed by competent mechanics, experienced and qualified to work on the specific equipment, and all work performed shall be first class and in accordance with good commercial practice.
B.3.6 METRIC PRODUCTS
Products manufactured to metric dimensions will be considered on an equal basis with those manufactured using inch-pound units, providing they fall within the tolerances specified using conversion tables contained in the latest revision of Federal Standard No. 376, and all other requirements of this document are met. If a product is manufactured to metric dimensions and those dimensions exceed the tolerances specified in the inch-pound units, a request should be made to the Contracting Officer to determine if the product is acceptable. The Contracting Officer, in concert with the Contracting Officer’s Representative (COR), will accept or reject the product.
B.3.7 SAFETY REQUIREMENTS
In the performance of this contract, the Contractor shall take such safety precautions as the Contracting Officer or his/her designee may determine to be reasonably necessary to protect the lives and health of occupants of the building. The Contracting Officer or his/her designee will notify the contractor of any noncompliance with the foregoing provisions and the action to be taken. The Contractor shall, after receipt of such notice, immediately correct the conditions to which attention has been directed. Such notice, when served on the Contractor or his/her representative at the site of the work, shall be deemed enough for the purpose aforesaid. If the Contractor fails or refuses to comply promptly, the Contracting Officer may issue an order stopping all and any part of the work and hold the Contractor in default.