This is a Statement of Work for Portsmouth Naval Shipyard (PNSY) seeking to purchase insulated flexible ventilation ductwork for temporary HVAC systems in an industrial outdoor environment.
The primary requirement is flexible insulated ducting with a nominal inside diameter of 20 inches in standard 25-foot long sections. The duct must have a minimum R-Value insulation rating of R-6 and be constructed of high-strength sewn two single-ply polyurethane-coated polyester fabric plies protecting a proprietary insulation barrier reinforced with spring steel wire helix and heavy-duty external PVC wearstrip. Both interior and exterior layers must meet UL94 fire resistance standards with a V-0 flame retardant rating, and each duct section must be labeled "FR." The ductwork must feature excellent UV stabilization and mold/mildew inhibitors for rigorous continuous outdoor exposure, operate within a temperature range of -60°F to +400°F, support positive working pressure of 30 IN/W.G., achieve full flexibility with a 14-degree bend radius or less, and compress at a 12:1 ratio or better. Material colors of yellow or magenta are strictly prohibited; exterior and interior fabric colors must be white. The duct must be new, not previously used or returned from lease, and the contractor must perform careful physical examination of each duct piece fully-extended prior to shipment to verify integrity and absence of damage, debris, chemicals, burns, cuts, mildew, rot, vermin, or permanent kinks. The approved model is Flexaust FX-400 IF. Delivery to site must be on or prior to the request date in fully-charged, fully-assembled, ready-to-use condition with accompanying documentation. The contractor is responsible for coordinating delivery timing with the designated Point-of-Contact and Contracting Officer's Representative. Receipt inspection by the government will similarly require full extension examination of each duct piece for the same quality criteria, with final acceptance by Portsmouth Naval Shipyard Code 420 COR forwarded to Code 220 Production Support Equipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ SPMYM326Q1125 0002.pdf | ||
| RFQ SPMYM326Q1125 0001.pdf | ||
| RFQ SPMYM326Q1125.pdf | ||
| Clauses - Full Text Provisions and Clauses.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Temporary Ventilation Support Equipment- Insulated Flex Duct
Spec #: 460INSDUCT Rev: Orig. Page 1 of 3
STATEMENT OF WORK
1. SCOPE
1.1. Portsmouth Naval Shipyard (PNSY) is seeking to purchase insulated ductwork to support temporary HVAC systems. The Insulated ductwork will be installed in an industrial outdoor environment and must be able to withstand the harsh weather elements. The duct size must be 20 IN nominal inside diameter and in standard lengths of 25 FT long sections.
2. REFERENCES
2.1. Issues of Publications - The following documents in effect on the date of this requested proposal is a part of this specification to the extent applicable, or as specified herein. Within the specification, they shall be referred to by their basic designation only.
2.1.1. Government
2.1.1.1. N/A
2.1.2. Nongovernment
2.1.2.1. Fire Standard: UL94
3. REQUIREMENTS
3.1. Component List
3.1.1. Required component Qtys provided on a separate spread sheet.
3.2. Insulated Flexible Ventilation Duct
3.2.1. Flexible insulated ducting, 20 IN diameter @ 25 FT long per section.
3.2.2. Total length required: Qty specified On a separate spread sheet.
3.2.3. Insulating R-Value: Minimum of R-6
3.2.4. Construction: High strength sewn two single-ply polyurethane coated polyester fabric plies protecting a proprietary insulation barrier reinforced with a spring steel wire helix & heavy-duty external PVC wearstrip.
3.2.4.1. Interior and exterior layers must meet fire resistance performance rating as defined by the reference in 2.1.2.1
3.2.4.2. Lock stitch construction with sewn cuff containing integral wire rope locking rings to enable multiple duct sections to be connected in series without requiring additional couplers or fittings
3.2.5. Exterior and interior fabric color must be white.
3.2.6. Both inner and outer duct layers must be tested per reference in section 2.1.2.1 and must be classified to have a flame retardant rating of V-0.
3.2.7. Each duct section must be labeled �FR�
3.2.8. Duct working pressure (Positive): 30 IN/W.G.
3.2.9. The ducting must feature excellent UV stabilization; mold and mildew inhibitors; and be constructed for rigorous and continuous outdoor exposure in such a harsh environment.
3.2.10. Application temperature range: -60°F / +400°F
3.2.11. The fully-flexible (14� bend radius or less) and fully-compressible (12:1 ratio or better) ducting shall be transported to the site and staged/stored at the site in pallet-sized wire baskets.
Rev: Orig. Page 2 of 3
3.2.12. The purchased duct must be new and not used or returned from a previous lease.
4. NOTES
4.1. Ducting constructed with material colors of yellow or magenta is strictly prohibited.
4.2. The Vendor must perform a careful physical examination of the ducting just prior to shipment. A physical examination requires that each individual piece of ducting is fully-extended in order to perform an adequate visual check of the product. The ducting material shall: (i) not be torn, accept for the minor pin hole type penetrations near the end finish wire ring ducting ends for the insertion of security tie-wraps to be installed after ducting interlocking; (ii) not be damaged nor vandalized; (iii) be clean and free of debris;
(iv) lack indication of chemicals, burns, cuts, or abrasion; (v) not exhibit signs of mildew, rot, nor vermin;
(vi) not have permanent kinks in the wire-reinforcement helix; and especially (vii) not have damaged nor bent wire end rings for the ducting with the end finish for the ducting ends.
5. GOVERNMENT FURNISHED MATERIAL (GFM)
5.1. N/A
6. RESPONSIBILITITES
6.1. Government
6.1.1. N/A
6.2. Contractor
6.2.1. Material supplied must meet all requirements specified within this SOW.
7. DELIVERY
7.1. Delivery - The machinery shall be in a fully-charged, fully-assembled, ready-to-use, and in a first-class-operating condition. Machines shall be functionally tested. The machinery with its support equipment shall be delivered to the site on or prior to the request date. It is incumbent and the responsibility of the Contractor to either confirm or coordinate the date and time of delivery prior to each shipment via the Point-of-Contact (POC) as designated on the Contract and/or the Contracting Officer's Representative (COR). The Government can provide forklift services for removing machinery from Vendor�s transport during work hours. Documentation with Shipyard copies shall accompany each delivery.
7.2. Security - To be allowed onto a government Shipyard, personnel must be US citizens and in possession of appropriate personal identification. Proof of US citizenship may be necessary and can be required for access to the drydock. Allowable documentation of US citizenship is an official government issued Certificate of Birth or Naturalization (w/ raised seal & not a photocopy) or a US passport (can be expired).
Vehicular access requires a non-expired personal Driver�s License and appropriate vehicle identification or registration. The transport vehicle must have the company�s name / logo prominently displayed. To gain access to the drydock environs, personnel must be escorted and possess / wear their own personal safety gear.
7.3. Inspection Criteria
7.3.1. Receipt Inspection must perform a careful physical examination of the ducting just upon delivery. A physical examination requires that each individual piece of ducting is fully-extended in order to perform an adequate visual check of the product. The ducting material shall: (i) not be torn, accept for the minor pin hole type penetrations near the end finish wire ring ducting ends for the insertion of security tie-wraps to be installed after ducting interlocking; (ii) not be damaged nor vandalized;
Rev: Orig. Page 3 of 3
(iii) be clean and free of debris; (iv) lack indication of chemicals, burns, cuts, or abrasion; (v) not exhibit signs of mildew, rot, nor vermin; (vi) not have permanent kinks in the wire-reinforcement helix; and especially (vii) not have damaged nor bent wire end rings for the ducting with the end finish for the ducting ends. Final Acceptance - Upon satisfactory completion of inspection and test of the equipment, the authorized Government Representative (Portsmouth Naval Shipyard, Code 420 Project COR) will sign and forward the acceptance document(s) to Code 220 Production Control for completion. Unloading of equipment from Vendor�s transport does not signify acceptance.
7.4. Acceptance - Upon satisfactory completion of inspection and test of the equipment, the authorized Government Representative (Portsmouth Naval Shipyard, Code 420 COR) will sign and forward the acceptance document(s) to Code 220 Production Support Equipment for completion. Unloading of equipment from Vendor�s transport does not signify acceptance.
8. GENERAL
8.1. Response to Request - As part of the response to this request, descriptive literature shall be furnished in sufficient detail to show that the proposed design will meet these specifications. Vendor submittals shall include brochures of the model being submitted, assembly sketches with critical dimensions, sketches (with dimensions) of all tooling being provided, statements of compliance with specification, and performance statements with special instructions. Supporting information shall be organized and packaged by unit. If supporting information includes multiple models the vendor shall clearly state model number of proposed unit and redact all information not applicable to proposed unit.
8.2. Approved Models- Flexaust FX-400 IF
8.2.1. https://www.flexaust.com/product/fx-400-if/
9. Attachments
N/A
Flex Tube Thermoplastic Rubber � Fire Retardant 8� (TR-FR 8�)
Medium weight co-extruded thermoplastic rubber hose with a rigid external polypropylene helix.
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Inside Diameter: 8�
Approx. Weight: 1.5 lbs. /ft.
Wall Thickness .035�
CL Bend Radius: 9.75�
Compression Ratio: 2:1
Negative Pressure: 12 in. / hg, Working Pressure: 8 PSI
Temperature Range: -60F to 275F
Color: Based on application. See JML
Length: 24 feet
VENT DUCT MUST BE MARKED �FR� AND SHALL BE PLACED EVERY FOOT (12").
FONT SIZE, LETTER STYLE AND INK COLOR NOT SPECIFIED, BUT MARKING SHALL
BE PERMANENT AND CLEARLY LEGIBLE.
Flex Tube Thermoplastic Rubber – TR-FR
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Temperature Range: -60F to 275F
Length: 24 feet
Inside Diameter: 3” o Approx. Weight: .45 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 4” o Compression Ratio: 2:1 o Negative Pressure: 22 in. / hg, o Working Pressure: 15 PSI
Inside Diameter: 4” o Approx. Weight: .6 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 5” o Compression Ratio: 2:1 o Negative Pressure: 20 in. / hg, o Working Pressure: 12 PSI
Inside Diameter: 6” o Approx. Weight: 1 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 7” o Compression Ratio: 2:1 o Negative Pressure: 16 in. / hg, o Working Pressure: 10 PSI
Inside Diameter: 8” o Approx. Weight: 1.5 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 9.75” o Compression Ratio: 2:1 o Negative Pressure: 12 in. / hg, o Working Pressure: 8 PSI
Color: Based on application. See JML
Flex Tube R-3 Blue – (R-3)
Heavy weight PVC hose reinforced with a coated spring steel wire helix (sizes 14" I.D. & above not available with a coated wire) environmentally friendly
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Spiral co-extruded engineered construction
Helix must protect against wear (abrasion resistance)
Moisture resistant
Chemical resistant
Fire retardant (FR) (UL 94-V2 material compliance)
Temperature Range: 20F to 160F
Length: 24 feet
Inside Diameter: 8” o Approx. Weight: .1.8 lbs. /ft.
o Wall Thickness .45” o CL Bend Radius: 7.7” o Compression Ratio: 2:1 o Negative pressure: 3 in. / hg.
o Working Pressure: 11 PSI
Color: Blue
ALL VENT DUCT MUST BE MARKED “TR-FR” OR “EF – FR” AND SHALL BE PLACED
EVERY FOOT (12"). FONT SIZE, LETTER STYLE AND INK COLOR NOT SPECIFIED, BUT
MARKING SHALL BE PERMANENT AND CLEARLY LEGIBLE.
Aluminum Flexible Hose Assembly
Unlined with NO PACKING- interlocking flexible aluminum hose assembly
Manufactured thickness required to .019” - .020”
Unlocked and deburred end cuts
Length: 20ft
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Temperature Range: -60F to 275F
Length: 24 feet
Inside Diameter: 3” o Approx. Weight: .45 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 4” o Compression Ratio: 2:1 o Negative Pressure: 22 in. / hg, o Working Pressure: 15 PSI
Inside Diameter: 4” o Approx. Weight: .6 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 5” o Compression Ratio: 2:1 o Negative Pressure: 20 in. / hg, o Working Pressure: 12 PSI
Inside Diameter: 6” o Approx. Weight: 1 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 7” o Compression Ratio: 2:1 o Negative Pressure: 16 in. / hg, o Working Pressure: 10 PSI
Inside Diameter: 8” o Negative Pressure: 12 in. / hg, o Working Pressure: 8 PSI
Color: Based on application. See JML
Flex Tube R-3 Blue – (R-3)
Heavy weight PVC hose reinforced with a coated spring steel wire helix (sizes 14" I.D. & above not available with a coated wire) environmentally friendly
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Spiral co-extruded engineered construction
Helix must protect against wear (abrasion resistance)
Moisture resistant
Chemical resistant
Fire retardant (FR) (UL 94-V2 material compliance)
Temperature Range: 20F to 160F
Length: 24 feet
Inside Diameter: 8” o Approx. Weight: .1.8 lbs. /ft.
o Wall Thickness .45” o CL Bend Radius: 7.7” o Compression Ratio: 2:1 o Negative pressure: 3 in. / hg.
Manufactured thickness required to .019” - .020”
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Temperature Range: -60F to 275F
Length: 24 feet
Inside Diameter: 3” o Approx. Weight: .45 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 4” o Compression Ratio: 2:1 o Negative Pressure: 22 in. / hg, o Working Pressure: 15 PSI
Inside Diameter: 4” o Approx. Weight: .6 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 5” o Compression Ratio: 2:1 o Negative Pressure: 20 in. / hg, o Working Pressure: 12 PSI
Inside Diameter: 6” o Approx. Weight: 1 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 7” o Compression Ratio: 2:1 o Negative Pressure: 16 in. / hg, o Working Pressure: 10 PSI
Inside Diameter: 8” o Negative Pressure: 12 in. / hg, o Working Pressure: 8 PSI
Color: Based on application. See JML
Flex Tube R-3 Blue – (R-3)
Heavy weight PVC hose reinforced with a coated spring steel wire helix (sizes 14" I.D. & above not available with a coated wire) environmentally friendly
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Spiral co-extruded engineered construction
Helix must protect against wear (abrasion resistance)
Moisture resistant
Chemical resistant
Fire retardant (FR) (UL 94-V2 material compliance)
Temperature Range: 20F to 160F
Length: 24 feet
Inside Diameter: 8” o Approx. Weight: .1.8 lbs. /ft.
o Wall Thickness .45” o CL Bend Radius: 7.7” o Compression Ratio: 2:1 o Negative pressure: 3 in. / hg.
Manufactured thickness required to .019” - .020”
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Temperature Range: -60F to 275F
Length: 24 feet
Inside Diameter: 3” o Approx. Weight: .45 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 4” o Compression Ratio: 2:1 o Negative Pressure: 22 in. / hg, o Working Pressure: 15 PSI
Inside Diameter: 4” o Approx. Weight: .6 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 5” o Compression Ratio: 2:1 o Negative Pressure: 20 in. / hg, o Working Pressure: 12 PSI
Inside Diameter: 6” o Approx. Weight: 1 lbs. /ft.
o Wall Thickness .035” o CL Bend Radius: 7” o Compression Ratio: 2:1 o Negative Pressure: 16 in. / hg, o Working Pressure: 10 PSI
Inside Diameter: 8” o Negative Pressure: 12 in. / hg, o Working Pressure: 8 PSI
Color: Based on application. See JML
Flex Tube R-3 Blue – (R-3)
Heavy weight PVC hose reinforced with a coated spring steel wire helix (sizes 14" I.D. & above not available with a coated wire) environmentally friendly
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Spiral co-extruded engineered construction
Helix must protect against wear (abrasion resistance)
Moisture resistant
Chemical resistant
Fire retardant (FR) (UL 94-V2 material compliance)
Temperature Range: 20F to 160F
Length: 24 feet
Inside Diameter: 8” o Approx. Weight: .1.8 lbs. /ft.
o Wall Thickness .45” o CL Bend Radius: 7.7” o Compression Ratio: 2:1 o Negative pressure: 3 in. / hg.
Manufactured thickness required to .019” - .020”
Flex Tube Thermoplastic Rubber – Fire Retardant 3” (TR-FR 3”)
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Inside Diameter: 3”
Approx. Weight: .45 lbs. /ft.
Wall Thickness .035”
CL Bend Radius: 4”
Compression Ratio: 2:1
Negative Pressure: 22 in. / hg, Working Pressure: 15 PSI
Temperature Range: -60F to 275F
Color: Based on application. See JML
Length: 24 feet
VENT DUCT MUST BE MARKED “FR” AND SHALL BE PLACED EVERY FOOT (12").
Flex Tube Thermoplastic Rubber – Fire Retardant 4” (TR-FR 4”)
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Inside Diameter: 4”
Approx. Weight: .6 lbs. /ft.
Wall Thickness .035”
CL Bend Radius: 5”
Compression Ratio: 2:1
Negative Pressure: 20 in. / hg, Working Pressure: 12 PSI
Temperature Range: -60F to 275F
Color: Based on application. See JML
Length: 24 feet
VENT DUCT MUST BE MARKED “FR” AND SHALL BE PLACED EVERY FOOT (12").
Flex Tube Thermoplastic Rubber – Fire Retardant 6” (TR-FR 6”)
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Inside Diameter: 6”
Approx. Weight: 1 lbs. /ft.
Wall Thickness .035”
CL Bend Radius: 7”
Compression Ratio: 2:1
Negative Pressure: 16 in. / hg, Working Pressure: 10 PSI
Temperature Range: -60F to 275F
Color: Based on application. See JML
Length: 24 feet
VENT DUCT MUST BE MARKED “FR” AND SHALL BE PLACED EVERY FOOT (12").
Flex Tube Thermoplastic Rubber – Fire Retardant 8” (TR-FR 8”)
Ultra smooth interior to maximize efficiency of airflow
Highly flexible
Tight bend radius without crimping
Crush resistant
Moisture resistant
Chemical resistant
Designed for applications with wide temperature ranges
Spiral co-extruded engineered construction
Helix must protect against wear
Fire Retardant (FR) (UL 94-V0 material compliance)
Inside Diameter: 8”
Approx. Weight: 1.5 lbs. /ft.
Wall Thickness .035”
CL Bend Radius: 9.75”
Compression Ratio: 2:1
Negative Pressure: 12 in. / hg, Working Pressure: 8 PSI
Temperature Range: -60F to 275F
Color: Based on application. See JML
Length: 24 feet
VENT DUCT MUST BE MARKED “FR” AND SHALL BE PLACED EVERY FOOT (12").