This document is a Statement of Work (SOW) for a requirement to replace refrigeration components for a tree cooler at the USDA Tahoe National Forest, Foresthill Ranger District location. The SOW outlines the contractor requirements, including dismantling and removing the existing mechanical refrigeration equipment, installing a new outdoor condensing unit and indoor evaporator system, running new refrigeration piping, and charging the system with new refrigerant. The work must be completed within 30 days of award, and no government-furnished equipment or travel is required. The contractor must provide a professional journeyman-class technician to perform the work. This SOW is associated with Solicitation Number 12970224Q0049, issued by the USDA Forest Service, for the Tree Cooler Repair requirement. Responses are due by 1700hrs on 26 July 2024 and should be sent to Veronica.Beck@usda.gov.

View the file

Other files for this federal contract opportunity

Other files attached to Tree Cooler Repair, newest first.
File Type Posted
12970224Q0049 RFQ AARD Cooler Repair Clauses and Provisions.pdf PDF
12970224Q0049 RFQ AARD Cooler Repair.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Department of Agriculture (USDA)

Statement of Work

Contents Project General Information

1.0 Scope of Work

2.0 Background

Contractor Requirements

3.0 Technical Requirements / Tasks

4.0 Government Furnished

5.0 Deliverables / Schedule

6.0 Travel

7.0 Contractor’s Key Personnel

8.0 Security Requirements

9.0 Data Rights

10.0 Section 508 – Electronic and Information Technology Standards Attachment ............................................................................................................................................. Error! Bookmark not defined.

Project ARRD Cooler Repair

General Information

1.0 Scope of Work

Replace refrigeration components for the tree cooler.

2.0 Background

The tree cooler is no longer functioning. The cooler needs to maintain a temperature of 32-36 degrees.

Contractor Requirements

3.0 Technical Requirements / Tasks

Dismantle and remove existing Mechanical Refrigeration equipment from site. Install new Outdoor condensing unit in place of old one. Install new Indoor evaporator system with new TXV, solenoid valve and coil and new temp/defrost controls. Run new insulated refrigeration copper pipe from outdoor unit to new indoor unit. Braze all connections, Pressure test with Nitrogen to 300 PSI and pull vacuum on refrigeration system to hold at 500 microns to prove leak free. Charge system with all new R-448 refrigerant. Start up and test equipment. Set all controls for proper operation.

Outdoor Condensing Unit, 2 horsepower, 1 phase, 208/230 volts Indoor Evaporator Assembly All Necessary Valves and Controls The cooler needs to maintain a temperature of 32-36 degrees.

Location:

FORESTHILL RANGER DISTRICT

22830 FORESTHILL RD

FORESTHILL CA 95631

4.0 Government Furnished

None.

5.0 Deliverables / Schedule

Complete work within 30 days of award.

6.0 Travel

None

7.0 Contractor’s Key Personnel

Professional journeyman class technician

8.0 Security Requirements

None

9.0 Data Rights

None

10.0 Section 508 – Electronic and Information Technology Standards None

Project
General Information
1.0 Scope of Work
Replace refrigeration components for the tree cooler.
2.0 Background
Contractor Requirements
3.0 Technical Requirements / Tasks
4.0 Government Furnished
5.0 Deliverables / Schedule
6.0 Travel
7.0 Contractor’s Key Personnel
8.0 Security Requirements
9.0 Data Rights
10.0 Section 508 – Electronic and Information Technology Standards

File details come from the government source that posted it. Updated .