Statement of Work / Performance Work Statement For Enid Lake Field Office
(1) Generac 50kW (minimum output) commercial diesel generator with auto transfer switch Scope of Work. Provide, deliver and install (1) Generac 50+kW commercial diesel generator with auto transfer switch meeting or exceeding the below specifications. This is a replacement for current Generac unit. Existing gen set and transfer switch will need to be removed by contractor prior to install.
Address for delivery: 264 County Road 39 Enid MS 38927
Period of Performance: All work shall be completed within 34 weeks of contract award.
Hours of Operation: Hours of operation for delivery shall be between the hours of 0700 and 1530 Monday through Friday (except federally observed holidays), unless special arrangements are made in advance.
Equipment must be of equal or greater quality and specifications listed below.
Breakdown of Generac diesel generator and auto transfer switch includes the following. Products shall be of equal or greater quality and specifications listed in description below:
(1) 50+kW commerical diesel powered generator with auto transfer switch with the following options;
· Stationary emergency-standby rated
· 50kW minimum rating, wired for 120/240 VAC three phase. 60 Hz
· Diesel engine
· Control panel ( Digital ) for gen set
· 100 gallon minimum, double walled fuel tank. Safety vented, low fuel switch, mechanical fuel level gauge
· Battery charger 120V
· Cranking battery of sufficient rating for power unit with battery holder/rack
· No Enclosure or casing required for gen-set
· Flex Exhaust
· EPA certified
· Critical Silencer
· Block Heater or Coolant Heater 120V
· Owner and Service manuals
· Standard warranty
(1) Automatic transfer switch meeting or excedding the following minimum options;
· 300Amp minimum, 3 pole 120/240 VAC three phase, 60 Hz
· NEMA 1 enclosure
· Programmable exerciser
· Lockable controller cover
· UL 1008 listed
· LCD display
· CSA- C22.2 No.178
· IBC Seismic Certified
· Non Service Entrance Rated
· In Phase Only Transfer
· Heater installed
· Outdoor rated enclosure
· Available non automatic operation without opening enclosure
· Owners manual
· Standard warranty
(1) Removal of existing gen set and auto transfer switch. Existing units will be left on site. Contractor only responsible for removing units. USACE employees will haul away old units. Removal of unit will include electrical connections and physical connections of gen set and transfer switch.
(1) Installation and setup of gen set and automatic transfer switch, including minimum (1) one hour of onsite training. Installation will include all wiring and connections of electrical components need for unit to operate per manufactures specs. Installation will meet all OSHA and NEMA electrical specifications for safety.