Federal Bureau of Prisons Federal Correctional Institution (FCI) Texarkana, Texas
Statement of Work (SOW) Construct Concrete Slab Foundation
Project 5D5S Replace Freezers
PART 1 – GENERAL
1.0 SUMMARY
A. The Federal Bureau of Prisons (FBOP) intends to make a single award to a responsible entity for the site preparation and construction of a new concrete foundation at the camp.
B. Strip to remove all top soil, gravel, and other deleterious materials from the subgrade to a minimum of 1 foot below the existing grade.
C. Over excavated a minimum of 4 feet below existing grade and replace with compacted select fill. The over-excavation should extend a minimum of 3 feet beyond the edge of the footing. After the excavation is complete and prior to the placement of fill, scarify the exposed subgrade to a depth of 12 inches, adjust the moisture content to, and maintain it within a range optimum to optimum+4% and re-compact to a minimum density of 98% of the maximum density defined by ASTM D 698(Standard Procter). Maintain specified moisture content until the subgrade is covered with fill or slab.
D. All concrete shall be 3000psi unless noted otherwise E. All concrete shall be installed to elevations and dimensions shown on shop drawings.
F. All concrete flat work shall have a broom finish.
G. All footings shall be poured monolithic. Concrete flat work (slabs) may be poured in sections utilizing a “key way” for cold joints. See detail F/S1 H. All footings shall be a minimum depth of 18”.
I. All reinforcement shall have a minimum of 1 ½ “concrete coverage. Use bar chairs where needed. (Do not allow rebar to come in contact with soil.)
J. All rebar shall be cold formed. Do not use heat to form bent bars or stirrups.
64'-11"
17'-8"17'-8"17'-8"17'-8"
93'-3"
12'-0"
2'-2"
1'-0"
2'-2" 2'-2" 2'-2"
107'-11 4"
100'
23'-0116 "
23'
0'-4"0'-2" Varies
1'-6"
1'-0"
Varies
18" o/c max
0'-4"0'-2"
1'-6"
Varies
1'-0"
0'-4" 0'-4"1'-0" 0'-2"
0'-758"
18" o/c max
0'-4"0'-2"
1'-6"
1'-0"
0'-6"
1'-0"
1'-6"
1'-6"
0'-6"
Varies
2'-0"
2'-0"
0'-4"0'-2"
1'-6"
Varies
1'-0"
0'-4" 0'-4"1'-0" 0'-2"
0'-618"
18" o/c max
U .S
. D E
P A
R
TM
E N
T O
F
JU
S
TI
C E
FE
D
ER
AL
B U
R
EA
U O
F
PR
IS
O
N S
S O
U
TH
C E
N
TR
A L
R E
G
IO
N
St ru ct ur al
S1
Date:No.
Sheet No.
Checked By:
Date:
Sh ee t T itl e:
Drawn By:
Project No.
File No.
Pr oj ec t T itl e:
ER
S
P E
F O
T N E
MT RA
FEDD
CITSUJ
S NOE
O
AL
BU
R E
A U
F
PRI
Legend:
Cut line Direction of View
Detail # Sheet #
BS1
A
CS1
DS1
DS1
Notes:
1. New concrete freezer/cooler foundation.
2. New concrete landing for loading/unloading. Landing shall be 4000psi concrete. 3000psi concrete may be used for footings.
3. #3 rebar 18" o/c each way.
4. #3 bent rebar installed 18" o/c. See detail J/S1.
5. #6 rebar continuous. Maximum 18" o/c. Minimum 18" overlap at all splice joints. Join corners using 4 @ #6 bent bars. See detail G/S1.
6. #3 rebar stirrups 32" o/c. See detail I/S1.
7. #3 rebar stirrups 32" o/c. See detail H/S1. Length of stirrup will vary with ground slope.
8. 2 @ #6 rebar continuous.
9. #6 x 18" rebar dowels 18" o/c.
10. Compacted sand.
11. Compacted fill. Depth will vary with existing soil elevation.
12. 12" asphaltic expansion joint. Apply sealant at finished joint. Sonneborn NP 1 or equal.
13. Formed "key way" for cold joint in concrete slabs.
14. Existing elevation.
15. New finished grade.
16. Existing Asphalt
= 99'-11"
= 99'-4 78"
= 99'-3 38"
= Elevation
= 99'-3 38"
= 99'-3 38"
= 99'-3 38"
General Notes:
1. All concrete shall be 3000psi unless noted otherwise.
2. All concrete shall be installed to elevations and dimensions shown on drawings.
3. All concrete flatwork shall have a broom finish.
4. All footings shall be poured monolithic. Concrete flatwork (slabs) may be poured in sections utilizing a "key way" for cold joints. See detail F/S1.
5. All footings shall be a minimum depth of 18".
6. All reinforcement shall have a minimum of 1 12" concrete coverage. Use bar chairs where needed. (Do not allow rebar to come in contact with soil.)
7. All rebar shall be cold formed. Do not use heat to form bent bars or stirrups.
8. Walk-ins shall be anchored using Hurricane Anchors provided by Polar King and shall be installed as per manufacturers specifications. See detail K/S1 (by Polar King)
B D
C
F
G
H I
J
3 3
23 3
4 4
6 7
9 9
12 13
CS1CS1CS1ES1
DS1
E
Typical
= 99'-09" = 97'-11"
= 97'-02"
= 98'-09 3/8"= 98'-07"
= 98'-09 3/8"
Revisions
FC
I T
EX
A
R K
A N
A
5D5S
R
EP
LA
C
E
FR
EE
ZE
R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text North
AutoCAD SHX Text East
AutoCAD SHX Text West
AutoCAD SHX Text South
AutoCAD SHX Text Plan
AutoCAD SHX Text North
| freezer pad5.pdf |
| Sheets and Views |
| FREEZER PAD-3 S1 |
File details come from the government source that posted it. Updated .