PPR – SELA-BAYOU SAUVAGE ABOVEGROUND FUEL TANKS
Fuel Tanks for Bayou Sauvage Urban National Wildlife Refuge A total of (3) new fuel tanks, (2) 1000 gallon above ground fuel tanks and (1) 2000 gallon above ground fuel tank delivered to: Southeast Louisiana Refuges Complex, 61389 Hwy 434, Lacombe LA 70445 Minimum Fuel Tank Specifications:
· Horizontal double walled
· UL-142 steel tanks for flammable and combustible fluids
· Inner gauge – 7 gauge
· Outer gauge – 10 gauge
· Supports- (4) skids full length with anchor plates – 7 gauge
· Fill opening- (1) 4” 150# Full Coupling w/Repad
· Pump opening- (1) 2” 150# Full Coupling w/Repad
· Gauge opening –(1) 2” 150# Full Coupling w/Repad
· Op vent opening- (1) 2” 150# Full Coupling w/Repad
· E-vent opening- (1) 6” Sch 40 Nipple (Inner E-Vent) w/ Repad
· E-vent opening- (1) 6” Sch 40 Nipple (Outer E-Vent)
· Leak Monitor - (1) 2” monitoring pipe (MNPT)
· Lift lug (2) small lift lug
· Remote gage opening- (1) 2” 150# full coupling w Repad
· Labeling- Set- Labeled per UL 142
· Surface preparation- brush blast
· Paint- Epoxy Paint
· Color- White
· Length- 2000 gallon not to exceed 150”; 1000 gallon not to exceed 76”
· Outside diameter- 2000 and 1000 gallon tanks not to exceed 67