This Statement of Work (SOW) details preventative maintenance requirements for air compressors at Bradley Air National Guard Base in East Granby, Connecticut. The 103rd Maintenance Group requires a qualified vendor to perform maintenance on two specific pieces of equipment located in Building 25: a Powerex Breathing Air Compressor (Model SEH3007E0AJ) and a Hankinson Breathing Air Dryer Unit (Model 95CBA).
The maintenance tasks include comprehensive service for the Powerex compressor, such as replacing one scroll pump, servicing five remaining pumps, checking pulley alignment and rotation, replacing belts and check valves, replacing pump tip seals, greasing pumps, verifying electrical specifications, checking for leaks, and adjusting system pressure. An additional requirement is to wire an inline audible alarm on the Hankinson air dryer supply side. The document also outlines strict security and access procedures, including background checks, identity verification, and mandatory AT Level I awareness training for contractor personnel accessing the National Guard installation.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bradley Air National Guard Base
103rd Maintenance Group 161 Rainbow Road East Granby, CT 06026
April 24, 2025
CTANG Breathing Air and Building Compressor Maintenance
Statement of Work (SOW)
PART I – BACKGROUND
Bradley Air National Guard Base (ANGB) is home to the 103rd Airlift Wing (AW) based at Bradley International Airport, CT. The 103rd AW flies the C-130 aircraft in support of tactical operations in the United States and overseas, fulfilling a wide range of operational missions in both peace and war situations.
PART II – GOALS AND OBJECTIVES
The 103d Maintenance Group requires preventative maintenance services for air compressors.
PART III: SCOPE OF WORK
The Connecticut Air National Guard requires a qualified vendor to perform service on various types of air compressors. The objective of the service is to conduct preventative maintenance tasks on the following equipment:
Location Manufacturer Model Serial Number Breathing Air Compressor, Building 25 Powerex SEH3007E0AJ 5953555-263 Breathing Air Dryer Unit, Building 25 Hankinson 95CBA 1000003133733
PART IV: APPLICABLE DOCUMENTS
The following documents and sources shall be considered a minimum of documents applicable to this project:
PART V: TASKS
1. BLDG 25 Powerex Breathing Air Compressor Scroll Pumps Replacement
1. Remove and replace 1 each SLAE05E pump (6)
2. Service 5 remaining pumps
3. Check the pump and motor pulley alignment
4. Check rotation
5. Replace belts
6. Replace in line check valves
7. Replace all pump tip seals
8. Grease all pumps
9. Check that volt-amps are within specification
10. Check for any air or oil leaks
11. Adjust system pressure and leave online
2. BLDG 25 Hankinson Breathing Air Dryer Unit
1. Wire an inline audible alarm on the air dryer supply side. The customer will run wire from their panel to air dryer.
PART VI – ACCESS AND GENERAL PROTECTION/SECURITY POLICY & PROCEDURES
Access and General Protection/Security Policy and Procedures. This standard language is for contractor employees with an area of performance within Government controlled installation, facility, or area. The contractor shall comply with all applicable installation/facility access and local security policies and procedures, which may be obtained from the Contracting Officer’s Representative (COR). The contractor shall also provide all information required for background checks to meet installation access requirements to be accomplished by the local installation’s Security Forces, Director of Emergency Services or local Security Office. The contractor shall ensure compliance with all personal identity verification requirements as directed by DoD, HAF and/or local policy. Should the Force Protection Condition (FPCON) change, the Government may require changes in contractor security matters or processes.
PART VII - FOR CONTRACTORS REQUIRING COMMON ACCESS CARD (CAC):
Before CAC issuance, the contractor employee requires, at a minimum, a favorably adjudicated National Agency Check with Inquiries (NACI) or an equivalent or higher investigation in accordance with Army Directive 2014-05. The contractor employee will be issued a CAC only if duties involve one of the following:
(1) Both physical access to a DoD facility and access, via logon, to DoD networks on-site or remotely; (2) Remote access, via logon, to a DoD network using DoD-approved remote access procedures; or (3) Physical access to multiple DoD facilities or multiple non-DoD federally controlled facilities on behalf of the DoD on a recurring basis for a period of 6 months or more. At the discretion of the sponsoring activity, an initial CAC may be issued based on a favorable review of the FBI fingerprint check and a successfully scheduled NACI at the Office of Personnel Management.
PART VIII - AT LEVEL I TRAINING: This provision/contract text is for contractor employees with an area of performance within a National Guard controlled installation, facility or area. All contractor employees, to include subcontractor employees, requiring access to National Guard installations, facilities and controlled access shall complete AT Level I awareness training. The contractor shall submit certificates of completion for each affected contractor employee and subcontractor employee, to the Contracting Officer’s Representative (COR).
mailto:desk@mail.mil
| PART I – BACKGROUND |
| PART II – GOALS AND OBJECTIVES |
| PART III: SCOPE OF WORK |
| PART IV: APPLICABLE DOCUMENTS |
| PART V: TASKS |
| PART VII – ACCESS AND GENERAL PROTECTION/SECURITY POLICY & PROCEDURES |
| PART VIII - FOR CONTRACTORS REQUIRING COMMON ACCESS CARD (CAC): |
| PART X - POINTS OF CONTACT: |
File details come from the government source that posted it. Updated .