Central Arkansas Veterans Healthcare System Statement of Work (SOW)

A. GENERAL GUIDANCE

1. Title of Project: Install emergency power connections to Emergency Management warehouses (building 200 &201).

2. Scope of Work:

· Furnish and install (1) 600A Square D Breaker to match existing main breaker with locking device in Main Switch Gear at each Building.

· Furnish and install (1) 24”x24”x12” Nema 3R J-Box with (10) (2 for Each Phase, 2 Neutrals, and 2 Grounds) Panel Mount Female Cam Locks with 4/0 DLO Cable from New Main Emergency Breaker to Cam Locks at each Building in specified locations.

· Furnish and install new breaker locking devices on existing 600A Main Breaker at each Building.

· All work to be performed during normal hours