This document is a Statement of Requirements for the United States Coast Guard (USCG) Base Astoria's purchase of a Hazardous Waste Locker. The locker must be Factory Mutual Approved, comply with multiple safety codes (IBC, IFC, EPA, NEC, OSHA), and meet specific technical specifications, including dimensions of 24.5' long, 10' deep, 8.5' high with three 56" wide x 82" high doors. Key requirements include a double-walled steel construction with a 2-hour fire rating, 1054-gallon internal spill containment, chemical-resistant epoxy coating, and additional safety features such as explosion-proof ventilation fans, lights, and a UL and FM approved ABC Dry Chemical Fire Suppression System.
The contractor will be responsible for delivering the hazardous waste locker to US Base Astoria at East Tongue Point in Astoria, Oregon, and offloading it from the delivery vehicle. The vendor must provide a product data sheet and obtain written USCG approval prior to shipping. The locker comes with a 15-year structural warranty and 1-year coating warranty. Total approximate weight is 19,800 lbs, and the unit is designed to be portable by forklift with front-to-rear loading capability. Additional specifications include seismic tie-down holes, ground connection, fibergrate flooring, and three steel loading ramps.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Wage Rates CLATSOP County.pdf | ||
| FP SUP A.pdf | ||
| FP SUP R.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF HOMELAND SECURITY
UNITED STATES COAST GUARD
Coast Guard Base Astoria
STATEMENT OF REQUIREMENTS FOR THE PURCHASE OF
A HAZARDOUS WASTE LOCKER
Requirements
1 JUSTIFICATION
USCG intends to procure a Hazardous Waste storage locker. This locker is essentially to safely temporarily store oily waste, used chemicals, flammables, and other hazardous materials generated by the operation of USCG ships.
2 STATEMENT OF REQUIREMENTS
Hazardous Waste Locker
Requirement
Number
Requirement Description
1 Factory Mutual Approved to meet FMRC Class 6049 (NFPA 30)
2 Complies with IBC, IFC, EPA, NEC, and OSHA codes
3 Has the following dimensions: 24.5’ long, 10’ deep, 8.5’ height, has 3 doors with each door 56” wide x 82” high, each door has a 3 point lock, total approximate weight is 19,800 lbs
4 All materials used to fabricate the locker shall be new, unused, non commercial grade ASTM A570 and commercial grade ASTM 569 and
ASTM A36 steel
5 Locker shall be double walled, 12 and 14 gauge welded stell construction with 2 hour fire rating
6 Sump shall be built of 10 gauge steel
7 Chemical resistant epoxy coating inside and outside with salt water primer
8 Fusible link fire dampeners
9 Internal spill containment of 1054 gallon minimum
10 Ground connection on all units
11 Spill containment drain on all units is a minimum of 4 inches above ground to allow drainage
12 Fibergrate flooring
13 Units are design to be portable by forklift, with front to rear loading capability, with forklift pockets
14 Seismic tie down holes are 1 inch diameter
15 All units must have 3/8 inch grounding lugs, set at 30 inches high
16 Two 2 hour fire rated separation wall with segregated sump dividing the building into 3 equal compartments
17 3 explosion proof forced air exhaust ventilation fan (Class I, Div I) 1,000 cfm
18 3 explosion proof LET lights (Class I, Div I) with switch
19 UL and FM approved ABC Dry Chemical Fire Suppression System with steel enclosure, manual pull station, and alarm
20 3 steel loading ramps
21 15 year warranty on structural
22 1 year warranty on coating
Vendor shall provide a product data sheet of the hazardous waste locker they intend to ship/deliver to the US Coast Guard. Prior to vendor shipping, the US Coast Guard must approve in writing the locker that the vendor intends to ship.
Contractor shall be responsible for the offloading of the hazardous waste locker from the delivery vehicle onto the ground at the delivery address. This may require the contractor to provide a heavy duty forklift/crane and operator at the delivery site.
1. DELIVERY LOCATION
US Base Astoria: East Tongue Point
37573 US-30
Astoria, OR 97103