STATEMENT OF NEED 55th OSS OSL VACUUM.docx

DOCX document 82 KB Posted

Attached to
AFE Central Vacuum
Solicitation number
FA460025Q0044
Issued by

About this file

The document is a Statement of Need for a central vacuum system for the 55th OSS/OSL AFE at Offut AFB, Nebraska. The system requires a comprehensive vacuum setup with specific technical specifications, including a 10 HP vacuum capable of handling talc dust, operating three 1" hoses simultaneously across four vacuum drops, with a 240 CFM minimum capacity and 11-gallon dust bucket storage. Key technical requirements include 460-3-60 power configuration, a 1-micron filter sleeve, noise levels under 90 decibels, and a remote start/stop station.

The vacuum system will be integrated into an AFE/SERE facility, with hard piping to four workstations in a storage room within an inspection area. The detailed specification includes precise copper tubing requirements (Type L, various diameters and lengths), four wall-mounted hose reels with 35-foot heavy-duty steel spring-return design, and specific hose kit configurations featuring static conductive and grounded components. The solicitation (FA460025Q0044) is issued by the Department of the Air Force Air Combat Command, targeting a central vacuum system with highly specialized industrial and technical specifications.

View the file

Other files

File Type Posted
Solicitation - FA460025Q0044 (1).pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF NEED

55th OSS/OSL AFE

1) This requirement is for a central vacuum system that will be integrated into the AFE/SERE facility being constructed on Offut AFB, NE. Vacuum will be located in a storage room within the inspection room with hard piping to 4 workstations.

2) The provided system shall be comprised of the following components: Vacuum, Electric Control Panel, Tube manifold system, and Hose Kits.

3) The system shall be able to handle slight amounts of talc dust and be able to operate (3) 1” hoses at any given time with a total of 4 vacuum drops.

4) The system shall meet the following requirements:

a) Power requirements

i) 460-3-60

b) Vacuum Requirements

i) Min 240 CFM

ii) Min 11 Gallons dust bucket storage capacity

iii) Filter sleave rated for min 1 micron

iv) Max 90 Decibles noise level at 3ft

v) Min 10 HP

c) Remote Start/Stop Stations

i) One remote start-stop station 120VAC with push button start/stop

d) Hose kits

i) 1-1/2” x 1” kit with 1-1/2” x 15’ static conductive hoses x 1” x 5’ hose to whip to connect to life raft

ii) Grounded

5) Tubing: Material Type L Copper

a) Pipe sizing- 2” and 1-1/2” per the construction drawings

b) Piping footage:

i) 20 feet 1 ½ inch diameter Wrot Copper 90 EII

ii) 5 feet 2 Wrot Copper 90 EII

iii) 1 2 inch diameter Wrot Copper Tee

iv) 1 1 ½ diameter Wrot Copper Coupling

v) 3 2 inch diameter Wrot Copper Coupling

vi) 6 1 ½ inch diameter Wrot Copper Union

vii) 6 1 ½ inch diameter Wrot Copper male Adapter

viii) 4 2 x 1 ½ inch Wrot Copper Reducing Tee

ix) 88 feet 1 ½ inch diameter Type L Hard Copper Tube

x) 98 feet 2 inch diameter Type L Hard Copper Tube

c) Hose reels approved per the plumbing schedule

i) (4) Wall mounted Hose reels

ii) 35 ft hose

iii) Spring return

iv) Heavy Duty Steel

v) (2) Hose reel mounted to wall- 6’0” AFF similar to dimensions below.

image1.png