This Standard Plans document provides technical specifications and installation details for the Town of Los Gatos' 2026 Annual Curb, Gutter, and Sidewalk Maintenance Project #25-813-9921. The document includes detailed construction standards for concrete work, tree planting, and sign installation. Concrete specifications require Class A concrete with one pound of lamp black per cubic yard, expansion joints with 1/2" x 12" slip at specified intervals, and dowels placed at 20-foot intervals, with an Aggregate Base Class II compacted to 95% maximum per ASTM D1557. Tree planting requirements specify 15-gallon trees with a minimum caliper of 1-1/2 inches and height of 7-8 feet, planted 4 inches higher than their nursery depth, with installation requiring 3 Agriform Planting Tablets (21 grams each, 20-10-5 analysis) placed equidistant in the planting pit. All planting stock requires approval from the Town Arborist. Electronic bids are due by Tuesday, March 17, 2026, at 2:00 pm via the Town's bidding portal at https://procurement.opengov.com/portal/losgatosca.

Sign installation standards specify regulatory and warning signs with a minimum 30" x 30" size using 3M Diamond Grade VIP reflective sheeting material. Sign posts must be 1.75" x 1.75" square, galvanized steel conforming to ASTM A653-94, Grade 55, with hot-dip zinc coating (G-90 designation), powder-coated black, and positioned with a minimum 7-foot height from grade to the near edge of sign and 2-foot lateral clearance from curb face. The specifications include detailed anchor requirements with 7/16" punched knockouts on 1-inch centers with tolerance of plus or minus 1/8" in 20 feet, either 6 or 12 sets of holes, and a penetrator point at the anchor bottom. All work must comply with the Manual on Uniform Traffic Control Devices (MUTC.D.) installation standards and Town Engineer specifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

18" 18"

1/4" 1 1/2" 6"

NOTES:

1. EXPANSION JOINTS WITH 1/2" x 12" SLIP.

2. DOWELS AT 20 FEET INTERVALS.

3. CONCRETE SHALL BE CLASS A.

4. ALL CONCRETE SHALL INCLUDE ONE (1)

POUND OF LAMP BLACK PER CUBIC YARD

OF CONCRETE.

AGGREGATE BASE CLASS II 95%

MAX. COMPACTION ASTM D1557

6"

NOT TO SCALE

6"

3"3"

NO 4 REBAR

PLAN VIEW

6"

V A

R

IE

S

1' M

IN

6' M

IN

5' M

IN

4' MIN.

1' 1/2" DIA BLACK RUBBER HOSE

(3) 2" DIAMETER PRESSURE TREATED

12 GA. WIRE, TWIST TO TIGHTEN

SHOVEL CUT ALL SIDES OF PIT

2" DEPTH MULCH AS SPECIFIED

RECOMPACTED NATIVE SOIL

PLANTING MIX

1'

PULL BURLAP OFF TOP 1/3

OF ROOT BALL

CENTER TREE IN PIT

3" WATER BASIN

POLES - TYP.

TYP.

BY PARKS SUPERINTENDENT.

TREE TYPE SHALL BE DETERMINED

NOTES

NOT TO SCALE

6" M

A X

B E

LO

W

M A

IN

F

O R

K O

R B

R A

N C

H

R O

O T

B A

R R

IE

R

PLANT TREES 4" HIGHER THAN DEPTH AT

WHICH GROWN IN NURSERY. AVOID

DAMAGE TO ROOTS. AVOID ROOTBALL

WHEN PLACING STAKES.

of large roots will encourage new roots initiating at the cuts.

TREE SPECIFICATIONS

All planting stock must must have the approval of the Town Arborist.

Any exception to the above must be approved by the Town Arborist.

Minimum spread of 2 - 3 feet.

CALIPER: 1-1/2 inches, measured 6 inches from the base.

HEIGHT: 7 - 8 feet high planted in the ground.

All 15 gal. trees must meet the following minimum specifications:

Use the remaining native soil to create a basin appropriate shovel handle as you fill. Be careful not to disturb the Fill around the rootball with backfill and pack the soil with the of the rootball. Do not pull the rootball apart. The severing compacted, carefully loosen the roots at the side and bottom with sharp shears or knife. If the rootball is dense or it from below. Sever any circling roots (3/16 inch or greater) Remove the rootball carefully from the container by supporting spacing. Tablets shall be 21 grams each with a guaranteed Place 3 Agriform Planting Tablets per tree at equidistant

Fill hole with the backfill mix to a level 1 inch below the curb.

Ag. mix shall be combined with existing soil, 1/3 mix, 2/3 and replaced with U.C. Ag. mix or approved equivalent. U.C.

The existing soil area is to be removed to a depth of 2 feet

Provide a 6 inch minimum clearance all around the rootball.

deep as the container in which the plant was delivered.

Dig the hole twice as large in diameter and 1-1/2 times as

PLANTING SEQUENCE

native soil.

to the site.

rootball itself.

test analysis of 20-10-5.

7.

6.

5.

4.

3.

BRANCHING NEED:

2.

1.

3.

1.

2.

CONCRETE

POUR

7/16" PUNCHED

KNOCKOUTS

TWO OPPOSITE

SIDES FROM 7'

ABOVE

SIDEWALK

TAMPER

PROOF DRIVE

RIVET (TYP)

7' -0

M

IN

(SEE STD. PLAN 448

SQ. TUBE SLEEVE

SQ. TUBE ANCHOR

FILLET WELD ALL AROUND

2 1/2" x 2 1/2" x 12 GA

2 1/4" x 2 1/4" x 12 GA

END CUT

PENETRATOR

FOR SIGN POST NOTES)

DRIVE RIVETS

2 TAMPER PROOF

6"

STEEL POST

1 3/4" SQ. GALVANIZED

6" MIN.

SIGN

D

SIGN

S E

LE

C

T P

U N

C H

E D

O N

B O

T H

S

ID

E S

SIGN INSTALLATION

DETAIL

E

SIGN

PER M.U.T.C.D.

INSTALLATION.

NOTES:

SHALL BE AS SHOWN ON THE PLANS AND

THE NEAR EDGE OF SIGN. SIGN LOCATION

CLEARANCE FROM THE FACE OF CURB TO

GRADE, OR TOP OF CURB, AND A 2' LATERAL

THE NEAR EDGE OF SIGN TO THE SIDEWALK

2 SIGNS SHALL HAVE A MIN. HEIGHT OF 7' FROM

CORE DRILLED BEFORE ATTEMPTING SIGN

1 SIDEWALKS AND PAVED AREAS SHALL BE

EQUIVALENT. POST SHALL BE POWDER-COATED BLACK.

(ASTM A70 GRADE 33) OR APPROVED

SELECT PUNCH TYPE GALVANIZED STEEL

4 ALL TUBING MATERIAL SHALL BE "ULTI-MATE"

a. REGULATORY AND WARNING SIGNS SHEETING

BY 3M TRAFFIC CONTROL MATERIALS DIVISION.

3 REFLECTIVE SHEETING SHALL BE MANUFACTURED

SHALL BE 3M DIAMOND GRADE VIP TYPE

MATERIAL OR EQUIVALENT. SIZE OF SIGNS SHALL BE NO

LESS THAN 30x30 UNLESS SPECIFIED BY THE TOWN

ENGINEER.

SIGN POST NOTES:

CONFORMING TO STANDARD SPECIFICATIONS FOR STEEL

5 TUBING SHALL BE ROLL FORMED FROM STEEL

SHEET, A.S.T.M. DESIGNATION A653-94, STRUCTURAL

QUALITY, GRADE 50 MODIFIED TO GRADE 55.

TREATMENT FOR ENHANCED CORROSION PROTECTION.

6 MATERIAL SHALL BE HOT-DIP GALVANIZED (ZINC COATED),

COATING DESIGNATION G-90, WITH ADDED CHEMICAL

AND WELDED SO AS THE WELD FLASH DOES NOT

TUBING, CAREFULLY FORMED FROM 14 GA. STEEL SHEET

7 THE CROSS SECTION OF THE POST SHALL BE SQUARE

INTERFERE WITH THE TELESCOPING PROPERTIES. SIZE OF

8 HOLE DIAMETER SHALL BE 7/16" (PLUS OR MINUS 1/64")

ON 1" CENTERS ON TWO OPPOSITE SIDES. HOLES SHALL BE

ON CENTERLINE OF EACH SIDE IN TRUE ALIGNMENT AND

OPPOSITE TO EACH OTHER. TOLERANCE ON THE HOLE

SPACING IS PLUS OR MINUS 1/8" IN 20'. FIRST SET OF HOLES

SHALL BE 1/2" FROM THE TOP OF THE ANCHOR. ANCHOR

SHALL HAVE EITHER 6 OR 12 SETS OF HOLES. THE BOTTOM

OF THE ANCHOR SHALL HAVE A PENETRATOR POINT.

POST SHALL BE 1.75" x 1.75".

9 CONCRETE SHALL BE POURED AROUND POST.