These are engineering design documents for HVAC upgrades at the Hubert Tech C Police building at Savannah State University, located in Savannah, Georgia. The project, identified by job number MRR-26-48-04, was released for construction on April 16, 2025, by Chatham Engineering Company, LLC. The documents detail comprehensive HVAC system modifications, including replacing air handling units, variable air volume boxes, ductwork, piping, and controls across multiple floor plans. The project involves Phase I and Phase II upgrades, with specific focus on electrical and mechanical system improvements for the police facility.
The design documents incorporate 2018 International Building Code with Georgia Amendments, 2018 International Mechanical Code with Georgia Amendments, 2015 International Energy Conservation Code with Georgia Amendments, and 2020 National Electrical Code. The technical specifications include detailed equipment schedules for air handling units, exhaust fans, dehumidifiers, hot water boilers, and pumps. Key components include a new air handling unit (AHU-1), condensing units (CU-1A,B), and multiple variable air volume (VAV) boxes with specific airflow and pressure requirements. The design emphasizes system efficiency, control sequences, and compliance with building and energy codes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00 Project Cover Page.pdf | ||
| DBB_Full Document MRR_26_48_04.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLICABLE CODES: SHEET INDEX:
SAVANNAH STATE UNIVERSITY
2020 NATIONAL ELECTRIC CODE
2015 INTERNATIONAL ENERGY CONSERVATION CODE WITH GEORGIA AMENDMENTS
2018 INTERNATIONAL MECHANCIAL CODE WITH GEORGIA AMENDMENTS
2018 INTERNATIONAL BUILDING CODE WITH GEORGIA AMENDMENTS
TITLE SHEET
SNS
SNS
T0.1
HVAC UPGRADES
HUBERT TECH C POLICE
M1.2 HVAC - FLOOR PLAN PHASE II
M1.1 HVAC - FLOOR PLAN PHASE I
M0.2 HVAC - PHASE II LEGEND, SCHEDULE, ABBREVIATIONS, AND DETAILS
M0.1 HVAC - PHASE I LEGEND, SCHEDULE, ABBREVIATIONS, AND DETAILS
E1.2 ELECTIRCAL - FLOOR PLAN PHASE II
E1.1 ELECTRICAL - FLOOR PLAN PHASE I
E0.1 LEGEND, NOTES, AND SPECIFICATIONS
T0.1 PROJECT TITLE SHEET
1 10/24/25 MRR-26-48-04 SNS
S A
V A
N N
A H
G
E O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\T0.1.dgn
CADD PLOT
24-OCT-2025
09:11 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
25010.00
R
L E
A S
D
F O
C
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
IT
Y
ELECTRICAL LEGEND
J
ETR
GENERAL NOTES & SPECIFICATIONS
DISCONNECT SWITCH
EQUIPMENT AS NOTED
EXISTING TO REMAIN
JUNCTION BOX
CONDUITS OVERHEAD
HOME RUN
G10. PROVIDE TYPED UPDATED PANEL DIRECTORY IN PANEL.
REQUIRING ELECTRICAL SERVICE.
G9. REFER TO MECHANICAL SYSTEM DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL EQUIPMENT
COVERS, UNLESS NOTED OTHERWISE. PLATES COLOR SHALL BE SELECTED BY ARCHITECT.
G8. BOXES FOR WALL MOUNTED OUTLETS SHALL BE 4-11/16" DEEP SQUARE TYPE WITH SINGLE GANG TILE
MOUNTING HEIGHTS SHALL BE COORDINATED WITH THE EQUIPMENT PROVIDED.
ARE SCHEMATIC. INTENDED ONLY TO CONVEY THE APPROXIMATE LOCATION. THE ACTUAL LOCATION AND
G7. THE LOCATION AND MOUNTING HEIGHTS OF DEVICES AND OUTLETS INDICATED ON THE ELECTRICAL PLANS
G6. PROVIDE GREEN EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS.
208/120V BLACK RED BLUE WHITE
PH A PH B PHC NEUTRAL
FOLLOWS:
G5. ALL CONDUCTORS TO BE STRANDED COPPER TYPE THWN. COLOR CODE AS
G4. LABEL ALL OUTLET AND JUNCTION BOXES SHOWING CIRCUIT NUMBER OR SYSTEM.
TO BE EMT WITH COMPRESSION FITTINGS; INSULATED THROAT CONNECTORS.
EARTH TO BE SCH 40 PVC. MC CABLE MAY BE USED FOR CONCEALED INSTALLATION. CONDUITS INSIDE
THREADED COUPLINGS, LOCKNUTS, BUSHINGS AND ELBOWS. ALL RACEWAY IN DIRECT CONTACT WITH THE
G3. ALL EXPOSED RACEWAY OUTSIDE OF THE BUILDING TO BE IN RGS OR IMC CONDUIT. PROVIDE STANDARD
G2. COORDINATE ALL WORK WITH EXISTING CONDITIONS AND OTHER TRADES.
SSU STANDARDS.
G1. ALL WORK TO COMPLY WITH 2023 NEC WITH GEORGIA AMENDMENTS, ALL STATE ORDINANCES, AND
P.M.
B.P.M.
E0.1
SPECIFICATIONS
LEGEND, NOTES &
BREAKER RATING
PHASE VOLTAGE
SIZE
CONDUIT
SIZE
CONDUCTOR
SIZE
CONDUCTOR
GROUND
HVAC EQUIPMENT SCHEDULE
EQUIPMENT
HVAC
CONNECTION
PANEL
2" AHU-1 MDP 200A 3-#3/0 1-#6
10/24/25 MRR-26-48-04 SNS
S A
V A
N N
O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\E0.1.dgn
CADD PLOT
24-OCT-2025
09:23 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
L E
A S
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
POLICE
OFFICE
309A
309B
309C
COMMUNICATIONS
309D
EVIDENCE
305B-1
VESTIBULE
305B
DEPT. CHIEF
305D
LIEUTENANT
305E
CHIEF
305C
CORRIDOR
STORAGE
WOMEN
MEN
MECHANICAL
305A
311A
HALL
MEN'S
LOCKER RM
WOMEN'S
LOCKER RM
JANITOR
311B
303B
303A
STORAGE
303C
CONFERENCE
303D
LOCKER
303E
BREAK ROOM
303F
CLASSROOM
306A
EVIDENCE
STORAGE
306B
301A
EVIDENCE
MEN'S
LOCKER RM
STORAGE
303C
CONFERENCE
303D
LOCKER
303E
EVIDENCE
STORAGE
306B
301A
S A
V A
N N
O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\E1.1.dgn
CADD PLOT
24-OCT-2025
09:22 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
L E
A S
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
IT
Y
AHU
AHU
EF
EF
EF
EF
EF
HWB
HWP
BPM
SCALE: 1 / 8 " = 1' - 0"
E1.1
E1.1 SCALE: 1 / 8 " = 1' - 0"
E1.1
PM
NOTES:
NOTES: (DEMOLITION)
E1.1 SCALE: 1 / 8 " = 1' - 0"
2 PART PLAN - ELECTRICAL
FLOOR PLAN - ELECTRICAL
DEMOLITION PLAN - ELECTRICAL
CU
200/3/3R
NOTE 1
(200/3)
PANEL GE
HWB
HWP
ETR NOTE 1
PANEL MDP
EXISTING
NOTE 2
PANEL DH
EXISTING
NOTE D1
NOTE D1
ETR
DRAWINGS.
TO REMAIN IS SHOWN SOLID. COORDINATE WITH MECHANICAL
D2. EQUIPMENT TO BE REMOVED IS SHOWN DASHED AND EQUIPMENT
EQUIPMENT TO BE DEMOLISHED WITH MECHANICAL DRAWINGS.
DEMOLISHED HVAC EQUIPMENT. COORDINATE EXACT ELECTRICAL
D1. REMOVE EXISTNG ELECTRICAL EQUIPMENT ASSOICATED WITH
FLOOR PLAN
ELECTRICAL -
MANUFACTURER.
LOCATION IN FIELD. MATCH EXISTING BREAKER TO EXISTING
VERIFY EXACT LOCATION OF LV TRANSFORMER AND BREAKER
PANEL DH TO LOW VOLTAGE TRANSFORMER FOR HVAC CONTROLS.
2. CONTRACTOR TO EXTEND 120V BRANCH CIRCUIT FROM EXISTING
SCHEDULE ON E0.1.
PANEL IN FIELD AND MATCH EXISTING. SEE HVAC EQUIPMENT
NEW 200A/3P BREAKER. VERIFY EXACT BREAKER LOCATION IN
PANEL MOUNTING BRACKETS IN PANEL TO FURNISH AND INSTALL A
PANEL MDP. SEE PANEL LOCATION ON DRAWING. REWORK EXISTING
1. CONTRACTOR TO EXTEND NEW BRANCH FROM EXISTING ELECTRICAL
1 10/24/25 MRR-26-48-04 SNS
TEST AND BALANCE:
AIR DISTRIBUTION:
GENERAL HVAC:
INSULATION FOR HVAC SYSTEMS:
AIR DEVICES:
F. Test and balance shall not be performed until system installation is complete.
E. Report shall be signed and dated by balance engineer.
solutions to.
D. Any deviations from design data shall be explained in the report - possible reasons for and
C. Final readings shall be set with -5% to +10% of design conditions.
B. All instruments required to balance the system shall be provided at the Contractor's expense.
of the systems.
A. Instruments used for balancing shall have been calibrated within 6 months prior to the balancing
The Contractor shall perform test and balance on the air and water distribution systems.
6" wg. Insulated flexible duct shall be Thermoflex or approved equal.
NFPA 255. Minimum working pressure for duct pressure class 4" and below shall be
The assembly shall have a maximum flame and smoke rating of 25/50 per ASTM E84 and jacket shall have a maximum vapor transmission rate of 0.1 grains/sq. ft./hr/inch Hg (perm).
C-value of .23 BTU/hr/sq. ft./degree F. at 75 degrees F. mean temperature. Vapor barrier helix, fiberglass insulation, and a vapor barrier jacket. Insulation shall have a maximum layer for minimum working pressure of 6" wg. bonded to a steel or aluminum spring wire comply with NFPA 90A and 90B. Insulated flexible duct shall consist of an inner film
1. Insulated flexible duct shall be Class 1 air duct in accordance with UL 181 and shall
C. Flexible Ductwork the SMACNA HVAC Duct Construction Manual for pressure classes specified hereinbefore.
1. Except where indicated otherwise duct construction shall conform to the recommendations of
B. Galvanized Steel Ductwork
Exhaust ductwork (general building) - 2 return ductwork (general building) - 2
Supply air ductwork (general building) + 2
System or Zone Pressure Class
150% of the scheduled fan S.P., whichever is greater:
4. Ductwork shall be classified and constructed in the following SMACNA pressure classes, or to the runners and runners welded to the duct.
of 1800 FPM or higher, the turning vanes shall be the double thickness type, with vanes welded locations shown on the drawings. In any supply, return or exhaust air ductwork with velocities
3. Turning vanes shall be installed in all 90 degree square and rectangular elbows and at other
2. Ductwork shall be square, rectangular, round, or flat oval, as indicated on the drawings.
coating shall be not less than 1.25 ounces (total for both sides) per square foot of sheet.
1. Ductwork shall be constructed of lock forming quality galvanized steel sheets.Galvanized
A. General
H1
ABBREVIATION DESCRIPTIONSYMBOL ABBREVIATION DESCRIPTION
MLD/MD
A/C
MANUAL DAMPER
ABOVE CEILING
AHU AIR HANDLING UNIT
AD DUCT ACCESS DOOR
T'STAT THERMOSTAT
BTUH BRITISH THERMAL UNITS PER HOUR
CFM CUBIC FEET PER MINUTE
CU CONDENSING UNIT
HWC HOT WATER COIL
DN DOWN
DWGS DRAWINGS
EF EXHAUST FAN
ELEC ELECTRIC
EXH EXHAUST
GPM GALLONS PER MINUTE
HVAC HEATING VENTILATING & AIR CONDITIONING
MAX MAXIMUM
MIN MINIMUM
SINGLE LINE DUCT
FLEXIBLE DUCT
DUCT TRANSITION
ROUND
TG TRANSFER GRILLE
TYP TYPICAL
AFF ABOVE FINISHED FLOOR
LEGEND & ABBREVIATIONS
DIRECTION OF FLOW
SYMBOL LOCATION FUNCTION
SURFACE
TYPE
TYPE
AIR DISTRIBUTION DEVICES
SYMBOL/TYPE,SEE
SPECIFICATIONS
FOR DESCRIPTION
X
NECK SIZE
AIR QUANTITY CFM
GENERAL NOTES:
INSIDE OUTSIDE
HEAT.HEAT. COOLING COOLING
DB F DB F DB F DB FWB F WB F
DESIGN CONDITIONS
ALL
AREA UNIT
24 70 75 63 79
CTE CONNECT TO EXISTING
ALL
- 4-WAY
- 3-WAY
- 2-WAY
- 1-WAY
OR
DIRECTION OF BLOW
A
B
CEILING
CEILING
CEILING EXHAUST
RETURN
SUPPLY
PERFORATED
REGISTER
REGISTER
PERFORATED
LOUVERED FACE
LAY-IN
LAY-IN
SURFACE MNT
TT
D CEILING SUPPLY LOUVERED FACE SURFACE MNT
C. Type 'D' supply register shall be Price Model 620D or approved equal.
C. Type 'C' return register shall be Price Model 630D or approved equal.
B. Type 'B' return air register shall be Price APDDR or approved equal.
A. Type 'A' supply air diffuser shall be Price APDN or approved equal.
HP HEAT PUMP
HOT WATER SUPPLY
HWS
HOT WATER RETURN HWR
AIR HANDLING UNITS
SYMBOL
TYPE
MINIMUM CFM
TOTAL CFM
MAX. FAN MOTOR HP
ENT. AIR WB, F
LVG. AIR DB, F
LVG. AIR WB, F
LOCATION
REMARKS
C O
O L I
N
I
L
AIR CFM
MINIMUM OUTSIDE
CHARACTERISTICS
ELECTRICAL
TEMP., F
MIN. SUCTION
VELOCITY, FPM
MAX. FACE
DROP, IN. H 0
MAX AIR PRESSURE
SEE ELEC DWGS
MECH ROOM
55.0
55.0
63.9
295,480
346,800
6,700
12,760
HORIZONTAL
PRESSURE, IN. H 0
EXTERNAL STATIC
AHU-1 CU-1A,B
3. NFPA Standard 101, Code for Safety of Life from Fire in Buildings and Structures.
2. NFPA Standard 90A, Installation of Air Conditioning and Ventilating Systems.
1. NFPA Standard 70, National Electric Code
B. The mechanical equipment and installation shall conform to the following standards:
3. The International Energy Conversation Code 2015Edition with Georgia Amendments.
2. The International Mechanical Code 2018 Edition with Georgia Amendments.
1. The International Building Code 2018 Edition with Georgia Amendments.
A. The mechanical equipment and installation shall conform to the following codes:
MECHANICAL ROOMS PRIOR TO FABRICATION OF DUCTWORK.
BE REQUIRED. CONTRACTOR SHALL ALSO VERIFY SPACE ABOVE CEILINGS AND IN
CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY AS MODIFICATIONS MAY
CONDITIONS AND THE CONDITIONS SHOWN ON THE DESIGN DOCUMENTS, THE
VERIFY CONDITIONS. IF ANY DEVIATIONS ARE DISCOVERED BETWEEN THE ACTUAL
AND EXISTING PLANS WHERE AVAILABLE. AS SUCH, THE CONTRACTOR SHALL FIELD
6. EXISTING CONDITIONS: THE DESIGN IS BASED ON BASIC FIELD INVESTIGATIONS
5. INSTALL TURNING VANES IN ALL 45 AND 90 DEGREE MITERED EBLOWS.
SQUARE DUCT WITH A TAKE-OFF COLLARE WITH SCOOP AND DAMPER.
4. FLEXIBLE OR ROUD DUCT SHALL BE CONNECTED TO RECTANGULAR OR
3. DUCT SIZES SHOWN ARE ACTUAL INSIDE DIMENSIONS.
HUMIDISTAT AND SENSORS TO MEET ADA REQUIREMENTS.
2. UNLESS OTHERWISE INDICATED, INSTALL AL SPACE THERMOSTATS,
1. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO INSTALLATION.
SYMBOL
TYPE
REMARKS
0.25
CLNG. CENT.
SEE ELEC DWGS
LOCATION
CHARACTERISTICS
ELECTRICAL
EVIDENCE STOR.
4.0
1,000
CFM
MAXIMUM SONES
PRESSURE, IN. H 0
EXTERNAL STATIC
DRIVE
DIRECT
MAXIMUM TIP SPEED, FPM
MAXIMUM FAN SPEED, RPM
VELOCITY, FPM
MAXIMUM OUTLET
EXHAUST FANS
EF-6
MAXIMUM MOTOR W
SYMBOL
TYPE
REMARKS
300.0
DX
SEE ELEC DWGS
LOCATION
CHARACTERISTICS
ELECTRICAL
80.0
80.0
61.0
73.0
28.0
EVIDENCE STORAG
DEHUMIDIFIER
DH-1
PROCESS FLOW, CFM
CAPACITY, PINTS/DAY
DEHUMIDIFICAITON
ENTERING AIR % RH
LEAVING AIR % RH
TO MAINTAIN 50% SPACE HUMIDITY.
SWITCH. HUMIDITY SENSOR SHALL ENERGIZE UNIT
SUPPLIED WITH HUMIDITY SENSOR AND DISCONNECT
APPROVED EQUAL. UNIT SHALL BE INDOOR MODEL
DEHUMIDIFIER SHALL BE APRILAIRE E080 OR
SENSOR.
SENSOR. FAN SHALL BE CONTROLLED BY VOC
DAMPER, DISCONNECT SWITCH, WALL CAP, AND VOC
EQUAL. PROVIDE FAN WITH GRAVITY BACKDRAFT
FAN SHALL BE GREENHECK SP OR APPROVED
- HVAC
ABBREVIATIONS PHASE I
LEGEND, SCHEDULE,
M0.1
SNS
SNS
BTU/HR
TOT. CAPACITY,
BTU/HR
SENS. CAPACITY,
76.5 ENT. AIR DB, F
SYMBOL
TYPE
LOCATION
REMARKS
289,240
EXISTING
29.2
SEE ELEC DWGS
ELECTRICAL
BTU/HR
OUTPUT CAPACITY,
BTU/HR
MAX. INPUT CAPACITY,
HOT WATER BOILERS
160.0
180.0
W A
T
T
FLOW, GPM
ENT. TEMP., F
LVG. TEMP., F
HWB-1 SYMBOL
TYPE
REMARKS
29.2
EXISTING
SEE ELEC DWGS
LOCATION
ELECTRICAL
HEAD, FT. H 02
PUMPS
FLOW, GPM
RPM
MIN. EFFICIENCY, %
MAXIMUM MOTOR HP
HWP-1
HWB HOT WATER BOILER
HWP HOT WATER PUMP
VAV VARIABLE AIR VOLUME
PIPING:
WROUGHT COPPER, ANSI 16.22, WITH WORKING PRESSURE OF NO LESS THAN 300 PSIG.
B. REFRIGERANT PIPING SHALL BE HARD DRAWN TYPE ACR SEAMLESS COPPER TUBING, ASTM B280. FITTINGS SHALL B
BE MADE WITH FITTINGS.
PIPES SHALL HAVE BURRS REMOVED BY REAMING AND CHANGES IN DIRECTION OF PIPING SHALL
ASTM B88. FITTINGS SHALL BE WROUGHT COPPER WITH SOLDER JOINTS MEETING ANSI B16.22.
A. PIPE AND FITTINGS FOR HYDRONIC SYSTEMS SHALL BE TYPE 'L' HARD-DRAWN COPPER MEETING
HVAC PIPING SPECIALTIES:
WITH GAUGE COCK. GAUGE AND GAUGE COCK SHALL BE BY WEISS OR APPROVED EQUAL.
THE APPLICATION FALLS IN THE APPROXIMATE MIDPOINT OF THE GAUGE RANGE. GAUGES SHALL BE PROVIDED
CONNECTIONS. RANGE FOR PRESSURE GAUGES SHALL BE SELECTED SO THAT THE NORMAL OPERATING POINT FOR
0.5% ACCURACY OF SCALE RANGE, PLEXIGLAS DIAL COVER, SAFETY BLOWOUT DISC AND 0.25 INCH LOWER
STEEL ROTARY GEAR MOVEMENTS, PHOSPHORUS BRONZE BOURDON TUBES, FORGED BRASS ROD SOCKETS AND TIPS.
C. HOT WATER PRESSURE GAUGE SHALL BE FLANGELESS TYPE WITH 4.5" DIAL, CAST ALUMINUM CASES, STAINLES
SHALL BE NIBCO OR APPROVED EQUAL.
AND CAP SHALL BE ASTM B62 CAST BRONZE WITH THREADED ENDS, INSIDE SCREW CAP, AND BRONZE DISC. VALVE
B. HOT WATER CHECK VALVE SHALL BE CLASS 125 HORIZONTAL SWING TYPE CONFORMING TO MSS SP-80. BODY
OR APPROVED EQUAL.
TEFLON SEAL, BRASS PACKING GLAND, STEEL LEVER HANDLE WITH VINYL HANDLE COVER. VALVE SHALL BE NIBCO
BODY SHALL BE ASTM B62 BRONZE WITH THREADED ENDS, FULL PORT, CHROME PLATED BRASS BALL, REPLACEABLE
A. HOT WATER SHUTOFF VALVES SHALL BE 3-PIECE BALL VALVE SIZED FOR 400 PSIG WOG, QUARTER TURN TYPE.
COILS, AND LOW SOUND PACKAGE.
LEAK ECONOMIZER, E-COATED
DISCONNECT SWITCH, ULTRA LOW
RELIEF, HAIL GAURDS, NON-FUSED
WITH VAV CONTROLS, BAROMETRIC
MODEL 50V5AX30. PROVIDE UNIT
PROVIDE AND INSTALL CARRIER
LOCAITON.
ONLY, FIELD VERIFY EQUIPMENT SIZE AND
INFORMATION PROVIDED FOR TEST AND BALANCE 1
LOCAITON.
ONLY, FIELD VERIFY EQUIPMENT SIZE AND
INFORMATION PROVIDED FOR TEST AND BALANCE
COVER EXTERIOR WITH ALUMINUM JACKETING MATERIAL 0.016 INCH THICK WITH SMOOTH FINISH.
APPLICATION. FLASH MASTIC AND REINFORCEMENT TO ALL METAL SUPPORTS AND TERMINATION POINTS.
RATE OF 4 GAL/100 SF WET FILM. MINIMUM DRY FILM THICKNESS OF 30 MILS FOR TWO COAT MASTIC
2" MINIMUM. APPLY FINISH COAT TO ENTIRE MEMBRANE OF WEATHERPROOFING MASTIC AT MINIMUM
GLASS MEMBRANE INTO WET TACK COAT. SMOOTH MEMBRANE TO AVOID WRINKLES. OVERLAP SEAMS
WATERPROOF MASTIC OVER ENTIRE INSULATION SURFACE AT RATE OF 2 GAL/100 SF WET FILM. EMBED
MINIMUM INSULATION VALUE OF R-8. EXTERIOR OF INSULATION SHALL HAVE A TACK COAT OF GREY
C. DUCT INSTALLED ON EXTERIOR OF BUILDING SHALL BE INSULATED WITH RIGID, FIBROUS GLASS BOARD
SECTION SIZED TO PROVIDED THE SAME INSULATION THICKNESS AS ON THE ADJOINING PIPE SECTIONS.
WITH INSULATION. INSULATE FLANGES, COUPLINGS, AND VALVES WITH OVERSIZED PIPE INSULATION
INSULATION TOGETHER AND SECURE JACKET LAPS. SEAL BUTT JOINTS WITH JOINTS STRIPS FURNISHED
INSTALLED OUTSIDE THE BUILDING SHALL BE INCREASED A MINIMUM OF 1/2". BUTT ALL JOINTS OF PIPE
PIPES 1-1/2" AND LARGER SHALL BE 2" THICK. THICKNESS OF INSULATION OF INSULATION ON PIPES
AND BUTT STRIPS. INSULATION ON PIPES 1-1/4" AND SMALL SHALL BE 1-1/2" THICK AND INSULATION ON
GLASS FIBER YARN AND BONDED TO ALUMINUM FOIL SECURED WITH SELF-SEALING LONGITUDINAL LAPS
TEMPERATURE WITH VAPOR RETARDER JACKET MADE OF WHITE KRAFT PAPER REINFORCED WITH
B. PIPE INSULATION FOR HYDRONIC SYSTEMS SHALL BE ONE PIECE FIBERGLASS PIPE INSULATION WITH shall be Knauf Ductwrap or approved equal. Insulation thickness shall be 2".
conductivity of 0.26 BTU/in. per sq.ft. per degree F per hour at 75°F mean temperature. Insulation kraft vapor barrier jacket. Insulation shall have a minimum density of 1.0 lb/cu. ft. and a maximum glass blanket type designed for use on surfaces up to 250 F with a factory applied aluminum foil and
A. FIBERGLASS BLANKET INSULATION on supply, return AND OUTSIDE AIR ducts shall be fibrous
1 10/24/25 MRR-26-48-04 SNS
S A
V A
N N
O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\M0.1.dgn
CADD PLOT
24-OCT-2025
09:14 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
L E
A S
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
M0.2
SNS
SNS
SYMBOL
TYPE
LOCATION
REMARKS
800 835
1,670
PRESS. INDEP.
1,600
PRESS. INDEP.
1.0
RM 309
1.0
RM. 305
VAV-2 VAV-1
1,200
PRESS. INDEP.
1.0
COMM 309D
VAV-3
MAXIMUM CFM
MINIMUM CFM
DROP, IN. H 0
MAXIMUM BOX PRESSURE
VARIABLE AIR VOLUME BOXES
HEATING CFM
MAXIMUM N.C. LEVEL
CAPACITY, BTU/HR
ENT. AIR DB, F
LVG. AIR DB, F
H E
A T I
N G
34,560
55.0
95.0
36,070
55.0
95.0
25,920
55.0
95.0
TEMP., F
ENTERING WATER
TEMP., F
LEAVING WATER
HOT WATER, GPM 3.5
180.0
160.0
3.6
180.0
160.0
2.6
180.0
160.0
1,600
PRESS. INDEP.
1.0
RM 311
VAV-4
34,560
55.0
95.0
3.5
180.0
160.0
1,845
PRESS. INDEP.
1.0
RM 303
VAV-5
39,745
55.0
95.0
4.0
180.0
160.0
3,900
PRESS. INDEP.
1.0
RM 302
VAV-6
38,880
55.0
95.0
4.0
180.0
160.0
PRESS. INDEP.
1.0
RM 306
VAV-7
8,640
55.0
95.0
0.9
180.0
160.0
PRESS. INDEP.
1.0
RM 301
VAV-8
20,750
55.0
95.0
2.1
180.0
160.0
1,690
PRESS. INDEP.
1.0
RM 301
VAV-9
36,505
55.0
95.0
3.6
180.0
160.0
PRESS. INDEP.
1.0
CONF 303
VAV-10
13,610
55.0
95.0
1.4
180.0
160.0
4 5
5. STRAINER
7. METERED BALANCING VALVE
9. UNION
10. 3/4" HOSE END DRAIN VALVE
11. MANUAL AIR VENT
8. BALANCING VALVE
1. VARIABLE AIR VOLUME BOX
4. SHUT-OFF VALVE
2. CHILLED WATER (OR HOT WATER) SUPPLY
3. CHILLED WATER (OR HOT WATER) RETURN
6. 3-WAY CONTROL VALVE
DETAILS - HVAC
VAV SCHEDULE AND
3D
DUCTWORK
REDUCER IF REQUIRED
CONNECT TO EXISTING
24"
VAV BOX
FOR FITTING TYPE
SEE SPECIFICATIONS
DISTANCE (2 FT. MAX.)
MFR'S RECOMMENDED
IF SCHEDULED
HOT WATER HEATING COIL
ANY OTHER OBSTRUCTION
WALL, PIPE OR
M0.2
SCALE: NOT TO SCALE
VAV BOX AND DUCTWORK DETAIL
M0.2
SCALE: NOT TO SCALE
VARIABLE AIR VOLUME BOX (3-WAY VALVE)
1 VAV BOX SHALL BE TITUS DESV WITH HOT WATER REHEAT COIL OR APPROVE EQUAL
SEQUENCE OF OPERATION:
C. CLOSE TEH OUTSIDE AIR DAMPER.
B. DE-ENERGIZE THE FAN.
A. SEND A SIGNAL TO THE FIRE ALARM SYSTEM
AIR SMOKE DETECTOR SHALL:
4. UNDER ALARM CONDITION, A SIGNAL FROM THE FIRE ALARM SYSTEM OR ACTIVATION OF THE SUPPLY
AIR DAMPER SHALL CLOSE. MANUAL RESET AT THE UNIT SHALL BE REQUIRED TO RESTART THE FAN MOTOR.
ON A FURTHER RISE IN STATIC PRESSURE TO 3 INCHES THE AHU SHALL SHUT DOWN AND THE OUTSIDE
G. ON A RISE IN STATIC PRESSURE AT THE FAN DISCHARGE TO 2 INCHES, AN ALARM SHALL BE INITIATED.
SECTION IN ORDER TO PROIVDE THE SCHEDULED OUTSIDE AIRFLOW RATE AS THE SUPPLY AIRFLOW VAIRES.
F. A MOTOR OPERATED DAMPER SHALL MODULATE IN RESPONSE TO AN AIRFLOW STATION IN THE OUTSIDE AIR
MODULATE TO MAINTAIN SET CONDITION.
THE AIRFLOW QUANTITY FROM DROPPING BELOW THIS MINIMUM FLOW RATE. THE COMPREESOR SHALL
E. WHEN THE AIRFLOW IS MODULATED DOWN TO THE MANUFACTURER'S MINIMUM RECOMMEDED SEETING, DOWNSTREAM OF THE AHU, THE FAN SPEED SHALL MODULATE TO MAINTAIN SET STATIC PRESSURE
D. ON A CHANGE IS SUPPLY AIR STATIC PRESSURE, AS MEASURED BY A SENSOR LOCATED 95% OF THE DISTANCE
C. COMPRESSOR SHALL MODULATE AS REQUIRED TO MAINTAIN LEAVING AIR TEMPERATURE
B. OUTSIDE AIR DAMPER SHALL BE CLOSED.
A. SUPPLY FAN SHALL BE ENERGIZED ONLY DURING A CALL FOR COOLING.
3. DURING UNOCCUPIED HOURS:
DAMPER SHALL MODULATE OPEN 100%, RETURN DAMPER SHALL CLOSE 100%, AND THE RELIEF FAN
CALLING FOR HEATING, AND OUTSIDE AIR TEMPERATURE BELOW COOLING SET CONDITION THE OUTSIDE
1. WITH RETURN AIR DRY BULB TEMPERATURE HIGHER THAN OUTSIDE AIR TEMPERTURE AND NO ZONE
H UNDER ECONOMIZER OPERATION:
AIR DAMPER SHALL CLOSE. MANUAL RESET AT THE UNIT SHALL BE REQUIRED TO RESTART THE FAN MOTOR.
ON A FURTHER RISE IN STATIC PRESSURE TO 3 INCHES THE AHU SHALL SHUT DOWN AND THE OUTSIDE
G. ON A RISE IN STATIC PRESSURE AT THE FAN DISCHARGE TO 2 INCHES, AN ALARM SHALL BE INITIATED.
SECTION IN ORDER TO PROIVDE THE SCHEDULED OUTSIDE AIRFLOW RATE AS THE SUPPLY AIRFLOW VAIRES.
F. A MOTOR OPERATED DAMPER SHALL MODULATE IN RESPONSE TO AN AIRFLOW STATION IN THE OUTSIDE AIR
MODULATE TO MAINTAIN SET CONDITION.
THE AIRFLOW QUANTITY FROM DROPPING BELOW THIS MINIMUM FLOW RATE. THE COMPREESOR SHALL
E. WHEN THE AIRFLOW IS MODULATED DOWN TO THE MANUFACTURER'S MINIMUM RECOMMEDED SEETING, DOWNSTREAM OF THE AHU, THE FAN SPEED SHALL MODULATE TO MAINTAIN SET STATIC PRESSURE
D. ON A CHANGE IS SUPPLY AIR STATIC PRESSURE, AS MEASURED BY A SENSOR LOCATED 95% OF THE DISTANCE
C. COMPRESSOR SHALL MODULATE AS REQUIRED TO MAINTAIN LEAVING AIR TEMPERATURE
B. OUTSIDE AIR DAMPER SHALL OPEN.
A. SUPPLY FAN SHALL BE ENERGIZED.
2. DURING OCCUPIED HOURS:
1. UNIT SHALL BE CONTROLLED THOUGH BUILDING AUTOMATION SYSTEM
VARIABLE VOLUME AIR HANDLING UNIT (AHU-1)
4. UNDER ALARM CONDITION, A SIGNAL FROM THE FIRE ALARM SYSTEM SHALL CLOSE THE COOLING VALVE/DAMPER.
AND HEATING COIL VALVE SHALL MODULATE TO MAINTAIN SET CONDITION.
WITH VALVE/DAMPER ENABLED:
3. UNDER NORMAL OPERATION A SIGNAL FROM THE THERMOSTAT SHALL ENABLE THE VALVE/DAMPER.
2. UNIT SHALL BE CONTROLLED THROUGH THERMOSTAT IN SPACE.
1. UNIT SHALL BE ENERGIZED CONTINOUSLY
VARIABLE VOLUME BOXES
1 1 1 1 1 1 1 1 1
1 10/24/25 MRR-26-48-04 SNS
S A
V A
N N
O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\M0.2.dgn
CADD PLOT
24-OCT-2025
09:13 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
L E
A S
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
MEN'S
LOCKER RM
STORAGE
303C
CONFERENCE
303D
LOCKER
303E
EVIDENCE
STORAGE
MEN'S
LOCKER RM
STORAGE
303C
CONFERENCE
303D
LOCKER
303E
EVIDENCE
STORAGE
306B
EVIDENCE
STORAGE
306B
S A
V A
N N
O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\M1.1.dgn
CADD PLOT
24-OCT-2025
09:13 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
L E
A S
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
IT
Y
10"/
7"/
7"/
10"/
6"/
6"/
6"/
6"/
X
8X6
X
7"/
7"/
7"/
8"/
8"/
10"/
6"/
18X14
10X10
14X12
12X12
AHU
8"/
8"/
8"/
8"/ 8"/
8"/
8"/
8"/
8"/
X
X
X
X
X
X
8"/
8"/
8"/
8"/
8"/
8"/
8"/
8"/
8"/2
X
X
8"/ 8"/
8"/
8"/
X
8"/ 8"/
8"/
8"/
8"/ 8"/
8"/
8"/
X
X
SKD
6"/
EF
EF
EF
6X6
8X8
6"/
EF
EF
HWB
HWP
HWB
HWP
AHU
HP
10"/
7"/
7"/
10"/
6"/
6"/
6"/
6"/
X
4"/
8X6
7"/
7"/
8"/
8"/
10"/
6"/
18X14
10X10
14X12
12X12
AHU
CU
8"/
8"/
8"/
8"/ 8"/
8"/
8"/
8"/
8"/
X
X
X
X
X
X
8"/
8"/
8"/
8"/
8"/
8"/
8"/
8"/
8"/2
X
X
8"/ 8"/
8"/
8"/
14X12
X
8"/ 8"/
8"/
8"/
8"/ 8"/
8"/
8"/
X
X
HWC
HWC
HWC
HWC
HWC
HWC
HWC
SKD
M1.1
SNS
SNS
M1.1
SCALE: 1 / 8 " = 1' - 0"
EF
EF
EF
6X6
8X8
6"/
DUCTWORK
HVAC - FLOOR PLAN
M1.1
SCALE: 1 / 8 " = 1' - 0"
NOTES: 1/M1.1
EXISTING TO REMAIN
EXISTING TO BE REMOVED
1 CUT, CAP, AND INSULATE DUCTWORK.
2 CUT AND CAP HOT WATER PIPE.
OFF SITE.
VALVES, AND CONTROLS SHALL BE REMOVED AND DISPOSED OF
EXISTING HOT WATER COIL AND ALL ASSOCIATED PIPING,
REMOVED AND DISPOSED OF OFF SITE.
EXISTING DUCTWORK, INSUALTATION AND AIR DEVICE SHALL BE
NOTES: 2/M1.1
NEW WORK
EXISTING TO REMAIN
CONNECT TO EXISTING.
ETR
EF
EF
EF
DH
B
RG
22X22
B
RG
22X22
B
RG
22X22
B
RG
22X22
REQUIREMENTS.
INSTALL FAN IN BETWEEN BAR JOISTS PER MANUFACTURER'S
ACTIVATED. REFER TO 1/M0.1 FOR DETAIL.
INSTALLED. FLOAT SWITCH SHALL DE-ENERGIZE UNIT WHEN
HAVE VALVED AND CAPPED DRAIN LINE AND FLOAT SWITCH
UNIT IN AUXILARY DRAIN PAN. AUXILLARY DRAIN PAN SHALL
ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS. INSTALL
DOWN OVER SPLASH BLOCK. SIZE AND INSTALL P-TRAP IN
INSTALL P-TRAP IN LINE AND ROUTE TO EXTERIOR AND TURN
CONDENSATE DRAIN FULL SIZE OF CONNECTION AT UNIT.
INSTALL UNIT ABOVE CEILING BETWEEN JOIST. INSTALL
OFF SITE.
EXISTING AIR DEVICE SHALL BE REMOVED AND DISPOSED OF
TERMINATE FAN WITH WALL CAP PROVIDED WITH FAN.
OFF SITE.
EXISTING THERMOSTAT SHALL BE REMOVED AND DISPOSED OF
LINE SET SHALL BE COVERED. REFER TO 2/M0.1 FOR DETAIL.
MANUFACTURER'S RECOMMENDATIONS. EXTERIOR REFRIGERANT
ASSOCAITED INDOOR UNIT. SIZE AND INSTALL PER
24" ABOVE GRADE. ROUTE REFRIGERANT LINE SET TO
INSTALL OUTDOOR UNIT ON STAND. STAND SHALL BE A MINIMUM
HWB
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
HWP
8"/
X
X
B
RG
22X22
6X6
12X12 *"/
B
12X12
6X6
B
RG
22X22
B
18X18
6X6
12X12
425 *"/
155 *"/
8"/ A
8"/ A
8"/ A
OF OFF SITE.
EXISTING DX COIL IN AHU SHALL BE REMOVED AND DISPOSED
OF OFF SITE.
LINE SETS AND INSULATION SHALL BE REMOVED AND DISPOSED
EXISTING CONDENSING UNIT AND ALL ASSOCIATED REFRIGERANT
B
RG
22X22
TRANSITION TO EXISTING DUCT AS REQUIRED.
FROM BOX AND CONNECT TO EXISTING DUCT AS SHOWN.
DUCT. FIELD VERIFY LOCATION AND SIZE. EXTEND DISCHARGE
DETAIL. CONNECT INLET TO EXISTING MAIN DUCT ON TOP OF
INSTALL VAV BOX ABOVE CEILING. REFER TO 1/M0.2 FOR
B
RG
22X22
RG
22X22
RG
22X22
6"/
10X10
6"/ 6"/ A
6"/
6"/ A
10"/ A
10"/ A
10"/ A
10"/ A
9 CAP EXISTING TRANSFER OPENING.
12"/ A
B
RG
22X22
14X14
12"/
12"/
RG
22X22
RG
22X22
REQUIRED.
FIELD VERIFY OPERATION OF EXISTING FAN. REPAIR FAN AS
2 2
AHU
S K
D
M1.1
SCALE: 1 / 8 " = 1' - 0"
PART PLAN - HVAC
DUCTWORK PLAN - HVAC
DUCTWORK DEMOLITION PLAN - HVAC
NOTES: 3/M1.1
NEW WORK
EXISTING TO REMAIN
1 REFER TO 2/M1.1 FOR CONTINUED.
MANUFACTURER'S REQUIRMENTS AND TURN OUT OVER GROUND.
SIZE OF CONNECTION AT UNIT. INSTALL P-TRAP IN LINE PER
INSTALL UNIT ON GROUND. INSTALL CONDENSATE DRAIN LINE FULL
DUCTWORK.COORDINATE DUCT ROUTING WITH EQUIPMENT IN AREA.
JACKETED PER SPECIFICATIONS FOR EXTERIOR
REQUIRED. EXTERIOR DUCTWORK SHALL BE INSULATED AND
CONNECT DUCTS TO UNIT AS SHOWN. TRANSITION DUCTWORK AS
32X32
36X36
X
X
X
50X18
50X18
X
8 REFER TO 3/M1.1 FOR CONT.
S K
D
B
RG
22X22
B
RG
22X22
B
RG
22X22
B
RG
22X22
HARDWARE. FIELD VERIFY DOOR SIZE PRIOR TO ODERING DOOR.
FULL SIZE OF DOOR OPENING. PROVIDE ALL REQUIRED MOUNTING
REMOVE EXISTING DOOR AND INSTALL ULINE MACHINE GUARD DOOR
DUCT PENETRATIONS. SEAL ALL DUCT PENETRATIONS.
SEAL DOOR OPENINGS TO MAKE WEATHER TIGHT. CUT DOOR FOR
SPOT WELD EXISTING DOOR TO MAKE INOPERABLE. CAULK AND
1 6/16/25DUCT PENETRATION NOTE SNS
2 10/24/25 MRR-26-48-04 SNS
MEN'S
LOCKER RM
STORAGE
303C
CONFERENCE
303D
LOCKER
303E
EVIDENCE
STORAGE
MEN'S
LOCKER RM
STORAGE
303C
CONFERENCE
303D
LOCKER
303E
EVIDENCE
STORAGE
306B
301A
S A
V A
N N
O
R G
IA
Sheet No.Date
Checked
Drawn
Job No.
Sheet Title
Revisions
No. Date Description By
E:\SSU Hubert Tech C Police HVAC Upgrades - 25010.00\CADD\M1.2.dgn
CADD PLOT
24-OCT-2025
09:12 sswanger
1 INCH
c1 P a rk o f
C o m m e rc e D ri v e S u it e
S a v a n n a h
G e o rg ia
T h is d ra w in g a n d a ll p ri n ts o f it a re t h e p ro p e rt y o f fo r w h ic h t h e y w e re i s s u e d
R e p ro d u c ti o n s o f th is d ra w in g w it h o u t th e
P H
O N
E -2
F
A X -2
C h a th a m E n g in e e ri n g C o m p a n y L L C
P ri n ts a re t o b e r e tu rn e d t o C h a th a m E n g in e e ri n g C o m p a n y L L C u p o n c o m p le ti o n o f u s e w ri tt e n c o n s e n t o f
C h a th a m E n g in e e ri n g C o m p a n y L L C i s n o t p e rm it te d
Stamp
1 INCH
L E
A S
N S T R
U C
T
IO
N
APRIL 16, 2025
S S
U M
R R -2
-4
-0
H U
B E
R T T
E C
H C P
O L
IC
E H
V A
C U
P G
R A
D E S
S A
V A
N N
A H S
T A T E U
N
IV
E R
S
IT
Y
AHU
EF
EF
EF
EF
EF
HWB
HWP
2" HWS/HWR
1•" HWS/HWR 1" HWS/HWR
EF
HWS/HWR
1•"
1" HWS/HWR
1‚" HWS/HWR
1‚" HWS/HWR 1" HWS/HWR
1" HWS/HWR
HWB
EF
DH
H
V
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
VAV
S K
D
SNS
SNS
NOTES: 1/M1.1
EXISTING TO REMAIN
EXISTING TO BE REMOVED
1 CUT, CAP, AND INSULATE DUCTWORK.
2 CUT AND CAP HOT WATER PIPE.
OFF SITE.
VALVES, AND CONTROLS SHALL BE REMOVED AND DISPOSED OF
EXISTING HOT WATER COIL AND ALL ASSOCIATED PIPING,
REMOVED AND DISPOSED OF OFF SITE.
EXISTING DUCTWORK, INSUALTATION AND AIR DEVICE SHALL BE
NOTES: 2/M1.1
NEW WORK
EXISTING TO REMAIN
CONNECT TO EXISTING.
CAP AND SEAL RETURN PENETRATION IN WALL.
SWITCH SHALL DE-ENERGIZE UNIT WHEN ACTIVATED.
BLOCK. INSTALL CONDENSATE FLOAT SWITCH IN LINE. FLOAT
AT UNIT. ROUTE TO EXTERIOR AND TURN DOWN OVER SPLASH
INSTALL CONDENSATE DRAIN LINE FULL SIZE OF CONNECTION
INSTALL UNIT ON WALL PER MANUFACTURER'S REQUIREMENTS.
REQUIREMENTS.
INSTALL FAN IN BETWEEN BAR JOISTS PER MANUFACTURER'S
ACTIVATED. REFER TO 1/M0.1 FOR DETAIL.
INSTALLED. FLOAT SWITCH SHALL DE-ENERGIZE UNIT WHEN
HAVE VALVED AND CAPPED DRAIN LINE AND FLOAT SWITCH
UNIT IN AUXILARY DRAIN PAN. AUXILLARY DRAIN PAN SHALL
ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS. INSTALL
DOWN OVER SPLASH BLOCK. SIZE AND INSTALL P-TRAP IN
INSTALL P-TRAP IN LINE AND ROUTE TO EXTERIOR AND TURN
CONDENSATE DRAIN FULL SIZE OF CONNECTION AT UNIT.
INSTALL UNIT ABOVE CEILING BETWEEN JOIST. INSTALL
OUTSIDE AIR INTAKE.
GRAVITY BACKDRAFT DAMPER IN FEILD TO ALLOW USE FOR
AND INSTALL CROWN MODEL 349 WITH SCREEN AND REMOVE
WALL CAP SHALL BE USED FOR OUTSDIE AIR INTAKE. PROVIDE
OFF SITE.
EXISTING AIR DEVICE SHALL BE REMOVED AND DISPOSED OF
8 TERMINATE FAN WITH WALL CAP PROVIDED WITH FAN.
OFF SITE.
EXISTING THERMOSTAT SHALL BE REMOVED AND DISPOSED OF
LINE SET SHALL BE COVERED. REFER TO 2/M0.1 FOR DETAIL.
MANUFACTURER'S RECOMMENDATIONS. EXTERIOR REFRIGERANT
ASSOCAITED INDOOR UNIT. SIZE AND INSTALL PER
24" ABOVE GRADE. ROUTE REFRIGERANT LINE SET TO
INSTALL OUTDOOR UNIT ON STAN. STAND SHALL BE A MINIMUM
M1.2
PIPING AND CONTROLS
HVAC - FLOOR PLAN
2" HWS/HWR
1•" HWS/HWR 1" HWS/HWR
EF
HWS/HWR
1•"
1" HWS/HWR
1‚" HWS/HWR
1‚" HWS/HWR 1" HWS/HWR
1" HWS/HWR
HWC
HWC
HWC
HWC
HWC
HWC 1
HWC
HWB
M1.2
SCALE: 1 / 8 " = 1' - 0"
PIPING AND CONTROLS DEMOLITION PLAN - HVAC
M1.2
SCALE: 1 / 8 " = 1' - 0"
PIPING AND CONTROLS PLAN - HVAC
ƒ" HWS/HWR ƒ" HWS/HWR
1" HWS/HWR
1 10/24/25 MRR-26-48-04 SNS
| T0.1 |
| T0.1 |
| BDR, CHATHAM 24X36.dgn |
| E0.1 |
| E0.1 |
| BDR, CHATHAM 24X36.dgn |
| E1.1 |
| E1.1 |
| SCRBGND NEW, Floor Plan redo.dgn |
| bdr, CHATHAM 24X36.dgn |
| new hvac, M1.1.dgn |
| SCRBGND ETR, Floor Plan redo.dgn |
| demo hvac, M1.1.dgn |
| SCRBGND PAC-1 (AHU-1), Floor Plan redo.dgn |
| M0.1 |
| M0.1 |
| bdr, CHATHAM 24X36.dgn |
| M0.2 |
| M0.2 |
| bdr, CHATHAM 24X36.dgn |
| M1.1 |
| M1.1 |
| SCRBGND-1, Floor Plan redo.dgn |
| bdr, CHATHAM 24X36.dgn |
| ETR, M1.1.dgn |
| SCRBGND-2, Floor Plan redo.dgn |
| SCRBGND, Floor Plan redo.dgn |
| ETR-1, M1.1.dgn |
| M1.2 |
| M1.2 |
| M1.1.dgn |
| SCRBGND-1, Floor Plan redo.dgn |
| bdr, CHATHAM 24X36.dgn |
| ETR, M1.2.dgn |
| Ref, M1.1.dgn |
| SCRBGND, Floor Plan redo.dgn |
| site.dgn |
File details come from the government source that posted it. Updated .