AMSC N/A FSC 6150

Distribution Statement A. Approved for public release, distribution is unlimited.

INCH-POUND

MIL-DTL-53126/3A

16 OCTOBER 2012

SUPERSEDING

MIL-E-53126(ME)

20 April 1992

DETAIL SPECIFICATION SHEET

POWER DISTRIBUTION, ILLUMINATION SYSTEMS, ELECTRICAL

DISTRIBUTION SYSTEM, 40 AMPS/PHASE (A/P)

This specification is approved for use within US Army Research Development and Engineering Command, Communications and Electronics Research and Development Center, Product Realization Directorate, Department of the Army and is available for use by all Departments and Agencies of the Department of Defense.

The requirement for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-53126.

1. SCOPE

1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type III, model: M40.

2. APPLICABLE DOCUMENTS

2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.

DRAWING# NOMENCLATURE DRAWING # NOMENCLATURE

CECOM & PM-MEP Drawings - Cage Code: 97403 and 30554

13229E6353 Distribution System, Electrical, Three Phase, 40 Amperes/Phase

13229E6357 Connector Assembly 40 AMP/PH Input Plug

Source: http://assist.dla.mil -- Downloaded: 2019-02-04T13:27Z Check the source to verify that this is the current version before use.

MIL-DTL-53126/3A

(Copies of drawings required by contractors in connection with specific acquisition functions should be obtained from: PROJECT MANAGER-MOBILE ELECTRIC POWER, 5850 Delafield Road, Bldg 324 FT BELVOIR VA 22060-5809.)

3. REQUIREMENTS

3.1. Requirements. The M40 PDISE shall be a self-contained, free-standing, man portable unit. The system shall be capable of distributing 40 A/P of electricity to all its outputs simultaneously, as specified herein.

Type IV – 40 A/P distribution system

3.2. Design. The M40 PDISE shall be IAW TA13229E6353 and as specified herein.

3.2.1. Dimensions. The M40 PDISE shall not be greater than the following dimensions:

Length (Inches) Width (Inches) Height (Inches)

25.00 19.00 18.00

3.2.2. Weight. The M40 PDISE shall weigh no more than 50 pounds.

3.2.3. M40 PDISE Inputs. The M40 PDISE shall have a single 3-phase input capable of handling 40 A/P.

3.2.3.1. Input circuit interrupter. The input circuit for the M40 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.

3.2.3.2. Input Connector. The M40 PDISE shall have a 40 ampere, three phase, male, input receptacle IAW 13229E6357.

3.2.4. M40 PDISE Outputs The M40 PDISE shall have the following output circuits and connectors:

Quantity Output Rating Ouput Connector P/N*

1 40Amp, 3 phase M90556C32413P

12 20 Amp, 3 phase M3406D16-10S

*Note: See 3.3.16.1 in MIL-DTL-53126.

3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.

3.2.5. Type III accessories. The unit shall be provided with the following accessories:

Quantity Description Reference*

1 Input interface cable assembly, rated at 40/60 amperes 3.3.18.1*

2 40/60 A/P cable assemblies 3.3.18.4*

3 20 A/P cable assemblies (25 ± 0.25 feet long) 3.3.18.6*

3 20 A/P cable assemblies (50 ± 0.25 feet long) 3.3.18.6*

2 Transition cable assemblies 3.3.18.8*

4 Single strap assemblies 3.3.19.2*

6 Cinching Strap 3.3.91.1*

1 Receptacle assembly 3.3.17*

1 In-Line GFCI 3.3.18.10*

1 Container 2.1

*Note: See requirement paragraph referenced MIL-DTL-53126.

2.00 MAX

10.75

2.50

CARRYING

STRAP

20.75

1.50

MARKING TAG

(WHITE)

CINCHING

STRAP

3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram:

C B

A

J2

J2C4L3 J2B4L2 J2A4L1

J2N4NEUT

J2G6GND

N G

OUTPUT

40 A 3 PHASE

L3

BB BB

L2 L1

BB

NEUT

BB BB

GND

CB1 INPUT

40 A 3 PHASE

J1A4CB1A

J1B4CB1B

J1C4CB1C

J1G6GND

J1N4NEUT

A B C

J1

G

N

CB1A

CB1B

CB1C

CB1A4L1

CB1B4L2

CB1C4L3

A B

C

J3 OUTPUT

20 A 1 PHASE CB3

J3A12CB3

J3B12NEUT

J3C12GND

CB312L3

A B C

J5 OUTPUT

20 A 1 PHASE CB5

J5A12CB5

J5B12NEUT

J5C12GND

CB512L2

A

B C

J7 OUTPUT

20 A 1 PHASE CB7

J7A12CB7

J7B12NEUT

J7C12GND

CB712L1

CB9 20 A 1 PHASE

OUTPUT J9

C

B A

J9C12GND

J9B12NEUT

J9A12CB9 CB912L3

A

B C

J11A12CB11

J11B12NEUT

J11C12GND

J11 OUTPUT

20 A 1 PHASE CB1

CB1112L2

CB13 20 A 1 PHASE

OUTPUT J13

J13C12GND

J13B12NEUT

J13A12CB13

C B

A CB1312L1

CB4

C B

A J4

J4C12GND

J4B12NEUT

J4A12CB4

OUTPUT

20 A 1 PHASE

CB412L3

CB6

C B A

J6

J6C12GND

J6B12NEUT

J6A12CB6

OUTPUT

20 A 1 PHASE

CB612L2

CB8

C

B

A J8

J8C12GND

J8B12NEUT

J8A12CB8

OUTPUT

20 A 1 PHASE

CB812L1

J10 A

B C

CB10

J10A12CB10

J10B12NEUT

J10C12GND

OUTPUT

20 A 1 PHASE

CB1012L3

CB12

C B

A

J12C12GND

J12B12NEUT

J12A12CB12

J12

OUTPUT

20 A 1 PHASE

CB1212L2

DS1CB1A

DS2CB1B

DS3CB1C

DS3

DS2

DS1

DS1NBB

DS2NBB

DS3NBB

LIGHT BRACKET

CIRCUIT BREAKER

MOUNTING PANEL

TOP COVER

CHASSIS GROUND

CB14 J14 OUTPUT

20 A 1 PHASE

CB1412L1

C B

A

J14C12GND

J14B12NEUT

J14A12CB14

3.2.7 This specification sheet had no superseding “base”. The original publication of this specification was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed necessary to capture the unique characteristics desired in the end item.

3.2.8 Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issue because this detail specification sheet although a part of the base document, was not published because it was a document with limited circulation and coordination that was used essentially by CR4.

Concluding Material

Custodian:

Preparing Activity:

Army - CR4 Army - CR4 (Project 6150-2012-012)

Review Activities:

DLA – GS

Note: The activities listed above were interested in this document as of the date of this document.

Since organization and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https://assist.dla.mil.

1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type III, model: M40.
2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.
3.2.1. Dimensions. The M40 PDISE shall not be greater than the following dimensions:
3.2.2. Weight. The M40 PDISE shall weigh no more than 50 pounds.
3.2.3. M40 PDISE Inputs. The M40 PDISE shall have a single 3-phase input capable of handling 40 A/P.
3.2.3.1. Input circuit interrupter. The input circuit for the M40 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.3.2. Input Connector. The M40 PDISE shall have a 40 ampere, three phase, male, input receptacle IAW 13229E6357.
3.2.4. M40 PDISE Outputs The M40 PDISE shall have the following output circuits and connectors:
*Note: See 3.3.16.1 in MIL-DTL-53126.
3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.5. Type III accessories. The unit shall be provided with the following accessories:
*Note: See requirement paragraph referenced MIL-DTL-53126.
3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram: