SPRBL1-20-Q-0029 Attachment 0003 (MIL-DTL-53126-3A-M40).pdf
Detail Specification Rev. A PDF 88 KB Posted
- Attached to
- Power Distribution Illumination System Electrical (PDISE) NSN 6150-01-598-4796, Distributing System M40
- Solicitation number
- SPRBL-20-Q-0029
View the file
Other versions and copies of MIL-DTL-53126-3A
| File | Revision | Posted | Attached to |
|---|---|---|---|
| SPRBL1-20-Q-0029 Attachment 0003 (MIL-DTL-53126-3A-M40).pdf Same revision and size as this file | Rev. A | Power Distribution Illumination System Electrical (PDISE) NSN 6150-01-598-4796, Distributing System M40 |
Who attaches MIL-DTL-53126-3A
| Agency | Files |
|---|---|
| Defense Logistics Agency Land and Maritime | 2 |
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMSC N/A FSC 6150
Distribution Statement A. Approved for public release, distribution is unlimited.
INCH-POUND
MIL-DTL-53126/3A
16 OCTOBER 2012
SUPERSEDING
MIL-E-53126(ME)
20 April 1992
DETAIL SPECIFICATION SHEET
POWER DISTRIBUTION, ILLUMINATION SYSTEMS, ELECTRICAL
DISTRIBUTION SYSTEM, 40 AMPS/PHASE (A/P)
This specification is approved for use within US Army Research Development and Engineering Command, Communications and Electronics Research and Development Center, Product Realization Directorate, Department of the Army and is available for use by all Departments and Agencies of the Department of Defense.
The requirement for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-53126.
1. SCOPE
1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type III, model: M40.
2. APPLICABLE DOCUMENTS
2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.
DRAWING# NOMENCLATURE DRAWING # NOMENCLATURE
CECOM & PM-MEP Drawings - Cage Code: 97403 and 30554
13229E6353 Distribution System, Electrical, Three Phase, 40 Amperes/Phase
13229E6357 Connector Assembly 40 AMP/PH Input Plug
Source: http://assist.dla.mil -- Downloaded: 2019-02-04T13:27Z Check the source to verify that this is the current version before use.
MIL-DTL-53126/3A
(Copies of drawings required by contractors in connection with specific acquisition functions should be obtained from: PROJECT MANAGER-MOBILE ELECTRIC POWER, 5850 Delafield Road, Bldg 324 FT BELVOIR VA 22060-5809.)
3. REQUIREMENTS
3.1. Requirements. The M40 PDISE shall be a self-contained, free-standing, man portable unit. The system shall be capable of distributing 40 A/P of electricity to all its outputs simultaneously, as specified herein.
Type IV – 40 A/P distribution system
3.2. Design. The M40 PDISE shall be IAW TA13229E6353 and as specified herein.
3.2.1. Dimensions. The M40 PDISE shall not be greater than the following dimensions:
Length (Inches) Width (Inches) Height (Inches)
25.00 19.00 18.00
3.2.2. Weight. The M40 PDISE shall weigh no more than 50 pounds.
3.2.3. M40 PDISE Inputs. The M40 PDISE shall have a single 3-phase input capable of handling 40 A/P.
3.2.3.1. Input circuit interrupter. The input circuit for the M40 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.3.2. Input Connector. The M40 PDISE shall have a 40 ampere, three phase, male, input receptacle IAW 13229E6357.
3.2.4. M40 PDISE Outputs The M40 PDISE shall have the following output circuits and connectors:
Quantity Output Rating Ouput Connector P/N*
1 40Amp, 3 phase M90556C32413P
12 20 Amp, 3 phase M3406D16-10S
*Note: See 3.3.16.1 in MIL-DTL-53126.
3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.5. Type III accessories. The unit shall be provided with the following accessories:
Quantity Description Reference*
1 Input interface cable assembly, rated at 40/60 amperes 3.3.18.1*
2 40/60 A/P cable assemblies 3.3.18.4*
3 20 A/P cable assemblies (25 ± 0.25 feet long) 3.3.18.6*
3 20 A/P cable assemblies (50 ± 0.25 feet long) 3.3.18.6*
2 Transition cable assemblies 3.3.18.8*
4 Single strap assemblies 3.3.19.2*
6 Cinching Strap 3.3.91.1*
1 Receptacle assembly 3.3.17*
1 In-Line GFCI 3.3.18.10*
1 Container 2.1
*Note: See requirement paragraph referenced MIL-DTL-53126.
2.00 MAX
10.75
2.50
CARRYING
STRAP
20.75
1.50
MARKING TAG
(WHITE)
CINCHING
STRAP
3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram:
C B
A
J2
J2C4L3 J2B4L2 J2A4L1
J2N4NEUT
J2G6GND
N G
OUTPUT
40 A 3 PHASE
L3
BB BB
L2 L1
BB
NEUT
BB BB
GND
CB1 INPUT
40 A 3 PHASE
J1A4CB1A
J1B4CB1B
J1C4CB1C
J1G6GND
J1N4NEUT
A B C
J1
G
N
CB1A
CB1B
CB1C
CB1A4L1
CB1B4L2
CB1C4L3
A B
C
J3 OUTPUT
20 A 1 PHASE CB3
J3A12CB3
J3B12NEUT
J3C12GND
CB312L3
A B C
J5 OUTPUT
20 A 1 PHASE CB5
J5A12CB5
J5B12NEUT
J5C12GND
CB512L2
A
B C
J7 OUTPUT
20 A 1 PHASE CB7
J7A12CB7
J7B12NEUT
J7C12GND
CB712L1
CB9 20 A 1 PHASE
OUTPUT J9
C
B A
J9C12GND
J9B12NEUT
J9A12CB9 CB912L3
A
B C
J11A12CB11
J11B12NEUT
J11C12GND
J11 OUTPUT
20 A 1 PHASE CB1
CB1112L2
CB13 20 A 1 PHASE
OUTPUT J13
J13C12GND
J13B12NEUT
J13A12CB13
C B
A CB1312L1
CB4
C B
A J4
J4C12GND
J4B12NEUT
J4A12CB4
OUTPUT
20 A 1 PHASE
CB412L3
CB6
C B A
J6
J6C12GND
J6B12NEUT
J6A12CB6
OUTPUT
20 A 1 PHASE
CB612L2
CB8
C
B
A J8
J8C12GND
J8B12NEUT
J8A12CB8
OUTPUT
20 A 1 PHASE
CB812L1
J10 A
B C
CB10
J10A12CB10
J10B12NEUT
J10C12GND
OUTPUT
20 A 1 PHASE
CB1012L3
CB12
C B
A
J12C12GND
J12B12NEUT
J12A12CB12
J12
OUTPUT
20 A 1 PHASE
CB1212L2
DS1CB1A
DS2CB1B
DS3CB1C
DS3
DS2
DS1
DS1NBB
DS2NBB
DS3NBB
LIGHT BRACKET
CIRCUIT BREAKER
MOUNTING PANEL
TOP COVER
CHASSIS GROUND
CB14 J14 OUTPUT
20 A 1 PHASE
CB1412L1
C B
A
J14C12GND
J14B12NEUT
J14A12CB14
3.2.7 This specification sheet had no superseding “base”. The original publication of this specification was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed necessary to capture the unique characteristics desired in the end item.
3.2.8 Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issue because this detail specification sheet although a part of the base document, was not published because it was a document with limited circulation and coordination that was used essentially by CR4.
Concluding Material
Custodian:
Preparing Activity:
Army - CR4 Army - CR4 (Project 6150-2012-012)
Review Activities:
DLA – GS
Note: The activities listed above were interested in this document as of the date of this document.
Since organization and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https://assist.dla.mil.
| 1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type III, model: M40. |
| 2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation. |
| 3.2.1. Dimensions. The M40 PDISE shall not be greater than the following dimensions: |
| 3.2.2. Weight. The M40 PDISE shall weigh no more than 50 pounds. |
| 3.2.3. M40 PDISE Inputs. The M40 PDISE shall have a single 3-phase input capable of handling 40 A/P. |
| 3.2.3.1. Input circuit interrupter. The input circuit for the M40 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit. |
| 3.2.3.2. Input Connector. The M40 PDISE shall have a 40 ampere, three phase, male, input receptacle IAW 13229E6357. |
| 3.2.4. M40 PDISE Outputs The M40 PDISE shall have the following output circuits and connectors: |
| *Note: See 3.3.16.1 in MIL-DTL-53126. |
| 3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit. |
| 3.2.5. Type III accessories. The unit shall be provided with the following accessories: |
| *Note: See requirement paragraph referenced MIL-DTL-53126. |
| 3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram: |