AMSC N/A FSC 6150
Distribution Statement A. Approved for public release, distribution is unlimited.
INCH-POUND
MIL-DTL-53126/2A
16 OCTOBER 2012
SUPERSEDING
MIL-E-53126(ME)
20 April 1992
DETAIL SPECIFICATION SHEET
POWER DISTRIBUTION, ILLUMINATION SYSTEMS, ELECTRICAL
FEEDER SYSTEM, 100 AMPS/PHASE (A/P)
This specification is approved for use within US Army Research Development and Engineering Command, Communications and Electronics Research and Development Center, Product Realization Directorate, Department of the Army and is available for use by all Departments and Agencies of the Department of Defense.
The requirement for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-53126.
1. SCOPE
1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type I, model: M100.
2. APPLICABLE DOCUMENTS
2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.
DRAWING# NOMENCLATURE DRAWING # NOMENCLATURE
CECOM & PM-MEP Drawings - Cage Code: 97403 and 30554
13229E6351 Feeder System, Electrical, Three Phase, 100 Amperes/Phase
13229E6327 Connector Assembly 100 AMP/PH Input Plug
Source: http://assist.dla.mil -- Downloaded: 2019-02-04T13:26Z Check the source to verify that this is the current version before use.
(Copies of drawings required by contractors in connection with specific acquisition functions should be obtained from: PROJECT MANAGER-MOBILE ELECTRIC POWER, 5850 Delafield Road, Bldg 324 FT BELVOIR VA 22060-5809.)
3. REQUIREMENTS
3.1. Requirements. The M100 PDISE shall be a self-contained, free-standing, man portable unit. The system shall be capable of distributing 100 A/P of electricity to all its outputs simultaneously, as specified herein.
Type II – 100 A/P feeder system
3.2. Design. The M100 PDISE shall be IAW TA13229E6351 and as specified herein.
3.2.1. Dimensions. The M100 PDISE shall not be greater than the following dimensions:
Length (Inches) Width (Inches) Height (Inches)
24.00 19.00 22.00
3.2.2. Weight. The M100 PDISE shall weigh no more than 60 pounds.
3.2.3. M100 PDISE inputs. The M100 PDISE shall have a single 3-phase input capable of handling 100 A/P.
3.2.3.1. Input circuit interrupter. The input circuit for the M100 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.3.2. Input Connector. The M100 PDISE shall have a 100 ampere, three phase, male, input receptacle IAW 13229E6327.
3.2.4. M100 PDISE Outputs The M100 PDISE shall have the following output circuits and connectors:
Quantity Output Rating Ouput Connector P/N*
2 60 Amp, 3 phase M90556C32413P
2 40 Amp, 3 phase M90556C32413P
2 20 Amp, 1 phase M3406D16-10S
*Note: See 3.3.16.1 in MIL-DTL-53126.
3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.5. Type I accessories. The unit shall be provided with the following accessories:
Quantity Description Reference*
1 Input interface cable assembly, rated at 100 amperes
3.3.18.1
2 100 A/P cable assemblies 3.3.18.3
4 Double-strap carriers 3.3.19.3
*Note: See requirement paragraph referenced MIL-DTL-53126.
CARRYING
STRAPS
CINCHING
STRAPS
CARRYING
STRAPS
MARKING TAG
(WHITE)
JOINING
STRAP
1.50 STK
10.00
27.75
4.75 3x 1.50
JOINING
STRAP
3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram:
CB
MAIN
J2G6GND
J2G6GND
J2G6GND
J2G6GND
G2
G1
G4
G3 J1G6GND
J1G6GND
J1G6GND G4
G3
G2
J2N1NEUT N
CB1C
CB1B
J1G6GND
J1N1NEUT
G1
N
J2C1L3
J2B1L2
J2A1L1
C
B
A CB1A A
B
C
J1A1CB1A
J1B1CB1B
J1C1CB1C
J3C4CB3
J3B4CB3
J3A4CB3A
C
B
A CB3A CB4A A
B
C
J4A4CB4A
J4B4CB4B
J4C4CB4C
N
G
J3N4NEUT
J3G6GND
CB3B
CB3C
G
N
J4G6GND
J4N4NEUT
CB4B
CB4C
BB
GND L3
BB
CB6C
CB6B
J6N4NEUT
J6G6GND
N
G
CB5C
CB5B
J5G6GND
J5N4NEUT
G
N
J8A12CB8
J8B12NEUT
J8C12GND
J6C4CB6C
J6B4CB6B
J6A4CB6A
100 A 3 PHASE
OUTPUT
40 A 3 PHASE
OUTPUT
60 A 3 PHASE
OUTPUT
20 A 1 PHASE
OUTPUT
A
B
C
J8
J6
C
B
A
J4
J2
CB812L1 CB8
CB6A
L2
BB BB
L1 NEUT
BB
CB5A
CB712L3 CB7
J1 INPUT
100 A 3 PHASE
J3 OUTPUT
60 A 3 PHASE
A
B
C
J5A4CB5A
J5B4CB5B
J5C4CB5C
J5 OUTPUT
40 A 3 PHASE
20 A 1 PHASE
OUTPUT J7
J7C12GND
J7B12NEUT
J7A12CB7
C
B
A
DS3CB1C
DS2CB1B
DS1CB1A
DS3NBB
DS2NBB
DS1NBB
DS3
DS2
DS1
CHASSIS GROUND
TOP COVER
CIRCUIT BREAKER
MOUNTING PANEL
LIGHT BRACKET
CB3A4L1
CB3B4L2
CB3C4L3
CB4A4L1
CB4B4L2
CB4C4L3
CB5A4L1
CB5B4L2
CB5C4L3
CB6A4L1
CB6B4L2
CB6C4L3
CB1C1L3
CB1B1L2
CB1A1L1
3.2.7. This specification sheet had no superseding “base”. The original publication was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed necessary to capture the unique characteristics desired in the end item.
3.2.8. Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issues because this detail specification sheet although a part of the base document, was not published because it was a document with limited coordination that was used essentially by CR4.
Concluding Material
Custodian:
Preparing Activity:
Army - CR4 Army - CR4 (Project 6150-2013-002)
Review Activities:
DLA – GS
Note: The activities listed above were interested in this document as of the date of this document.
Since organization and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https://assist.dla.mil.
| 1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type I, model: M100. |
| 2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation. |
| 3.2.1. Dimensions. The M100 PDISE shall not be greater than the following dimensions: |
| 3.2.2. Weight. The M100 PDISE shall weigh no more than 60 pounds. |
| 3.2.3. M100 PDISE inputs. The M100 PDISE shall have a single 3-phase input capable of handling 100 A/P. |
| 3.2.3.1. Input circuit interrupter. The input circuit for the M100 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit. |
| 3.2.3.2. Input Connector. The M100 PDISE shall have a 100 ampere, three phase, male, input receptacle IAW 13229E6327. |
| 3.2.4. M100 PDISE Outputs The M100 PDISE shall have the following output circuits and connectors: |
| *Note: See 3.3.16.1 in MIL-DTL-53126. |
| 3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit. |
| 3.2.5. Type I accessories. The unit shall be provided with the following accessories: |
| *Note: See requirement paragraph referenced MIL-DTL-53126. |
| 3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram: |
| 3.2.7. This specification sheet had no superseding “base”. The original publication was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed n... |
| 3.2.8. Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issues because this detail specification sheet although a part of the base document, was not published because it wa... |
NOMENCLATURE