AMSC N/A FSC 6150

Distribution Statement A. Approved for public release, distribution is unlimited.

INCH-POUND

MIL-DTL-53126/2A

16 OCTOBER 2012

SUPERSEDING

MIL-E-53126(ME)

20 April 1992

DETAIL SPECIFICATION SHEET

POWER DISTRIBUTION, ILLUMINATION SYSTEMS, ELECTRICAL

FEEDER SYSTEM, 100 AMPS/PHASE (A/P)

This specification is approved for use within US Army Research Development and Engineering Command, Communications and Electronics Research and Development Center, Product Realization Directorate, Department of the Army and is available for use by all Departments and Agencies of the Department of Defense.

The requirement for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-53126.

1. SCOPE

1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type I, model: M100.

2. APPLICABLE DOCUMENTS

2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.

DRAWING# NOMENCLATURE DRAWING # NOMENCLATURE

CECOM & PM-MEP Drawings - Cage Code: 97403 and 30554

13229E6351 Feeder System, Electrical, Three Phase, 100 Amperes/Phase

13229E6327 Connector Assembly 100 AMP/PH Input Plug

Source: http://assist.dla.mil -- Downloaded: 2019-02-04T13:26Z Check the source to verify that this is the current version before use.

(Copies of drawings required by contractors in connection with specific acquisition functions should be obtained from: PROJECT MANAGER-MOBILE ELECTRIC POWER, 5850 Delafield Road, Bldg 324 FT BELVOIR VA 22060-5809.)

3. REQUIREMENTS

3.1. Requirements. The M100 PDISE shall be a self-contained, free-standing, man portable unit. The system shall be capable of distributing 100 A/P of electricity to all its outputs simultaneously, as specified herein.

Type II – 100 A/P feeder system

3.2. Design. The M100 PDISE shall be IAW TA13229E6351 and as specified herein.

3.2.1. Dimensions. The M100 PDISE shall not be greater than the following dimensions:

Length (Inches) Width (Inches) Height (Inches)

24.00 19.00 22.00

3.2.2. Weight. The M100 PDISE shall weigh no more than 60 pounds.

3.2.3. M100 PDISE inputs. The M100 PDISE shall have a single 3-phase input capable of handling 100 A/P.

3.2.3.1. Input circuit interrupter. The input circuit for the M100 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.

3.2.3.2. Input Connector. The M100 PDISE shall have a 100 ampere, three phase, male, input receptacle IAW 13229E6327.

3.2.4. M100 PDISE Outputs The M100 PDISE shall have the following output circuits and connectors:

Quantity Output Rating Ouput Connector P/N*

2 60 Amp, 3 phase M90556C32413P

2 40 Amp, 3 phase M90556C32413P

2 20 Amp, 1 phase M3406D16-10S

*Note: See 3.3.16.1 in MIL-DTL-53126.

3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.

3.2.5. Type I accessories. The unit shall be provided with the following accessories:

Quantity Description Reference*

1 Input interface cable assembly, rated at 100 amperes

3.3.18.1

2 100 A/P cable assemblies 3.3.18.3

4 Double-strap carriers 3.3.19.3

*Note: See requirement paragraph referenced MIL-DTL-53126.

CARRYING

STRAPS

CINCHING

STRAPS

CARRYING

STRAPS

MARKING TAG

(WHITE)

JOINING

STRAP

1.50 STK

10.00

27.75

4.75 3x 1.50

JOINING

STRAP

3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram:

CB

MAIN

J2G6GND

J2G6GND

J2G6GND

J2G6GND

G2

G1

G4

G3 J1G6GND

J1G6GND

J1G6GND G4

G3

G2

J2N1NEUT N

CB1C

CB1B

J1G6GND

J1N1NEUT

G1

N

J2C1L3

J2B1L2

J2A1L1

C

B

A CB1A A

B

C

J1A1CB1A

J1B1CB1B

J1C1CB1C

J3C4CB3

J3B4CB3

J3A4CB3A

C

B

A CB3A CB4A A

B

C

J4A4CB4A

J4B4CB4B

J4C4CB4C

N

G

J3N4NEUT

J3G6GND

CB3B

CB3C

G

N

J4G6GND

J4N4NEUT

CB4B

CB4C

BB

GND L3

BB

CB6C

CB6B

J6N4NEUT

J6G6GND

N

G

CB5C

CB5B

J5G6GND

J5N4NEUT

G

N

J8A12CB8

J8B12NEUT

J8C12GND

J6C4CB6C

J6B4CB6B

J6A4CB6A

100 A 3 PHASE

OUTPUT

40 A 3 PHASE

OUTPUT

60 A 3 PHASE

OUTPUT

20 A 1 PHASE

OUTPUT

A

B

C

J8

J6

C

B

A

J4

J2

CB812L1 CB8

CB6A

L2

BB BB

L1 NEUT

BB

CB5A

CB712L3 CB7

J1 INPUT

100 A 3 PHASE

J3 OUTPUT

60 A 3 PHASE

A

B

C

J5A4CB5A

J5B4CB5B

J5C4CB5C

J5 OUTPUT

40 A 3 PHASE

20 A 1 PHASE

OUTPUT J7

J7C12GND

J7B12NEUT

J7A12CB7

C

B

A

DS3CB1C

DS2CB1B

DS1CB1A

DS3NBB

DS2NBB

DS1NBB

DS3

DS2

DS1

CHASSIS GROUND

TOP COVER

CIRCUIT BREAKER

MOUNTING PANEL

LIGHT BRACKET

CB3A4L1

CB3B4L2

CB3C4L3

CB4A4L1

CB4B4L2

CB4C4L3

CB5A4L1

CB5B4L2

CB5C4L3

CB6A4L1

CB6B4L2

CB6C4L3

CB1C1L3

CB1B1L2

CB1A1L1

3.2.7. This specification sheet had no superseding “base”. The original publication was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed necessary to capture the unique characteristics desired in the end item.

3.2.8. Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issues because this detail specification sheet although a part of the base document, was not published because it was a document with limited coordination that was used essentially by CR4.

Concluding Material

Custodian:

Preparing Activity:

Army - CR4 Army - CR4 (Project 6150-2013-002)

Review Activities:

DLA – GS

Note: The activities listed above were interested in this document as of the date of this document.

Since organization and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https://assist.dla.mil.

1.1. Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type I, model: M100.
2.1. Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.
3.2.1. Dimensions. The M100 PDISE shall not be greater than the following dimensions:
3.2.2. Weight. The M100 PDISE shall weigh no more than 60 pounds.
3.2.3. M100 PDISE inputs. The M100 PDISE shall have a single 3-phase input capable of handling 100 A/P.
3.2.3.1. Input circuit interrupter. The input circuit for the M100 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.3.2. Input Connector. The M100 PDISE shall have a 100 ampere, three phase, male, input receptacle IAW 13229E6327.
3.2.4. M100 PDISE Outputs The M100 PDISE shall have the following output circuits and connectors:
*Note: See 3.3.16.1 in MIL-DTL-53126.
3.2.4.1. Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.5. Type I accessories. The unit shall be provided with the following accessories:
*Note: See requirement paragraph referenced MIL-DTL-53126.
3.2.6. Wiring diagram. The circuits shall be configured as specified in the following wiring diagram:
3.2.7. This specification sheet had no superseding “base”. The original publication was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed n...
3.2.8. Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issues because this detail specification sheet although a part of the base document, was not published because it wa...

NOMENCLATURE

File details come from the government source that posted it. Updated .