This is a technical specification document for a freshwater or seawater fire main hose assembly required by Pearl Harbor Naval Shipyard & Intermediate Maintenance Facility (PHNSY & IMF).

The specification requires a 4-inch inner diameter, 15-foot-long hose assembly with nonmetallic construction featuring high UV protection and abrasion resistance for use in a marine environment with high UV exposure. The hose must have a minimum working pressure of 250 PSI, burst pressure of 1,000 PSI, rated bend radius of 16 inches or less, and continuous temperature rating of -20°F to 180°F. Construction requirements specify a nitrile rubber tube meeting ARPM Class B standards for oil resistance, reinforcement with synthetic textile fabrics and high-tensile wire helix, and a nonslip nitrile rubber cover with high abrasion and ozone resistance formulated to prevent cracking or failure for a minimum of 8 years. The hose shall be manufactured to ARPM standard IP-2 and assembled per NAHAD certification standards. End fittings must include brass 4-inch, 300 PSI heavy-duty male and female cam and groove adapters (PT Coupling Co. specified or equal) with four stainless steel locking arms on the female coupler, coupled using stainless steel crimp ferrules with no hose clamps permitted. All end fittings, ferrules, and one inch of hose at each end shall be painted fire engine red with at least 80 percent coverage. Hose branding shall include standard line markings, working pressure, date of manufacture, "PHNSY & IMF S/99," and contrasting 1-inch lettering. Vendors must provide manufacturer cut sheets with technical specifications and contact information, reference manufacturer part numbers, and submit sample hose assemblies for destructive testing at vendor expense if requested. Each hose assembly shall be hydrostatically tested at 275 PSIG for 10 minutes, assigned a unique serial number, and provided with written certification signed by the tester including test date, pressure, and duration. Or-equal offers require prior approval from PHNSY & IMF Code 260.8.

View the file

Other files

File Type Posted
Solicitation - SPMYM426Q3302_FINAL.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1 – Additional Technical Information 11 January 2025

Filename: Hose Assy Fire Main FW&SW 4 IN x 15 FT PHNSY (1-11-2025).doc

CONTRACT ITEM DESCRIPTION:

Freshwater or Seawater Suction/Discharge Fire Main Hose Assembly (4" ID X 15’ Long)

Purchase Specification:

Hose, Nonmetallic, High UV Protection & Abrasion Resistant Tube & Cover: Coupled and Fully Assembled.

Application or Intended Use: Will be installed in the high UV exposure weather in a marine environment for use as a temporary freshwater or saltwater fire header. Use location in Pearl Harbor, Hawaii. When not in use, hose will be coiled and stacked for storage in an area.

1. Size: 4” ID, length 15’

2. Nominal OD: n/a

3. Vacuum: Full

4. Working Pressure: 250 PSI, minimum.

5. Burst Pressure: 1,000 PSI, minimum.

6. Rated bend radius: 16 inches or less.

7. Rated Continuous Temperature: -20ºF to 180ºF

8. Weight of hose: approximately 3-4 lbs. per foot, not including the added weight of end fittings.

Construction:

9. Tube: Nitrile rubber. Shall meet Association for Rubber Product Manufacturers (ARPM), Class B standard for medium/high oil resistance. Hose shall have a wall construction which allows the use of crimped or swaged couplings with interlocking ferrules.

10. Reinforcement: Multiple plies of synthetic textile fabrics with one or more high-tensile strength wire helix.

11. Cover: Non-slip grip exterior surface for safety and handling. Nitrile rubber with high abrasion resistance. The cover shall be formulated to provide resistance to high UV exposure and weathering adequate to prevent cracking or failure due to these causes for a minimum of 8 years when installed and stored as described in this specification. Class B standard for medium/high oil resistance. High ozone resistance.

12. Cover Color: Black cover with a contrasting Red colored brand strip down the entire lay line with contrasting lettering.

13. The hose shall be manufactured in conformance with ARPM standard IP-2.

14. Hose end assembly shall be accomplished in accordance with established National Association for Hose Accessories Distribution

(NAHAD) certification standards.

15. Each hose assembly shall have the following components installed at each end:

A. 1st Hose End; Brass, 4”, 300 psi, Heavy Duty Male Cam & Groove Adapter by Hose Shank. PT Coupling Co., alloy UNS C92200, Part # 40EHD, Item # 1200540H, or equal.

B. 2nd Hose End; Brass, 4”, 300 psi, Heavy Duty Female Cam & Groove Coupler by Hose Shank with four (4) Stainless Steel Cam Arms, Pins, and Pull Rings. PT Coupling Co., alloy UNS C92200, Part # 40CHD, Item # 1200340H (modified to include four (4) stainless steel locking arms, pins, and pull rings), or equal.

C. End Fitting Interlocking Ferrules: End fittings shall be coupled to the hose with PT Coupling Co., “Pro-Grip C50SS Stainless Steel Crimp Ferrule”, sized to match the hose and fittings. No hose clamps or bands will be accepted.

16. End fittings shall be made from virgin brass, and meet Commercial Item Description (CID) A-A-59326 and shall have a working pressure of 300 PSI or greater. The ferrules and at least one inch of hose at each end of the hose assembly shall be painted “fire engine” red, or similar. Paint coverage of these areas shall be at least 80%.

17. Branding / Marking: Hose shall be continuously ink-branded, stencil painted, Mylar or stripe branded /marked in 1” lettering (minimum), which shall be in a contrasting color to the RED band strip and black outer cover of the hose. The lettering shall state as a minimum:

A. Standard Hose Brand/Line/Model number, working pressure, date of manufacture

B. PHNSY & IMF S/99

18. Price quotes for market survey request will not be accepted without the hose, fitting, and ferrule manufacturer cut sheets or product description sheets attached, which shall include as a minimum the technical characteristic of the components and the manufacturer’s address, telephone/fax number and manufacturer point of contact. The market survey price quote must reference the manufacturer’s part numbers for the item quoted.

19. Each quoting vendors, if requested, shall submit a five foot (or longer) hose assembly at vendor expense, for destructive testing analysis by the government.

20. Or-Equal offers must be approved by PHNSY & IMF, Code 260.8 prior to purchase.

Packaging Requirements

21. Packing to prevent any damage including kinking, gouges, cuts, or abrasions of hose covers, or damage/deformation of end fittings.

Packing shall not violate the minimum bend radius of hose assembly (see para 6).

Hose Test & Assembly Certification:

22. Each hose assembly shall be hydrostatically strength tested with commercial clean, fresh water as a test medium, at 275 (+10, -0)

PSIG for 10 minutes. Each certified hose assembly shall be assigned a unique serial number by the vendor assembling the hose carcass and end fittings. The serial number shall be permanently stamped or etch marked on the hose ferrule of each hose end. Hose manufacturer shall certify that hose assemblies are free of leaks, deformation, layer separation, excessive twisting or kinking; that end fittings are not damaged or faulty, and that the end fittings and ferrules are properly positioned on the hose ends, in accordance to NAHAD standards. Also that the hose does not have hairline cracks, breaks, abrasions, soft spots, bulges, or other defects in the outer cover. Written certification of satisfactory hose end assembly in accordance with NAHAD standards and satisfactory hydrostatically testing shall be provided with each shipped hose. Written certifications shall include the witness signature of the tester, test date, test pressure and duration, and shall include the unique hose serial numbers.