OFFICIAL (OPEN)
Date: 19 May 2021
SPECIFICATIONS
FOR
GROUND SUPPORT EQUIPMENT
INTRODUCTION
1. The Contractor shall provide and deliver the list of Ground Support Equipment (GSE) and associated services[footnoteRef:1] detailed in this document to support flying activities in Mountain Home Air Force Base (MHAFB). All goods and services shall be provisioned in accordance with the requirements as stated within this document and all applicable federal, state, local laws and applicable regulations. [1: Includes the delivery and collection of the equipment, and the 1-to-1 exchange of malfunctioned equipment.]
2. The Contractor shall offer the list of GSE and associated services required by the Authority on a rental basis.
REQUIREMENTS
3. Requirement Window.
a. Delivery: not later than 18 Aug 2021 0900H
b. Collection: not earlier than 30 Sep 2021 0900H
4. Delivery Location. The GSE and associated services shall be delivered to drop-off point within Mountain Home Air Force Base (MHAFB) (refer to Figure 2). The GSE shall be collected from the same location by the Contractor.
5. The breakdown of requirements is tabulated in Table 1 below.
Table 1: List of Ground Logistics Support Required
| S/N |
| Description |
| Qty Required |
| Other Operational Requirements |
| 1 |
| 3.1kVA Diesel Generators |
| 02 |
| · A/C Frequency: 50 Hz |
· A/C Output Voltage: 220 V
· Rated A/C Output: 2.8 kVA
· Maximum A/C output: 3.1 kVA
· Generator shall be equipped with US domestic power outlets
· Generator is required to be portable (i.e. can be towed by a tractor or shifted by a forklift)
| 2 |
| 15kVA Diesel Generators |
| 06 |
| · Power Rating: 15kVA |
· Rated Voltage: 230VAC
· Rated Current: 32A
· No. of Phases: 1 and 3
· No. of Outlets: Minimum one 1-phase outlet and one 3-phase outlet
| 3 |
| 16kVA Diesel Generators |
| 04 |
| · Power Rating: 16kVA |
· Rated Voltage: 230 / 400VAC
· Rated Current: 23.8A
· No. of Phases: 3
| 4 |
| 65kVA Diesel Generators |
| 06 |
| · Power Rating: 65kVA |
· Rated Voltage: 400VAC
· No. of Phases: 3 (50Hz)
· Requires US 110V domestic electrical outlets
| 5 |
| Electrical Power Cable Extension |
| 06 |
| · Output Rating: 230VAC, 1-Phase, 16A |
· Length: at least 250ft
· Recommended: 3/C 10 AWG (5.26mm) Cable (refer to Figure 1)
· The contractor is required to splice the power cable extension to the generator, and the adapter connector provided by the Authority. The Contractor shall also terminate the splice at the end of the requirement window.
| 6 |
| Electrical Power Cable Extension |
| 06 |
| · Output Rating: 230VAC, 3-Phase, 32A |
· Length: at least 250ft
· Recommended: 6/4 Type G Cable (refer to Figure 1)
· The contractor is required to splice the power cable extension to the generator, and the adapter connector provided by the Authority. The Contractor shall also terminate the splice at the end of the requirement window.
| 7 |
| Cable Protector Ramps |
| As Required |
| · Length of cable to be protected: approximately 500ft |
· Diameter of cable to be protected: 4 x ¼ in Fibre Optic cable
· The Contractor shall provide the manpower to lay the cable protector ramps at the predetermined location (refer to Figure 3) under supervision of the Authority’s personnel. The Contractor shall also provide the manpower to collect the cable protector ramps at the end of the requirement window.
· Sample:
Figure 1: Electrical Power Cable Extension required for Rental Generators (Items 5 & 6) Require Splicing Require Splicing Require Splicing Require Splicing
Figure 2: Drop-Off & Collection Point for GSE
The Contractor shall provide the manpower to lay the cable protector ramps along the gravel path depicted by the yellow box. The Contractor shall also provide the manpower to collect the cable protector ramps at the end of the requirement window.
OFFICIAL (OPEN)