This document is a Bill of Materials (BOM) detailing electrical panel components and circuit breakers required for an I-Line Panelboard assembly. The specification includes one main panelboard interior (HCP36868M, 800A with main breaker) and matching enclosure (HC4286WP, 42" W x 86" H x 12.95" D, Type 3R/12), along with associated grounding and neutral assembly kits. The BOM specifies multiple circuit breakers across different ratings and manufacturers: one 400A Q-series breaker, four 100A PowerPacT H breakers (HGA36100), and three 60A PowerPacT B breakers (BDA36060). Additional components include filler covers in 4.5-inch and 1.5-inch sizes, a Schneider Electric I-Line Enable Module (ICWL243X5563) with PM5563 Power Meter for 480VAC monitoring with Modbus capability, and three split-core current transformers (METSECTSP5A4080U, 800A with 5A output). All items are specified by manufacturer part number with exact quantities for procurement.

View the file

Other files

File Type Posted
RFQ.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Line Item Component Part Number Description Quantity

1.1 I-Line Panel Internals HCP36868M Interior, I-Line Panelboard, HCP, 800A, w/main breaker, 72in CB space, for 42in W x 86in H x 9.5in D box, Cu bus

1.2 I-Line Panel Enclsure HC4286WP Box, I-Line Panelboard, HCP, 42in W x 86in H x 12.95in D, Type 3R/12, w/trim

1.3 Ground Bar PK32DGTA Grounding Kit 1

1.4 Neutral Assembly Kit HCW8SN Solid neutral assembly kit, I-Line Panelboard, HCP, 800A, 14 AWG to 750kcmil

1.5 4.5 in Covers HNM4BL PNLBD 4.5" FILLER BLANK, 5 EA PER BOX 3

1.6 1.5 in Covers HNM1BL PNLBD 1.5" FILLER BLANK, 3 EA PER BOX 2

1.7 400 A Circuit Breaker Q432400 Circuit breaker, Q4, 400A, 3 pole, 240VAC, 25kA, I-Line, thermal magnetic

2.3 100A Circuit Breaker HGA36100 Circuit breaker, PowerPacT H, 100A, 3 pole, 600VAC, 18kA, I- Line, thermal magnetic, 80%, ABC

2.4 60A Circuit Breaker BDA36060 Circuit breaker, PowerPacT B, 60A, 3 pole, 600Y/347VAC, 14kA, I-Line, thermal magnetic, 80%, ABC

3.2 100A Circuit Breaker HGA36100 Circuit breaker, PowerPacT H, 100A, 3 pole, 600VAC, 18kA, I- Line, thermal magnetic, 80%, ABC

4.1 Power Metering Module ICWL243X5563

Schneider Electric ICWL243X5563 Picture I-Line Enable Module, PM5563 Power Meter, 480VAC, wide side left, w/CT shorting block, dual E/N + Modbus, 6in space

4.2 Current Transformer METSECTSP5A4080U split core current transformer, PowerLogic UL2808 CT, size4, 800A, 5A output

5.2 100A Circuit Breaker HGA36100 Circuit breaker, PowerPacT H, 100A, 3 pole, 600VAC, 18kA, I- Line, thermal magnetic, 80%, ABC