Specifications.pdf
PDF 186 KB Posted
- Attached to
- Diesel Tank Pump for BIA, Cheyenne River Agency
- Solicitation number
- 140A0124Q0011
About this file
This document contains specifications for a replacement diesel fuel pump and installation services. The Bureau of Indian Affairs Great Plains Region requires a Gasboy Atlas 9823K AST Single Remote Pump with a 10 vane rotary pump rated for 21 GPM, electronic register, 1" piping and fittings, and compatible with fuels up to B20. The existing pump will be removed and the new pump installed on an underground tank at the BIA Cheyenne River Agency in Eagle Butte, South Dakota. Pricing must include all costs for removal of the old pump, purchase and delivery of the new pump, and installation services. A point of contact is provided for any questions. Installation is to be completed by December 31, 2022.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Provisions_and_Clauses.pdf | ||
| Sol_140A0124Q0011.pdf | ||
| Request_for_Quotes.pdf | ||
| DOL_Wage_Determination.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS (BRAND NAME OR EQUIVALENT)
Gasboy Atlas 9823K AST Single Remote Pump w/Pulse Output
• Model Number: 9823K
• Description: ASTRA Split AST Pump
• Compatible Fluids: Conventional Motor Fuels, Oxygenated Fuel
Blends up to 15% Ethanol (E15), and Bio-Diesel Blends up to 20% (B20)
• Type: Pump
• Nozzle Position: Front Load
• Hoses: 1
• Products: 1
• Register: Electronic
• Electronic Totalizer: 999999
• Unit of Measure: Gallons
• Meter: Gilbarco 4 Piston Positive Displacement CFT Meter
• Pump/Motor: 1
• Pump: 10 Vane Rotary with Air Separator
• Motor: 1 HP (Continuous Duty Cycle) - 115V/60Hz (230V/50Hz
Optional)
• Flow Rating: 21 GPM
• Piping: 1 in. Internal Fuel Piping
• Discharge: 1 in. NPT
• Inlet: 1-1/2 in. NPT Island Connection
• Filter Adapter: Internal Spin-On Style with Standard Filter Base
• Working Pressure: 50 PSI
• Operating Temperature: -22°F to 131°F (-30°C to +55°C)
• Junction Box: Field Wiring Junction Box
• Housing: G90 Galvanized Steel (11 GA)
• Panels: Lockable Removable - Painted; Galvanized Steel (16
Gauge)
• Sheathing: Replaceable - Painted G60; Galvanized Steel (16
Gauge)
• Approvals: UL, cUL listed, NCWM approved, MC approved
• Warranty: 12 Month - Parts and Labor
1” Hanging Hardware to include nozzle, swivel, breakaway, curb hose, stubby hose.
Pipe and Fittings as needed.
Price must include all costs related to the replacement of the pump, including removal of existing pump, purchase of new pump, delivery and installation of new pump.
POINT OF CONTACT:
Terry Halfred 605-365-6572
Below is the tank that the pump needs to be installed on.