Specifications for Paint Cure Booth Inside a Shipping Container (JML 6147-5025)

This document is a federal specification for a portable, self-contained paint cure booth and touch-up room designed for use in dry-dock and pier-side environments. The containerized unit must operate continuously 24/7 in heavy-duty industrial environments with limited space, withstand salt and dust conditions, and operate across a temperature range of -32°F to 110°F with up to 100% non-condensing humidity. The shipping container serves as the structural basis and shall meet ISO 668 specifications with outside nominal dimensions of 9'6" high × 8'0" wide × 20'0" long, divided into a cure room and equipment room with dual man-doors for emergency egress.

The paint cure room working area must measure minimum 8'H × 7'6"W × 12'L and meet Class I Division 1 NFPA 33 requirements for spray application of flammable materials. The enclosure requires structural steel framing with 18-gauge painted steel wall and ceiling panels, fully functional dry chemical automatic sprinkler system (NFPA 17 compliant), LED overhead lighting providing minimum 100-foot candles, white enamel interior finish, and airflow maintained between 2000-3000 CFM. The equipment room houses the exhaust fan unit (tube axial with totally enclosed fan cooled motor), heating system maintaining 90-100°F interior at 30°F exterior using 80/20 recirculation mode, and electrical systems operating from single-source 460 VAC, 3-phase, 60 Hz power. All equipment must comply with OSHA standards (29 CFR 1910, 1915), applicable NFPA standards (70, 79, 33, 17), ANSI/ASHRAE Standard 52.2, AWS-D1 welding codes, and feature noncombustible or Class 2 filters with 98.6% efficiency, U.S. or Canadian manufactured bearings, and hazardous material exclusions including radioactive materials, asbestos, mercury, cadmium, lithium, and polychlorinated biphenyls. The contractor shall provide NRTL listing or field inspection approval, one-year warranty, five copies of operation/maintenance manuals with schematics, and must schedule basic performance testing with minimum 15-day advance notice to Puget Sound Naval Shipyard, with final acceptance requiring completion of all inspections, testing, and OSHA certification.

View the file

Other files

File Type Posted
CDRLS COMBINED.pdf PDF
Solicitation - SPMYM226Q7708.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .