Specifications.pdf

PDF 956 KB Posted

Attached to
CUSTOMS HOUSE ELECTRICAL RENEWAL Federal contract opportunity
Solicitation number
140P5425R0008
Issued by
Department of the Interior National Park Service Southeast Region

About this file

This document is a detailed electrical specifications file for the Christiansted National Historic Site's Danish Customs House electrical component renewal project. The specifications (Section 26 05 00) provide comprehensive technical requirements for electrical systems, including raceway installations, grounding, cable trays, support systems, identification, and electrical power monitoring. The project involves renewing electrical components at a historic site located at 2100 Church Street, St. Croix, VI 00820, with the serving utility being WAPA and the power source an underground 480/3/60, 400A utility-owned pad-mount transformer.

The document includes extensive technical details across multiple parts, covering topics such as conductor and cable specifications, support and seismic restraint requirements, installation guidelines, identification protocols, and quality control measures. The specifications outline precise requirements for electrical equipment, including acceptable manufacturers, installation methods, testing procedures, and performance standards. Key components include raceway and cable support systems, grounding electrodes, warning labels, equipment identification, and electrical power monitoring protocols, with a strong emphasis on compliance with NFPA 70, NECA standards, and other relevant electrical codes and regulations.

View the file

Other files for this federal contract opportunity

Other files attached to CUSTOMS HOUSE ELECTRICAL RENEWAL, newest first.
File Type Posted
Sol_140P5425R0008_Amd_0002.pdf PDF
Question___Answers_0002.pdf PDF
Sol_140P5425R0008_Amd_0001.pdf PDF
Past_Performance_Questionnaire.pdf PDF
Sol_140P5425R0008.pdf PDF
Wage_Determination.pdf PDF
Drawings.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMON WORK RESULTS FOR ELECTRICAL SECTION 26 05 00

Christiansted National Historic Site Christiansted, ST. Croix

Renew Electrical Components at Historic Danish Customs House Danish Customs House Christiansted National Historic Site

PMIS Number: 215118B

PROJECT SPECIFICATIONS

NATIONAL PARK SERVICE (NPS)

Design of Electrical Components – Christiansted National Historic Site

SUMMARY SHEET

PART 1 Introduction

This appendix of the Design Standards and Guidelines (DSG) presents USVI Public Utilities (SPU)

Standard Specifications for electrical design. These specifications are presented in Construction

Specification Institute (CSI) MasterFormat 2004. Table 1 lists the template SPU standards developed during DSG publication. It will be necessary to review its list and add or subtract sections with the current MasterFormat as specific project requirements.

Table 1

CSI Specifications List Revision 2020

CSI # Title

1 26 05 00 Common Work Results for Electrical

2 26 05 19 Low Voltage Electrical Power Conductors and Cables

3 26 05 26 Grounding and Bonding for Electrical Systems

4 26 05 29 Hanger Supports for Electrical Systems

5 26 05 33 Raceway and Boxes for Electrical Systems

6 26 05 36 Cable Tray for Electrical Systems

7 26 05 48 Vibration and Seismic Controls for Electrical Systems

8 26 05 53 Identification for Electrical Systems

9 26 08 13 Acceptance Testing

9 26 09 13 Electrical Power Monitoring

10 26 09 23 Lighting Control Devices

11 26 12 19 Pad-Mounted Transformers

12 26 13 13 Medium-Voltage Circuit Breaker Switchgear

13 26 13 19 Medium-Voltage Vacuum Interrupter Switchgear

14 26 22 00 Low-Voltage Transformers

15 26 24 13 Switchboards

16 26 24 16 Panelboards

17 26 24 19 Motor Control Center (MCC)

18 26 25 00 Enclosed Bus Assemblies

19 26 27 26 Wiring Devices

20 26 28 13 Fuses

21 26 28 16 Enclosed Switches and Circuit Breakers

22 26 29 13 Enclosed Controllers

23 26 29 23 Variable-Frequency Motor Controllers

24 26 32 13 Engine Generators

25 26 33 53 Static Uninterruptable Power Supply

26 26 36 00 Transfer Switches

27 26 41 13 Lightning Protection for Structures

28 26 43 13 Surge Protection Device (SPD)

29 26 51 00 Interior Lighting

30 26 56 00 Exterior Lighting

31 40 95 33.23

Fiber Optic Process Control Networks

SUMMARY

SHEET

Section Name: COMMON WORK RESULTS FOR

ELECTRICAL Section Number: 26 05 00

Prepared By: Alondra Mayol

Reviewed By: Ricardo Ramos

Date Issued: Oct 2024

Description: Design Standards and Guidelines (DSG)

Revision # Date Paragraph(s) Revised

1 10/7/2024 Entire document reformatted to Guidelines

PART 1 GENERAL

1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.02 SUMMARY

A. Section Includes:

1. Site information.

2. Electrical equipment coordination and installation.

3. Sleeves for raceways and cables.

4. Sleeve seals.

5. Grout.

6. Common electrical installation requirements.

1.03 DEFINITIONS

A. The following standard acronyms are used throughout the Bid Documents:

EPDM: Ethylene-propylene-diene terpolymer rubber.

NBR: Acrylonitrile-butadiene rubber.

1.04 SUBMITTALS

A. Product Data: For sleeve seals.

1.05 SITE INFORMATION

A. Location: C h r i s t i a n s t e d N a t i o n a l H i s t o r i c S i t e 2 1 0 0 C h u r c h S t r e e t # 1 0 0 S t . C r o i x , V I 0 0 8 2 0

B. Serving Utility: WAPA

C. Service Source: [Underground to utility-owned pad-mount transformer, 480/3/60, 400A

1.06 COORDINATION

A. Coordinate arrangement, mounting, and support of electrical equipment:

1. To allow replacement of damaged electrical components and system balance

2. To provide for ease of disconnecting the equipment with minimum interference to other installations.

3. To allow right-of-way for piping and conduit installed at required.

4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.

PART 2 PRODUCTS

2.01 SLEEVES FOR RACEWAYS AND CABLES

A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.

C. Sleeves for Rectangular Openings: Galvanized sheet steel.

1. Minimum Metal Thickness:

a. For sleeve cross-section rectangle perimeter less than 50 inches and no side more than 16 inches thickness shall be 0.052 inch.

b. For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches and 1 or more sides equal to, or more than, 16 inches, thickness shall be

0.138 inch.

2.02 SLEEVE SEALS

A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Advance Products & Systems, Inc.

b. Calpico, Inc.

c. Link Seal, Inc (SPU preferred).

d. Metraflex Co.

e. Pipeline Seal and Insulator, Inc.

2. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable.

3. Pressure Plates: Stainless steel. Include two for each sealing element.

4. Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates to sealing elements. Include one for each sealing element.

2.03 GROUT

A. Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for application and a 30-minute working time. Product: Jet Set.

PART 3 EXECUTION

3.01 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1, NEC, NFPA 70E, OSHA and SPU DSG.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right-of-Way: Give to piping systems installed at a required slope.

3.02 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.

B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.

C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.

E. Cut sleeves to length for mounting flush with both surfaces of walls.

F. Extend sleeves installed in floors 2 inches above finished floor level.

G. Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and raceway or cable, unless indicated otherwise.

H. Seal space outside of sleeves with grout for penetrations of concrete and masonry

1. Promptly pack grout solidly between sleeve and wall so no voids remain.

Tool exposed surfaces smooth; protect grout while curing.

I. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Division 07 Section "Joint Sealants."

J. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with firestop materials. Comply with requirements in Division 07 Section "Penetration Firestopping."

K. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.

L. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.

M. Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals.

3.03 SLEEVE-SEAL INSTALLATION

A. Install to seal exterior wall penetrations.

End of Section 26 05

PART 4 GENERAL

4.01 RELATED DOCUMENTS

4.02 SUMMARY

A. This Section includes the following:

1. Wires and cables rated 600 V and less.

2. Connectors, splices, and terminations rated 600 V and less.

4.03 SUBMITTALS

A. Product Data: For each type of product indicated. Under Part II, line-out products not offered for this job.

4.04 COORDINATION

A. Set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

PART 5 PRODUCTS

5.01 CONDUCTORS AND CABLES

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Alcan Products Corporation; Alcan Cable Division.

2. American Insulated Wire Corp.; a Leviton Company.

3. Belden.

4. General Cable Corporation.

5. Southwire Company.

B. Copper Conductors: Comply with NEMA WC 70.

C. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN.

5.02 CONNECTORS AND SPLICES

1. AFC Cable Systems, Inc.

2. Hubbell Power Systems, Inc.

3. O-Z/Gedney; EGS Electrical Group LLC.

4. 3M; Electrical Products Division.

5. Tyco Electronics Corp.

B. Description: UL listed and labeled factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.

PART 6 EXECUTION

6.01 CONDUCTOR MATERIAL APPLICATIONS

A. Feeders: Copper. Stranded for all feeder conductors.

B. Branch Circuits: Copper. Stranded for all branch circuits.

6.02 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE

APPLICATIONS AND WIRING METHODS

A. Service Entrance: Type XHHW, single conductors in raceway.

B. Exposed Feeders: Type XHHW, single conductors in raceway.

C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type XHHW single conductors in raceway.

D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type

XHHW, single conductors in raceway.

E. Exposed Branch Circuits, Including in Crawlspaces: Type XHHW, single conductors in raceway.

F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN, single conductors in raceway.

G. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground:

Type XHHW, single conductors in raceway.

H. Class 1 Control Circuits: Type THHN-THWN, in raceway.

I. Class 2 Control Circuits: Type THHN-THWN, in raceway.

6.03 INSTALLATION OF CONDUCTORS AND CABLES

A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.

Surface-mount on unfinished cement walls.

B. Use manufacturer-approved pulling compound or lubricant where necessary;

compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

E. Support cables according to Division 26 Section "Hangers and Supports for Electrical Systems."

F. Identify and color-code conductors and cables according to Division 26 Section

"Identification for Electrical Systems."

6.04 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

B. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors. No aluminum conductors are allowed.

C. Wiring at Outlets: Install conductor at each outlet, with at least 6-inches of slack.

6.05 FIELD QUALITY CONTROL

A. Testing Agency: Contractor to perform tests and inspections and prepare test reports.

B. Perform tests and inspections and prepare test reports.

C. Tests and Inspections:

1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each splice in cables and conductors No. 3 AWG and larger. Remove box and equipment covers so splices are accessible to portable scanner.

a. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each splice 11 months after date of Substantial Completion.

b. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

c. Record of Infrared Scanning: Prepare a certified report that identifies splices checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

D. Test Reports: Prepare a written report in conformance with NETA specifications to record the following:

1. Model, serial number and latest calibration of each instrument used.

2. Test procedures used.

3. Test results that comply with requirements.

4. Test results that do not comply with requirements and corrective action taken to achieve compliance with requirements.

5. Legibly sign, print name, and date each sheet.

E. Remove and replace malfunctioning units and retest as specified above.

PART 7 GENERAL

7.01 RELATED DOCUMENTS

7.02 SUMMARY

A. This Section includes methods and materials for grounding systems and equipment.

7.03 SUBMITTALS

A. Product Data: For each type of product indicated. In Part 2 line-out items not offered for this project.

B. Other Informational Submittals: Plans showing dimensioned as-built locations of grounding features specified in Part 3 "Field Quality Control" Article, including the following:

1. Test wells.

2. Ground rods.

3. Ground rings.

4. Grounding arrangements and connections for separately derived systems.

C. Grounding for sensitive electronic equipment.

D. Operation and Maintenance Data: For grounding to include the following in emergency, operation, and maintenance manuals:

1. Instructions for periodic testing and inspection of grounding features at test wells based on NETA MTS.

a. Tests shall be to determine if ground resistance or impedance values remain within specified maximums, and instructions shall recommend corrective action if they do not.

b. Include recommended testing intervals and maximum values.

7.04 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with UL 467 for grounding and bonding materials and equipment.

PART 8 PRODUCTS

8.01 CONDUCTORS

A. Insulated Conductors: Copper wire or cable insulated for 600V unless otherwise required by applicable Code or authorities having jurisdiction.

B. Bare Copper Conductors:

1. Solid Conductors: ASTM B 3.

2. Stranded Conductors: ASTM B 8.

3. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4-in in diameter.

4. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.

5. Bonding Jumper: Copper tape, braided conductors, terminated with copper ferrules; 1-5/8-in wide and 1/16-in thick.

C. Bare Grounding Conductor and Conductor Protector for Wood Poles:

1. No. 4 AWG minimum, soft-drawn copper.

2. Conductor Protector: Half-round PVC or wood molding. If wood, use pressure-treated fir or cypress or cedar.

D. Grounding Bus: Rectangular bars of annealed copper, 1/4-in x 2-in in cross section, unless otherwise indicated; with insulators.

8.02 CONNECTORS

A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having jurisdiction for applications in which used, and for specific types, sizes, and combinations of conductors and other items connected.

B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type, with at least two bolts.

1. Pipe Connectors: Clamp type, sized for pipe.

C. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.

8.03 GROUNDING ELECTRODES

A. Ground Rods: Copper-clad steel, 3/4-in x 10-ft.

1. Termination: Factory-attached No. 4/0 AWG bare conductor at least 48-in long or UL approved mechanical ground rod connector.

2. Backfill Material: Electrode manufacturer's recommended material.

PART 9 EXECUTION

9.01 APPLICATIONS

A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger, unless otherwise indicated.

B. Underground Grounding Conductors: Install bare copper conductor, No. 2/0 AWG minimum.

1. Bury at least 24-in below grade.

2. Duct-Bank Grounding Conductor: Bury 12-in above duct bank when indicated as part of duct-bank installation.

C. Isolated Grounding Conductors: Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.

D. Grounding Bus: Install in electrical and telephone equipment rooms, in rooms housing service equipment, and elsewhere as indicated.

1. Install bus on insulated spacers 1-in, minimum, from wall 6-in above finished floor, unless otherwise indicated.

2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, down to specified height above floor, and connect to horizontal bus.

E. Conductor Terminations and Connections:

1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.

2. Underground Connections: Welded connectors, except at test wells and as otherwise indicated.

3. Connections to Ground Rods at Test Wells: Bolted connectors.

F. Connections to Structural Steel: Welded connectors.

9.02 EQUIPMENT GROUNDING

A. Install insulated equipment grounding conductors with all feeders and branch circuits.

B. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:

1. Feeders and branch circuits.

2. Lighting circuits.

3. Receptacle circuits.

4. Single-phase motor and appliance branch circuits.

5. Three-phase motor and appliance branch circuits.

6. Flexible raceway runs.

7. Armored and metal-clad cable runs.

C. Computer and Rack-Mounted Electronic Equipment Circuits: Install insulated equipment grounding conductor in branch-circuit runs from equipment-area power panels and power-distribution units.

D. Signal and Communication Equipment: For telephone, alarm, voice and data, and other communication equipment, provide No. 4 AWG minimum insulated grounding conductor in raceway from grounding electrode system to each service location, terminal cabinet, wiring closet, and central equipment location.

1. Service and Central Equipment Locations and Wiring Closets: Terminate grounding conductor on a 1/4-in x 2-in x 12-in grounding bus.

2. Terminal Cabinets: Terminate grounding conductor on cabinet grounding terminal.

E. Metal and Wood Poles Supporting Outdoor Lighting Fixtures: Install grounding electrode and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors.

9.03 INSTALLATION

A. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

B. Common Ground Bonding with Lightning Protection System: Comply with NFPA 780 and UL96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit.

C. Ground Rods: Drive rods until tops are 2-in below finished floor or final grade, unless

1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating, if any.

2. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor.

D. Test Wells: Ground rod driven through drilled hole in bottom of handhole. Handholes are specified in Division 26 Section "Underground Ducts and Raceways for Electrical Systems," and shall be at least 12-in deep, with cover.

1. Test Wells: Install at least one test well for each service, unless otherwise indicated. Install at the ground rod electrically closest to service entrance. Set top of test well flush with finished grade or floor.

E. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance, except where routed through short lengths of conduit.

1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.

2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports:

Install so vibration is not transmitted to rigidly mounted equipment.

3. Use exothermic-welded connectors for outdoor locations, but if a disconnect-type connection is required, use a bolted clamp.

F. Grounding and Bonding for Piping:

1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes, using a bolted clamp connector or by bolting a lug-type connector to a pipe flange, using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end. Comply with USVI Electrical Code Supplement: see 250.104(E).

2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.

3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.

G. Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of associated fans, blowers, electric heaters, and air cleaners. Install bonding jumper to bond across flexible duct connections to achieve continuity.

H. Grounding for Steel Building Structure: Install a driven ground rod at base of each corner column and at intermediate exterior columns at distances not more than 60-ft apart.

I. Ground Ring: Install a grounding conductor, electrically connected to each building structure ground rod and to each steel column, extending around the perimeter of building.

1. Install tinned-copper conductor not less than No. 2/0 AWG for ground ring and for taps to building steel.

2. Bury ground ring not less than 24-in from building foundation.

J. Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70, using a minimum of 20-ft of bare copper conductor not smaller than No. 4 AWG.

1. If concrete foundation is less than 20-ft long, coil excess conductor within base of foundation.

2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Extend grounding conductor below grade and connect to building grounding grid or to grounding electrode external to concrete.

9.04 FIELD QUALITY CONTROL

A. Perform the following tests and inspections and prepare test reports:

1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.

2. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, and at individual ground rods. Make tests at ground rods before any conductors are connected.

a. Measure ground resistance not less than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.

b. Perform tests by fall-of-potential method according to IEEE 81.

3. Prepare dimensioned drawings locating each test well, ground rod and ground rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.

B. Report measured ground resistances that exceed the following values:

1. Power and Lighting Equipment or System with Capacity 500 kVA and Less:

10 ohms.

2. Power and Lighting Equipment or System with Capacity 500 to 1000 kVA:

5 ohms.

3. Power and Lighting Equipment or System with Capacity More Than 1000 kVA:

3 ohms.

4. Power Distribution Units or Panelboards Serving Electronic Equipment: 3 ohm(s). C. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify project manager promptly and include recommendations to reduce ground resistance.

SUMMARY

SHEET

PART 10 GENERAL

10.01 RELATED DOCUMENTS

10.02 SUMMARY

1. Hangers and supports for electrical equipment and systems.

B. Related Sections include the following:

1. Division 6 Section 26 05 48, "Vibration And Seismic Controls For Electrical Systems" for products and installation requirements necessary for compliance with seismic criteria.

10.03 DEFINITIONS

A. RMC: Rigid metal conduit.

10.04 PERFORMANCE REQUIREMENTS

A. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.

10.05 SUBMITTALS

A. Product Data: For the following:

1. Steel slotted support systems (Electric strut).

B. Shop Drawings: Show fabrication and installation details and include calculations for

1. Trapeze hangers. Include Product Data for components.

2. Steel slotted channel systems. Include Product Data for components.

3. Equipment supports.

10.06 QUALITY ASSURANCE

A. Comply with NFPA 70.

PART 11 PRODUCTS

11.01 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly.

1. Available Manufacturers: Subject to compliance with requirements, manufacturers

a. Allied Tube & Conduit.

b. Cooper B-Line, Inc.; a division of Cooper Industries.

c. ERICO International Corporation.

d. GS Metals Corp.

e. Thomas & Betts Corporation.

f. Unistrut; Tyco International, Ltd.

g. Wesanco, Inc.

2. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to

MFMA-4.

a. Channel Dimensions: Selected for applicable load criteria but in no case less than 1-5/8-in.

3. Fittings and Accessories: Products of channel and angle manufacturer and designed for use with those items.

4. Fitting and Accessory Materials: Same as channels and angles, except metal items may be stainless steel.

B. Raceway and Cable Supports: As described in NECA 1 and NECA 101.

C. Conduit and Cable Support Devices: Mallablei-iron hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

D. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported.

Body shall be malleable iron.

E. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

F. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:

1. Epoxy and powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.

a. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1) Hilti Inc.

2) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.

3) MKT Fastening, LLC.

4) Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.

2. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to

MSS Type 18; complying with MFMA-4 or MSS SP-58.

3. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for attached structural element.

4. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM

A 325.

5. Toggle Bolts: All-steel springhead type.

6. Hanger Rods: Threaded steel, minimum 3/8-in dia - must be double-nutted.

PART 12 EXECUTION

12.01 APPLICATION

A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical equipment and systems except if requirements in this Section are stricter.

B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for RMC as scheduled in NECA 1, where its Table 1 lists maximum spacings less than stated in NFPA 70. Minimum rod size shall be 3/8-in in diameter - must be double-nutted.

C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

D. Secure raceways and cables to these supports with single-bolt conduit clamps.

12.02 SUPPORT INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this Article.

B. Raceway Support Methods: In addition to methods described in NECA 1, RMC may be supported by openings through structure members, as permitted in NFPA 70.

C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200lb.

D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

1. To Wood: Fasten with lag screws or through bolts.

2. To New Concrete: Bolt to concrete inserts.

3. To Masonry: Epoxy anchors.

4. To Existing Concrete: Epoxy anchors.

5. Instead of expansion anchors, powder-actuated driven threaded studs provided with lock washers and nuts may be used in existing standard-weight concrete 4-in thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4-in thick.

6. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that meet seismic-restraint strength and anchorage requirements.

E. Drill holes for epoxy anchors in concrete at locations and to depths that avoid reinforcing bars.

End of Section 26 05 29

Design of Electrical Components – Christiansted National Historic Site

PART 13 GENERAL

13.01 RELATED DOCUMENTS

13.02 SUMMARY

A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.

NOTE: A paragraph on underground distribution was deleted.

13.03 DEFINITIONS

A. RMC: Rigid metal conduit.

1. Al: Aluminum.

2. GRS: Galvanized rigid steel

B. PVC-GRS: PVC coated galvanized rigid steel

C. IMC: Intermediate metal conduit.

D. EMT: electrical metallic tubing

E. LFMC: Liquidtight flexible metal conduit.

13.04 SUBMITTALS

A. Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

B. Shop Drawings: For the following raceway components. Include plans, elevations, sections, details, and attachments to other work.

1. Custom enclosures and cabinets.

2. For handholes and boxes for underground wiring, including the following:

a. Duct entry provisions, including locations and duct sizes.

1) Frame and cover design.

2) Grounding details.

3) Dimensioned locations of cable rack inserts, pulling and lifting irons, and eye-bolts.

C. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, based on input from installers of the items involved:

1. Structural members in the paths of conduit groups with common supports.

2. Process piping, HVAC and plumbing items and architectural features in the paths of conduit groups with common supports.

D. Manufacturer Seismic Qualification Certification: Submit certification that enclosures and cabinets and their mounting provisions, including those for internal components, will withstand seismic forces defined in Division 26 Section 26 05 48,"Vibration and Seismic Controls for Electrical Systems." Include the following:

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

a. The term "withstand" means "the cabinet or enclosure will remain in place without separation of any parts when subjected to the seismic forces specified and the unit will retain its enclosure characteristics, including its interior accessibility, after the seismic event."

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

E. Qualification Data: For professional engineer and testing agency.

F. Source quality-control test reports.

13.05 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in

B. Comply with NFPA 70.

PART 14 PRODUCTS

14.01 METAL CONDUIT AND TUBING

1. AFC Cable Systems, Inc.

2. Alflex Inc.

3. Allied Tube & Conduit; a Tyco International Ltd. Co.

4. Anamet Electrical, Inc.; Anaconda Metal Hose.

5. Electri-Flex Co.

6. Manhattan/CDT/Cole-Flex.

7. Maverick Tube Corporation.

8. Ocal.

9. O-Z Gedney; a unit of General Signal.

10. Robroy.

11. Wheatland Tube Company.

B. PVC-Coated Steel Conduit: PVC-coated rigid steel conduit.

1. Comply with NEMA RN 1.

2. Coating Thickness: 0.040 inch minimum.

C. Rigid Steel Conduit: ANSI C80.1.

D. IMC: ANSI C80.6.

E. FMC: Zinc-coated steel.

F. LFMC: Flexible steel conduit with PVC jacket.

G. Fittings for Conduit (Including all Types and Liquidtight): NEMA FB 1; listed for type and size raceway with which used, and for application and environment in which installed.

H. Joint Compound for Rigid Steel Conduit: Listed for use in cable connector assemblies, and compounded for use to lubricate and protect threaded raceway joints from corrosion and enhance their conductivity.

14.02 METAL WIREWAYS

1. Cooper B-Line, Inc.

2. Hoffman.

3. Square D; Schneider Electric.

B. Description: Sheet metal sized and shaped as indicated, NEMA 250, Type 12, unless

C. Fittings and Accessories: Include couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

D. Wireway Covers: Hinged type.

1. Finish: Manufacturer's standard enamel finish.

14.03 BOXES, ENCLOSURES, AND CABINETS

1. Cooper Crouse-Hinds; Div. of Cooper Industries, Inc.

2. EGS/Appleton Electric.

3. Erickson Electrical Equipment Company.

4. Hoffman.

5. Hubbell Incorporated; Killark Electric Manufacturing Co. Division.

6. O-Z/Gedney; a unit of General Signal.

7. RACO; a Hubbell Company.

8. Robroy Industries, Inc.; Enclosure Division.

9. Thomas & Betts Corporation.

10. Walker Systems, Inc.; Wiremold Company (The).

11. Woodhead, Daniel Company; Woodhead Industries, Inc. Subsidiary.

B. Cast-Metal Outlet and Device Boxes: NEMA FB 1, ferrous alloy, Type FD, with gasketed cover.

C. Cast-Metal Access, Pull, and Junction Boxes: NEMA FB 1, cast iron with gasketed cover.

D. Hinged-Cover Enclosures: NEMA 250, Type 12, with continuous-hinge cover with flush latch, unless otherwise indicated.

1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.

E. Cabinets:

1. NEMA 250, Type 12, galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel.

2. Hinged door in front cover with flush latch and concealed hinge.

3. Key latch to match panelboards.

4. Metal barriers to separate wiring of different systems and voltage.

5. Accessory feet where required for freestanding equipment.

14.04 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING

A. Description: Comply with SCTE 77.

1. Color of Frame and Cover: Gray.

2. Configuration: Units shall be designed for flush burial and have open bottom, unless otherwise indicated.

3. Cover: Weatherproof, secured by tamper-resistant locking devices and having structural load rating consistent with enclosure.

4. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.

5. Cover Legend: Molded lettering, "ELECTRIC."

B. Polymer-Concrete Handholes and Boxes with Polymer-Concrete Cover: Molded of sand and aggregate, bound together with polymer resin, and reinforced with steel or fiberglass or a combination of the two.

a. Armorcast Products Company.

b. Carson Industries LLC.

c. CDR Systems Corporation.

d. NewBasis.

e. Utility Vault

C. Fiberglass Handholes and Boxes with Polymer-Concrete Frame and Cover: Sheet-molded, fiberglass-reinforced, polyester-resin enclosure joined to polymer-concrete top ring or frame.

a. Armorcast Products Company.

b. Carson Industries LLC.

c. Christy Concrete Products.

d. Synertech Moulded Products, Inc.; a division of Oldcastle Precast.

D. Fiberglass Handholes and Boxes: Molded of fiberglass-reinforced polyester resin, with covers of polymer concrete.

a. Carson Industries LLC.

b. Christy Concrete Products.

c. Nordic Fiberglass, Inc.

14.05 SLEEVES FOR RACEWAYS

A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

14.06 SLEEVE SEALS

1. Advance Products & Systems, Inc.

2. Calpico, Inc.

3. Link Seal

4. Metraflex Co.

5. Pipeline Seal and Insulator, Inc.

B. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and cable.

1. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable.

2. Pressure Plates: Stainless steel. Include two for each sealing element.

3. Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates to sealing elements. Include one for each sealing element.

PART 15 EXECUTION

15.01 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below, unless otherwise indicated:

1. Exposed Conduit: Rigid steel conduit.

2. Concealed Conduit, Aboveground: Rigid steel conduit.

3. Underground Conduit: RNC, Type EPC-80-PVC, direct buried.

4. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.

5. Boxes and Enclosures, Aboveground: NEMA 250, Type 12.

6. Application of Handholes and Boxes for Underground Wiring:

a. Handholes and Pull Boxes in Driveway, Parking Lot, and Off-Roadway

Locations, Subject to Occasional, Nondeliberate Loading by Heavy Vehicles:

Fiberglass enclosures with polymer-concrete frame and cover, SCTE 77, Tier 15 structural load rating.

b. Handholes and Pull Boxes in Sidewalk and Similar Applications with a Safety

Factor for Nondeliberate Loading by Vehicles: Heavy-duty fiberglass units with polymer-concrete frame and cover, SCTE 77, Tier 8 structural load rating.

c. Handholes and Pull Boxes Subject to Light-Duty Pedestrian Traffic Only:

Fiberglass-reinforced polyester resin, structurally tested according to SCTE 77 with 3,000-lbf vertical loading.

B. Comply with the following indoor applications, unless otherwise indicated:

1. Exposed, Not Subject to Physical Damage: RMC.

2. Exposed, Not Subject to Severe Physical Damage: RMC.

3. Exposed and Subject to Severe Physical Damage: Rigid steel conduit. Includes raceways in the following locations:

a. Process areas.

b. Loading dock.

c. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units.

d. Mechanical rooms.

4. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.

5. Damp or Wet Locations: Rigid steel conduit.

6. Boxes and Enclosures: NEMA 250, Type 12.

C. Minimum Raceway Size: 3/4-in trade size.

D. Raceway Fittings: Compatible with raceways and suitable for use and location.

15.02 INSTALLATION

A. Comply with NECA 1 for installation requirements applicable to products specified in Part 2 except where requirements on Drawings or in this Article are stricter.

B. Keep raceways at least 6-in away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping. Do not interfere with operating and maintenance access to process piping devices, as valves, strainers, gages, etc.

C. Complete raceway installation before starting conductor installation.

D. Support raceways as specified in Division 26 Section 26 05 29, "Hangers and Supports for Electrical Systems."

E. Group conduit in parallel runs where practical, and use conduit rack constructed of steel channel with conduit straps or clamps. Provide space for 25 percent additional conduit. Bends in parallel conduit runs must be concentric. All conduits must be run straight and true.

F. Arrange stub-ups so curved portions of bends are not visible above the finished slab.

G. Install no more than the equivalent of three 90-degree bends in any conduit run without a pullbox.

H. Raceways Embedded in Slabs:

1. Minimum size conduit larger than 1-in trade size, parallel or at right angles to main reinforcement. Where at right angles to reinforcement, place conduit close to slab support.

2. Arrange raceways to cross building expansion joints at right angles with expansion fittings.

3. Change from PVC to rigid steel conduit before rising above the floor.

I. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions:

Apply listed compound to threads of raceway and fittings before making up joints.

Follow compound manufacturer's written instructions. Provide MSDS for any compound used.

J. Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings to protect conductors, including conductors smaller than No. 4 AWG.

K. Install raceway sealing fittings at suitable, approved, and accessible locations and fill them with listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway sealing fittings at the following points:

1. Where conduits entering or leaving Class I, Div 1 or Class I, Div 2 areas.

2. Where otherwise required by NFPA 70.

L. Flexible Conduit Connections: Use maximum of 72-in of liquid tight flexible conduit for equipment subject to vibration, noise transmission, or movement; and for transformers and motors.

15.03 INSTALLATION OF UNDERGROUND CONDUIT

A. Direct-Buried Conduit:

1. Excavate trench bottom to provide firm and uniform support for conduit. Prepare trench bottom as specified in Division 31 Section "Earth Moving" for pipe less than 6-in in nominal diameter.

2. Install backfill as specified in Division 31 Section "Earth Moving."

3. After installing conduit, backfill and compact. Start at tie-in point, and work toward end of conduit run, leaving conduit at end of run free to move with expansion and contraction as temperature changes during this process. Firmly hand tamp backfill around conduit to provide maximum supporting strength. After placing controlled backfill to within 12-in of finished grade, make final conduit connection at end of run and complete backfilling with normal compaction as specified in Division 31 Section "Earth Moving."

4. Install manufactured duct elbows for stub-ups at poles and equipment and at building entrances through the floor, unless otherwise indicated. Encase elbows for stub-up ducts throughout the length of the elbow.

5. Install manufactured rigid steel conduit elbows for stub-ups at poles and equipment and at building entrances through the floor.

a. Couple steel conduits to ducts with adapters designed for this purpose, and encase coupling with 3-in of concrete.

b. For stub-ups at equipment mounted on outdoor concrete bases, extend steel conduit horizontally a minimum of 60-in from edge of equipment pad or foundation. Install insulated grounding bushings on terminations at equipment.

6. Warning tape: Bury detectable warning tape 12-in above direct-buried conduits.

15.04 INSTALLATION OF UNDERGROUND HANDHOLES AND BOXES

A. Install handholes and boxes level and plumb and with orientation and depth coordinated with connecting conduits to minimize bends and deflections required for proper entrances.

B. Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from 1/2-in sieve to No. 4 sieve and compacted to same density as adjacent undisturbed earth.

C. Install removable hardware, including pulling eyes, cable stanchions, cable arms, and insulators, as required for installation and support of cables and conductors and as indicated. Select arm lengths to be long enough to provide spare space for future cables, but short enough to preserve adequate working clearances in the enclosure.

D. Field-cut openings for conduits according to enclosure manufacturer's written instructions. Cut wall of enclosure with a tool designed for material to be cut. Size holes for terminating fittings to be used, and seal around penetrations after fittings are installed.

15.05 PROTECTION

A. Provide final protection and maintain conditions that ensure coatings, finishes, and cabinets are without damage or deterioration at time of Substantial Completion.

1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.

PART 16 GENERAL

16.01 RELATED DOCUMENTS

16.02 SUMMARY

A. This Section includes steel cable trays and accessories.

16.03 SUBMITTALS

A. Product Data: Include data indicating dimensions and finishes for each type of cable tray indicated.

B. Shop Drawings: For each type of cable tray.

1. Show fabrication and installation details of cable tray, including plans, elevations, and sections of components and attachments to other construction elements.

Designate components and accessories, including clamps, brackets, hanger rods, splice-plate connectors, expansion-joint assemblies, straight lengths, and fittings.

2. Seismic-Restraint Details: Signed and sealed by a qualified professional engineer, licensed in the state where Project is located, who is responsible for their preparation.

a. Design Calculations: Calculate requirements for selecting seismic restraints.

b. Detail fabrication, including anchorages and attachments to structure and to supported cable trays.

C. Coordination Drawings: Floor plans and sections, drawn to scale. Include scaled cable tray layout and relationships between components and adjacent structural, electrical, and mechanical elements. Show the following:

1. Vertical and horizontal offsets and transitions.

2. Clearances for access above and to side of cable trays.

3. Vertical elevation of cable trays above the floor or bottom of ceiling structure.

D. Field quality-control reports.

E. Operation and Maintenance Data: For cable trays to include in emergency, operation, and maintenance manuals.

16.04 QUALITY ASSURANCE

A. Source Limitations: Obtain cable tray components through one source from a single manufacturer.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in

C. Comply with NFPA 70.

16.05 DELIVERY, STORAGE, AND HANDLING

A. Store indoors to prevent water or other foreign materials from staining or adhering to cable tray. Unpack and dry wet materials before storage.

PART 17 PRODUCTS

17.01 MANUFACTURERS

1. Chalfant Manufacturing Company.

2. Cooper B-Line, Inc.

3. Cope, T. J., Inc.; a subsidiary of Allied Tube & Conduit.

4. GS Metals Corp.; GLOBETRAY Products.

5. MONO-SYSTEMS, Inc.

6. MPHusky.

7. PW Industries.

17.02 MATERIALS AND FINISHES

A. Cable Trays, Fittings, and Accessories: Steel, complying with NEMA VE 1.

B.

1. Electrogalvanized before fabrication, complying with ASTM B 633; with hardware galvanized according to ASTM B 633.

B. Sizes and Configurations: Refer to the Cable Tray Schedule on Drawings for specific requirements for types, materials, sizes, and configurations.

1. Center-hanger supports may be used…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .