Specification_Section_12_64_13.pdf

PDF 364 KB Posted

Attached to
FPCM-COR-BOOTHS-RS Privacy Booths
Solicitation number
0000040482
Issued by
Kings County, California

About this file

This is a specification section for VEST Privacy Booths from the California Department of Corrections and Rehabilitation (CDCR), detailing technical requirements for prefabricated single-occupant video conference booths with integrated lighting, ventilation, and communications capabilities. The specification outlines two booth sizes: a standard interior dimension of 35" x 35" x 84" and an accessible ADA-compliant model measuring 42" x 84" x 84". The specification identifies three acceptable manufacturers as the basis of design: PoPS (Pillar of Public Safety) in Chicago, Illinois; Cubicall in North Las Vegas, Nevada; and SpaceWorx in Laurel, Maryland. The document requires comprehensive submittals including product data, shop drawings with seismic anchor plans, lighting and communications diagrams, and 3D isometric images. A preinstallation coordination meeting with the CDCR Representative is mandated. No specific project quantities, response dates, award dates, or contract term information is provided in this technical specification document.

The specification establishes performance standards rather than pricing terms, requiring steel structures to carry a minimum 10-year manufacturer's warranty and all other components to have a minimum 1-year warranty. All exposed fasteners must be stainless steel and tamperproof in accordance with security standards. The booths must meet fire safety standards per ASTM E84 with flame spread ratings not exceeding 25 and smoke density not exceeding 450, and achieve a minimum STC rating of 35dB acoustic performance per ASTM E90. Detailed requirements are specified for walls, ceilings, doors, glazing, hardware, exhaust systems, LED lighting, ethernet connectivity, electrical receptacles, and videoconference device mounting. The specification permits substitutions for manufacturers not listed, contingent upon compliance with Section 01 25 00 Substitution Procedures, and requires all installations to be completed level and in accordance with CDCR Representative approval.

View the file

Other files

File Type Posted
12_-_FPCM-COR-BOOTHS-RS-ADDENDUM__1.pdf PDF
Invitation_for_Bid__COR_Privacy_Booths.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A/E Firm Name Institution Name A/E Project Number Project Name Bid Package ## – If Applicable

VEST PRIVACY BOOTHS

20260630 12 64 13 – 1 [20260921]

SECTION 12 64 13

VEST PRIVACY BOOTHS

PART 1 GENERAL

1.1 SUMMARY

A. Section Includes:

1. Prefabricated interior free-standing single-occupant booth.

1.2 REFERENCES

A. ASTM E84 – Test Method for Surface Burning Characteristics of Building Materials.

B. ASTM E90 – Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements.

C. ASTM D3935 – Standard Specification for Polycarbonate (PC) Unfilled and Reinforced Material.

D. ASTM C1349 – Standard Specification for Architectural Flat Glass Clad Polycarbonate.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 00 – Submittal Procedures and Section 01 33 23 – Shop Drawings, Product Data, and Samples.

B. Product Data:

1. Product data for products and materials indicated. Product data to include any available brochures and a technical product information sheet listing key features such as model number, base features, and optional accessories.

2. Manufacturer’s technical bulletins and installation/application instructions.

C. Shop Drawings: Include isometric and 3D images, plans, elevations, sections, details, accessories, electrical service connection, and fastening and anchorage details.

1. Seismic Anchor Plans: Submit seismic anchor plans and templates. Include location, diameter, and projection of anchor connections required to attach booths to substrate.

2. Lighting: Drawings, Diagrams, and Supporting Documents for Luminaires:

a. Include plans, elevations, sections, and mounting and attachment details.

b. Include details of luminaire assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

c. Include diagrams for lighting, power, signal, and control wiring.

3. Communications: Drawings, Diagrams, and Supporting Documents for Communications:

a. Include plans, elevations, sections, and mounting and attachment details.

b. Include points of connection to web-based audio/visual communication equipment and devices.

4. Isometric Drawings: To aid the Owner in visualizing the proposed completed booth, provide isometric and/or computer-generated 3D image(s) of proposed product.

20260630 12 64 13 – 2 [20260921]

D. Samples:

1. Submit samples of prefinished metal and panel finishes in each selected color/finish.

1.4 COORDINATION

A. Coordinate Preinstallation Coordination Meeting with CDCR Representative.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Deliver, store, and handle packaged materials in the manufacturer’s original, sealed containers, each clearly identified with the manufacturer’s name, and name and type of product.

B. Store materials subject to damage by dirt and moisture in a clean, dry location, off the ground, and suitably protected.

1.6 WARRANTY

A. Steel Structure: Minimum 10-year manufacturer’s warranty.

B. All other components: Minimum 1-year manufacturer’s warranty.

PART 2 PRODUCTS

2.1 GENERAL

A. Prefabricated single occupant video conference booth, with built-in lighting, ventilation, and communications.

1. Size:

a. Standard: minimum 35” x 35” x 84” interior.

b. Accessible: minimum 42” x 84” x 84” interior.

2.2 BASIS OF DESIGN PRODUCT

A. Acceptable Manufacturers/Products – Basis of Design and subject to compliance with requirements as indicated in this specification as follows:

PoPS – Pillar of Public Safety 333 N. Green, 8th floor Chicago, Il 60607 Sales@popsbooth.com

Cubicall 580 W. Cheyenne, Suite 100 North Las Vegas, NV 89030 anthony@cubicallbooth.com

SpaceWorx 14250 Cherry Lane Ct.

Laurel, MD 20707 info@spaceworx.us

20260630 12 64 13 – 3 [20260921]

1. For manufacturers not listed, comply with substitution requirements in Section 01 25 00

– Substitution Procedures.

2.3 FASTENERS, SCREWS, AND BOLTS

1. All Exposed Fasteners: Stainless steel, tamperproof in accordance with Section 05 05 53

– Security Metal Fastenings.

2.4 CASTERS, LEVELING FEET, AND SEISMIC RESTRAINT

A. Provide casters, leveling feet, and seismic restraint conforming to the following:

1. Leveling casters: 800 pounds minimum load capacity; Atlas Casters Model 1000 Series

#LC1030CS-SB-PHN or approved equal.

2. Leveling feet: 1,000 pounds minimum load capacity; stainless steel foot; Atlas Casters

#LV6311-SS-SS or approved equal.

3. Seismic restraint: Stainless steel compatible with leveling feet; Atlas Casters #XA-

LVRT63 or approved equal.

4. Securely attach booth to floor to resist overturning by seismic activity and vandalism using fasteners recommended by booth manufacturer and as specified herein.

2.5 WALLS

A. General: Prefabricated wall panels comprised of cold-rolled steel framing, prefinished interior sheet metal skin covering acoustic lining, minimum 5/8-inch plywood core, and prefinished exterior sheet metal skin.

1. Interior Wall Finish: Minimum 16-gauge steel with perforated hole spacing of 3/16-inch diameter holes at 9/32 inch on center. Omit gaps (anti-ligature) or anywhere contraband can be slipped into/hidden. Removable to facilitate cleaning.

a. Color: Prefinished; white or off-white as selected by the CDCR Representative from the manufacturer’s standard range.

2. Exterior Wall Finish: Minimum 18-gauge steel with smooth surface. Omit gaps (anti-ligature) or anywhere contraband can be slipped into/hidden.

a. Color: Prefinished [Match CDCR Representative’s sample.][Selected by the CDCR

Representative from the manufacturer’s standard range.]

3. Flame spread rating of materials must not exceed 25, smoke density must not exceed 450 per ASTM E84.

4. Acoustic Performance: Wall assembly must achieve minimum STC rating of 35dB per

ASTM E90[, not including any applied acoustic treatment].

2.6 CEILING/ROOF

A. General: Prefabricated ceiling/roof panel comprised of cold-rolled steel framing, prefinished interior sheet metal skin covering acoustic lining, and minimum 5/8-inch plywood panel/roof.

1. Ceiling Finish: Minimum 16-gauge steel with perforated hole spacing of 3/16-inch diameter holes at 9/32 inch on center. Omit gaps (anti-ligature) or anywhere contraband can be slipped into/hidden. Removable to facilitate cleaning.

a. Color: Prefinished to match walls.

2. Flame spread rating of materials must not exceed 25, smoke density must not exceed 450 per ASTM E84.

3. Acoustic Performance: Ceiling assembly must achieve minimum STC rating of 35dB per ASTM E90[, not including any applied acoustic treatment].

20260630 12 64 13 – 4 [20260921]

2.7 FLOORS

A. General: Design to support minimum 40 pounds per square foot live load.

B. Finish: Rubber tile or sheet fully adhered to substrate.

2.8 STEEL DOORS AND SIDELITES

A. References:

1. American National Standards Institute (ANSI) / Steel Door Institute (D-SDI):

a. ANSI/SDI A250.8 – Specifications for Standard Steel Doors &Frames (SDI-100)

b. ANSI/SDI 250.10 – Test Procedure and Acceptance Criteria for Prime Painted Steel

Surfaces for Steel Doors and Frames.

2. ASTM International (formerly American Society for Testing and Materials) (ASTM):

a. ASTM A653 – Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.

3. American Welding Society (AWS):

a. AWS D1.1 – Standard Welding Code – Steel.

b. AWS D1.3 – Standard Welding Code – Sheet Steel.

4. Certification Listings; Intertek Testing Services NA, Inc.

5. Hollow Metal Manufacturers Association (HMMA).

6. Steel Door Institute (SDI):

a. ANSI/SDI-A250.8 – Specifications for Standard Steel Doors and Frames (SDI-100).

7. The Society for Protective Coatings (SSPC) (also known as The Association for Materials

Protection.

B. Manufactured Units:

1. Comply with ANSI/SDI A250.8.

2. Provide glazing stops and gaskets at glazed openings.

a. Typical: Unless noted or detailed otherwise, provide integral stop at interior face;

loose (removable) stops at exterior face, for shop assembly with countersunk tamperproof fasteners.

b. Removable Stops: 3/4-inch deep typical unless noted otherwise. Finish to match steel frames.

3. Provide reinforcing for all surface-applied hardware.

C. Steel Doors:

1. Dimensions: 1-3/4 inches thick x 3 feet wide x 7 feet high.

2. Door Type: Outward-swinging with full-height glazing, stile and rail construction with 3-inch stiles, 6-inch mid-rail, 12-inch bottom rail, and 3-inch top rail.

3. Doors: ANSI/SDI A250.8 Level 3, Physical Performance Level A, Model 3 stile and rail, extra heavy-duty, face sheet minimum 16-gauge cold-rolled steel.

4. Finish: Factory finished powder coated.

D. Steel Frames:

1. Integral panel welded type with mitered corners.

2. Door Frames: ANSI/SDI A250.8 Level 3, minimum 16-gauge cold-rolled steel, full profile weld.

3. Finish: To match door.

20260630 12 64 13 – 5 [20260921]

4. Material: Minimum 16-gauge sheet steel, cold-rolled, free from scale, pitting and surface defects.

5. Hardware Reinforcement:

a. Provide concealed reinforcement of sheet or bar steel to receive hardware. Drill and tap to template requirements for field installation.

b. Hinge Plates: 7-gauge, 1-1/4 inches x 10 inches minimum size.

c. Reinforcement for Surface Applied Hardware: Minimum 10-gauge.

d. Other Items: Conform to HMMA Standards.

E. Orientation: Optional lefthand/righthand door swing, monitor location, and sidelight for ADA models orientation/layout must be available for selection by CDCR Representative, based on specific location(s) of installation.

2.9 GLAZING

A. Minimum 15/32-inch monolithic abrasion-resistant clear non-reflective polycarbonate sheet glazing glass per ASTM C1349.

1. Grade 4 per ASTM F1915.

2. UV resistant.

3. Flame spread rating of insulation materials must not exceed 25, smoke density must not exceed 450 per ASTM E84.

2.10 HARDWARE

A. Pull handle on exterior side of door: Minimum 3/4-inch-diamter, US32D stainless steel, 8-inch center-to-center.

B. Recessed 14-gauge 304 stainless steel pull handle on interior side of door.

1. Acceptable Manufacturers/Products, as listed below and meeting the criteria and requirements specified herein:

a. Willoughby Locking Systems; WFP0405.

b. Kingsway Group; KG80.

c. For manufacturers/products not listed, comply with substitution requirements in

Section 01 25 00 – Substitution Procedures.

C. Hinges: Full mortise, minimum 14-gauge 304 stainless steel, continuous full-height.

D. Passage roller latch: Full mortise heavy-duty stainless steel body and roller.

E. Continuous acoustical door seal.

2.11 STOOL

A. General:

1. 12-inch-diameter seat material to be minimum 14-gauge stainless steel, #4 finish. 17-inches to 19-inches seat height. Post and base may be stainless steel or powder coated paint.

2. Secure stool to floor with minimum (4) stainless steel machine bolts with acorn nuts set with threadlocker.

3. Stool must not include a restraint ring.

20260630 12 64 13 – 6 [20260921]

B. Acceptable Manufacturers/Products, as listed below and meeting the criteria and requirements specified herein:

1. Acorn; Model ASF2429.

2. Britex; Model US-STLF.

3. Britex; Model US-STLR.

4. G2 Kryptomax; Model KM-FMS.

5. G2 Kryptomax; Model KM-FMS-EC.

6. Norix; Model S561-120.

7. For manufacturers/products not listed, comply with substitution requirements in Section

01 25 00 – Substitution Procedures.

2.12 EXHAUST

A. Provide exhaust fan capable of minimum 55 CFM and minimum 16-gauge air transfer grille.

Fan to discharge to adjacent space.

1. Controls: Toggle switch on exterior of booth.

2.13 LIGHTING

A. Recessed LED lighting:

1. Lens: Security type with 15/32 monolithic polycarbonate.

2. Mounting: Recessed.

3. Finish: Polyester powder coat.

4. LED Module: Serviceable LED array. Minimum 80 CRI standard.

5. Controls: Toggle switch on exterior of booth.

2.14 TELECOMMUNICATIONS

A. Ethernet:

1. Provide two data outlets with RJ-45 ports, one installed outside of the booth on the same end as the computer or data components, one data outlet installed inside of the booth, interconnected to the data outlet inside the booth.

2. All CAT 6 wiring must be routed in metallic conduit. Wiring installed outside conduit is prohibited.

2.15 POWER

A. Receptacle: 120V, 15A, installed inside of the booth on the same end as the computer or data components.

2.16 SWITCHES

A. Provide toggle type manual switches to control the branch circuits for lighting and exhaust system.

B. Manual switches must be installed outside of the booth on the same end as the computer or data components. Do not locate on the front of the booth.

C. Automatic controls for lighting systems are prohibited.

20260630 12 64 13 – 7 [20260921]

2.17 VIDEOCONFERENCE DEVICE

A. Booth to be provided with VESA mount adapter and wall bracket securely attached to wall panel stud or backing of adequate strength to prevent vandalism.

B. CDCR will provide and install a Desk videoconference device to the booth manufacturer installed bracket.

PART 3 EXECUTION

3.1 EXAMINATION

A. The installer must verify that project conditions are suitable before beginning installation of booth.

3.2 INSTALLATION

A. Booths must be installed level, located individually together in accordance with approved drawings or the CDCR Representative.

3.3 ADJUSTMENT

A. Adjust doors for smooth and balanced movement through full swing (170 degrees).

B. Adjust doors for proper interior operation, free from binding, sticking, sagging, or other defects.

Doors must operate freely with no binding or displacement of frame or hardware.

3.4 TOUCH-UP AND CLEANING

A. Clean and restore soiled surfaces. Remove scraps and debris, and leave site in a clean condition.

B. Primed or painted surfaces which have been scratched or otherwise marred during installation, cleaning, including marks caused by spreader removal, must promptly be finished smooth, cleaned, treated for maximum paint adhesion, and touched up with specified primer and finish paint to match.

END OF SECTION