This document is an Amendment of Solicitation/Modification of Contract for two Computer Numerical Control (CNC) Horizontal Boring Mills at Puget Sound Naval Shipyard. The solicitation (SPE4A8-25-R-0009) has been extended to close on October 8, 2025, to provide time for answering vendor questions. The procurement includes multiple line items for two Fives Model PT 1500 Plain Table Horizontal Boring Mills with Integrated Contouring Head, with associated services such as tooling, training, technical data, IUID tagging, foundation preparation, installation, and equipment removal.
The amendment addresses numerous technical and logistical questions from potential vendors, including installation requirements, electrical connections, foundation removal, site preparation, and work scheduling. Key details include a 406-day delivery timeline, delivery to Bremerton, Washington, and specific requirements for electrical systems, foundation design, and equipment removal. NAVFAC will review design submittals, with 20 business days allocated for initial review and 10 days for revisions. The contract requires professional engineer stamp on construction drawings, and some work must be performed during back shifts or weekends to minimize disruption to shipyard operations.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NO.
See Block 14
4. REQUISITION/PURCHASE REQ. NO.
22-25-1009
5. PROJECT NO. (If applicable)
6. ISSUED BY CODE SPE4A8 7. ADMINISTERED BY (If other than Item 6) CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
CODE FACILITY CODE
SPE4A825R0009
X
2025 AUG 04
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of OffersX X is extended, is not extended.
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
12. ACCOUNTING AND APPROPRIATION DATA (If required)
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO.
IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc. ) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).X
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
E. IMPORTANT: Contractor is not, X is required to sign this document and return 1 copies to issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A NAME AND TITLE OF SIGNER (Type or print)
NSN 7540-01-152-8070
Previous edition unusable
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA FAR (48 CFR) 53.243
16B. UNITED STATES OF AMERICA15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
(a) By completing Items 8 and 15, and returning
DLA AVIATION
ASC INDUSTRIAL PLANT EQUIPMENT
6090 STRATHMORE ROAD
RICHMOND VA 23237
15C. DATE SIGNED 16C. DATE SIGNED
D. OTHER (Specify type of modification and authority)
09/23/2025
3. EFFECTIVE DATE
See Attached Continuation Sheet(s).
(X)
CHECK ONE
9A. AMENDMENT OF SOLICITATION NO.
9B. DATED (SEE ITEM 11)
13. THIS APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
CONTINUATION SHEET REFERENCE NO. OF DOCUMENT BEING CONTINUED:
CONTINUED ON NEXT PAGE
PAGE 2 OF 11 PAGES
SPE4A825R0009 - 0001
The purpose of this amendment is to:
1. The solicitation SPE4A8-25-R-0009, for Two (2) Computer Numerical Control (CNC) Horizontal Boring Mills –Fives Model PT 1500 – Plain Table Horizontal Boring Mill with Integrated Contouring Head (ICH) in accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025, close date will be extended until COB 08 October 2025. The purpose of the extension is to provide answers to questions:
Vendor Questions:
1. (PD) 3.10. Installation. Contractor shall be responsible for attached Installation Responsibilities chart and Local Documents Attachment A for site specific facility requirements. Installation shall comply with EM 385-1-1 and UFC 3-301-01. Installation maximum allowable space (L,W,H) shall be 34 feet x 34 feet x 17 feet and IAW Attachment B.
Will the construction design be reviewed by NAVFAC?
2. (PD) 3.10. Installation. Contractor shall be responsible for attached Installation Responsibilities chart and Local Documents Attachment A for site specific facility requirements. Installation shall comply with EM 385-1-1 and UFC 3-301-01. Installation maximum allowable space (L,W,H) shall be 34 feet x 34 feet x 17 feet and IAW Attachment B.
How many working days will NAVFAC review period be limited to?
3. (PD) 3.10. Installation. Contractor shall be responsible for attached Installation Responsibilities chart and Local Documents Attachment A for site specific facility requirements. Installation shall comply with EM 385-1-1 and UFC 3-301-01. Installation maximum allowable space (L,W,H) shall be 34 feet x 34 feet x 17 feet and IAW Attachment B.
Is there a specification or standard required for the construction design?
4. (PD) 3.3.19.2. Facility Electrical Connections. Electrical connections made to the facility electrical system shall conform to NFPA 70.
Will a load study and arc flash study be required on the power sources as part of this contract?
5. (Attachment E) 1.1. Removal of Existing Giddings & Lewis Horizontal Boring Mill. The Government’s installation site for Machine #2 is currently occupied by a Giddings & Lewis HBM. The existing HBM shall be removed by the contractor once Machine #1 has been fully accepted by the Government. Equipment removal shall include the existing HBM and all associated equipment including but not limited to the machine, electrical cabinets, hydraulic power unit and chiller, deck plates, outrigger supports, disconnect switch A, and all strut, conduit and conductors back to the connection point at overhead Buss B-5-44. The contractor shall submit a phased removal, disposition, and installation plan.
Attachment E, paragraph 1.1 states that machine 2 needs to be fully accepted prior to removal of existing Giddings & Lewis machine. Is there a period the government will require to familiarize themselves with the new machine 2 prior to removal of existing Giddings & Lewis machine?
6. (Attachment E) 1.1. Removal of Existing Giddings & Lewis Horizontal Boring Mill. The Government’s installation site for Machine #2 is currently occupied by a Giddings & Lewis HBM. The existing HBM shall be removed by the contractor once Machine #1 has been fully accepted by the Government. Equipment removal shall include the existing HBM and all associated equipment including but not limited to the machine, electrical cabinets, hydraulic power unit and chiller, deck plates, outrigger supports, disconnect switch A, and all strut, conduit and conductors back to the connection point at overhead Buss B-5-44. The contractor shall submit a phased removal, disposition, and installation plan.
If there is a period required such as 6 months, we will need to account for this in the total duration of the contract. How do we proceed with final acceptance on the first machine so there is no down time on the existing machine?
7. (Attachment E) 2.1. Phased Removal, Disposition, and Installation Plan. Prior to beginning equipment removal, the contractor shall submit a phased removal and disposition plan for a 10 working day Government review. The plan dates shall include Government acceptance date of Machine #1, start dates for equipment removal, equipment movement dates, date equipment will arrive at Navy designated scrap facility or DRMO. Equipment Removal and Transportation Requirements. The Contractor shall remove or relieve any sources of stored energy (gravitational, mechanical, electrical, etc.) that remain within the equipment. The Contractor shall remove bulk fluids, dirt, and debris and manage this waste as designated by the Government in Attachment A. The Contractor shall be responsible for all lifting, rigging and transportation of the equipment to a designated Government scrap facility within a 50-mile radius of Puget Sound Naval Shipyard (PSNS). The contractor shall have the transport vehicle weighed at the PSNS Building 535 scale house before and after the equipment is loaded onto the vehicle. The contractor shall be responsible to clean any residual fluids, dirt, and debris found to have leaked from the removed equipment for a period of two (2) weeks after removal.
If the existing Gidding & Lewis machine is to be turned over to DRMO, it will need to be carefully disassembled, labeled and protected so it is possible to reassemble. This will add significant cost to the equipment removal scope as compared to removal for scrap. Should we plan on removal for DRMO or removal for scrap?
8. (PD) 3.3.19. Electrical System. Each machine shall conform to NFPA 79 or equivalent ISO/EN/DIN/JIS standard. The existing electrical power source available at the installation site is 240 VAC, 3-phase. The contractor shall establish electrical connection at overhead bus duct which is approximately thirty (30) feet in elevation. The machine’s electrical system shall be tolerant of voltage fluctuation of ± 10 percent. The electrical system shall be complete, including transformers required to modify the existing source voltage to the proper operating voltage of the equipment. A properly rated and fused single disconnect device, controlling all electrical power to the equipment, shall be utilized on the machine with means of lockout in the off position only.
PAGE 3 OF 11 PAGES
The wire in the disconnect located on Column C4 resembles the appearance of asbestos insulation. Could the government test this wire insulation for asbestos? I do not see that this has specifically been tested in the environmental reports. If not, should the contractor plan on this being asbestos?
9. (PD) 3.3.19. Electrical System. Each machine shall conform to NFPA 79 or equivalent ISO/EN/DIN/JIS standard. The existing electrical power source available at the installation site is 240 VAC, 3-phase. The contractor shall establish electrical connection at overhead bus duct which is approximately thirty (30) feet in elevation. The machine’s electrical system shall be tolerant of voltage fluctuation of ± 10 percent. The electrical system shall be complete, including transformers required to modify the existing source voltage to the proper operating voltage of the equipment. A properly rated and fused single disconnect device, controlling all electrical power to the equipment, shall be utilized on the machine with means of lockout in the off position only.
I do not see that this has specifically been tested in the environmental reports. If not, should the contractor plan on this being asbestos?
10. (Attachment D) 3.13. Storage. Lay-down area(s) will be provided within the vicinity of the installation site for storage of Contractor’s materials and tools. The Contractor shall submit an Area Outage Request to the Receiving Activity’s Point of Contact no later than 20 business days prior to the outage date. The Government does not accept responsibility for security of Contractor’s materials or tools. The area must be kept clean and orderly, free of rags, paper, and other debris. Failure to maintain the area in a clean condition may result in the loss of the area. The Contractor shall be responsible to restore the storage area to original condition after use.
Attachment A only shows the designated machine areas and does not show designated laydown areas for staging.
Attachment D references laydown areas for materials and tools only. The site location of machine 2 appears to be a laydown storage area for the shops. Will the government be responsible for clearing this area prior to turn over to the contractor?
11. (Attachment D) 3.13. Storage. Lay-down area(s) will be provided within the vicinity of the installation site for storage of Contractor’s materials and tools. The Contractor shall submit an Area Outage Request to the Receiving Activity’s Point of Contact no later than 20 business days prior to the outage date. The Government does not accept responsibility for security of Contractor’s materials or tools. The area must be kept clean and orderly, free of rags, paper, and other debris. Failure to maintain the area in a clean condition may result in the loss of the area. The Contractor shall be responsible to restore the storage area to original condition after use.
Machine 1 location has some items around the exiting Giddings & Lewis machine such as tool cabinets. Will the government be responsible for relocating all items they want to keep prior to turning over the area to the contractor?
12. (Attachment D) 3.13. Storage. Lay-down area(s) will be provided within the vicinity of the installation site for storage of Contractor’s materials and tools. The Contractor shall submit an Area Outage Request to the Receiving Activity’s Point of Contact no later than 20 business days prior to the outage date. The Government does not accept responsibility for security of Contractor’s materials or tools. The area must be kept clean and orderly, free of rags, paper, and other debris. Failure to maintain the area in a clean condition may result in the loss of the area. The Contractor shall be responsible to restore the storage area to original condition after use.
This project will require laydown space around work site as well as outside for parking and equipment. Will the government allow sufficient laydown space to complete this project?
13. (PD) 3.10.6. Existing Foundation Removal for Machine #2. The existing foundation supporting the existing equipment outlined in Attachment D shall be completely removed. Any excavated area not being occupied by the new foundation and machine shall be filled with CDF and capped with concrete with the same thickness of the existing floor slab. The concrete cap shall have rebar grid that is doweled into the existing slab.
There are existing foundations located at machine 1 and 2. Are there record drawings of these foundation available?
14. (Attachment A) – questions (Electrical): Site visit indicated additional questions that are not indicated in SOW or Attachment A:
Column C2 has a transformer and panel that will be in the way of the machine 2 installation.Is the contractor responsible for relocating or will the government complete that prior to turning the area over to the contractor?
15. (Attachment A) – questions (Electrical): Site visit indicated additional questions that are not indicated in SOW or Attachment A:
There is an existing stainless steel disconnect located on column D2 that feeds power to the existing Giddings & Lewis machine. Is this disconnect to be replaced and upgraded to current code requirements?
16. (Attachment D) 4.1. Regular working hours. All work is to be performed during PSNS & IMF regular work hours from 7:30 a.m. to 4:00 p.m., Monday through Friday, except for Federal Holidays. Work performed outside of regular working hours requires notification two business days in advance for consideration and approval. Work that disrupts the normal operations of PSNS & IMF will be required to take place outside of regular working hours/days mentioned above.
Disruptive work may include excavation and movement of equipment through buildings.
Demolition of the existing foundations will require breaking up the concrete. This can be completed in several ways with varying costs. The most cost-effective method is to use an excavator with a demo hammer as used on prior projects. Will this method be allowed?
17. (Attachment D) 4.1. Regular working hours. All work is to be performed during PSNS & IMF regular work hours from 7:30 a.m. to 4:00 p.m., Monday through Friday, except for Federal Holidays. Work performed outside of regular working hours requires notification two business days in advance for consideration and approval. Work that disrupts the normal
PAGE 4 OF 11 PAGES
operations of PSNS & IMF will be required to take place outside of regular working hours/days mentioned above.
Disruptive work may include excavation and movement of equipment through buildings.
Will this method require swing or night shift work only?
18. (Attachment D) 4.1. Regular working hours. All work is to be performed during PSNS & IMF regular work hours from 7:30 a.m. to 4:00 p.m., Monday through Friday, except for Federal Holidays. Work performed outside of regular working hours requires notification two business days in advance for consideration and approval. Work that disrupts the normal operations of PSNS & IMF will be required to take place outside of regular working hours/days mentioned above.
Disruptive work may include excavation and movement of equipment through buildings.
Will concrete saw cutting require swing on night shift or can this be completed during day shift?
19. (Attachment D) 4.1. Regular working hours. All work is to be performed during PSNS & IMF regular work hours from 7:30 a.m. to 4:00 p.m., Monday through Friday, except for Federal Holidays. Work performed outside of regular working hours requires notification two business days in advance for consideration and approval. Work that disrupts the normal operations of PSNS & IMF will be required to take place outside of regular working hours/days mentioned above.
Disruptive work may include excavation and movement of equipment through buildings.
The power taps will require an outage on the main bus above each location. We assume this will be required to be completed on a weekend or holiday. Is that accurate?
Answer to Questions:
1. Yes, the design submittals for this project will be reviewed by the NAVFAC Facilities Engineering and Acquisition Division (FEAD). The FEAD review will include, but is not limited to, review of the foundation design and the design of any supporting mechanical or electrical utility systems proposed by the contractor.
2. NAVFAC will have 20 business days to review drawing submittals and 10 business days to review drawing revisions.
3. Per paragraph 3.10.8.2, 100% construction design drawings shall be stamped by a professional engineer. The professional engineer shall follow all local and state standards.
4. See attachment titled: Contractor Electrical Data Requirements. The contractor shall provide all data in the Contractor Electrical Data Requirements attachment. The contractor data will be provided to NAVFAC. NAVFAC will perform and arc flash study and create a new one line diagram.
5. 15 business days is required between acceptance of the first HBM and removal of the existing HBM.
6. 15 business days is required between acceptance of the first HBM and removal of the existing HBM.
7. The existing HBM will be treated as scrap.
8. Treat the wire as asbestos.
9. Treat the wire as asbestos.
10. The Government will clear the area and turn it over to the Contractor.
11. The Government will clear the area and turn it over to the Contractor.
12. The Government will provide sufficient laydown area for the Contractor.
13. Yes, existing foundation drawings will be provided at contract award.
14. The Government will relocate the existing panel and transformer.
15. The existing disconnect switch shall be replaced.
16. Use of an excavator with demo hammer is acceptable although hours of demolition will have to be done on back shifts.
17. Yes, foundation demolition will have to take place on back shifts.
18. Concrete cutting will have to take place on back shifts.
19. Outages will have to happen on weekends or holidays.
2.All offers will be considered valid for 120 days from the closing date in this amendment.
3.Before award, direct any questions to Christina Gibbs at Christina.Gibbs@dla.mil.
4.All other terms and conditions remain the same.
List of Attachments:
Attachment A: Contractor Electrical Data Requirements.
PAGE 5 OF 11 PAGES
SUPPLIES/SERVICES: 3408-N00001784
ITEM DESCRIPTION:
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Two (2) Computer Numerical Control (CNC) Horizontal Boring Mills –Fives Model PT 1500 – Plain Table Horizontal Boring Mill with Integrated Contouring Head (ICH).
ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT .
0001 3408-N00001784 2.000 EA $ ________________ $ ________________
IPE - Milling Equipment
QTY VARIANCE: PLUS 0% MINUS 0%
INSPECTION POINT: ORIGIN
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
PREP FOR DELIVERY:
WILL BE PACKAGED IN ACCORDANCE WITH ASTM D3951.
DELIVER TWO (2) EACH TO:
PUGET SOUND NAVAL SHIPYARD
1400 FARRAGUT AVE
BREMERTON, WA 98314
DODAAC:
N00024
GOVT USE
External External External Customer RDD/ ITEM PR PRLI PR PRLI Material Need Ship Date .
0001 7011795696 0001 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3419-N00001761
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Tooling.
0002 3419-N00001761 2.000 EA $ ________________ $ ________________
IPE - Tooling
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
PAGE 6 OF 11 PAGES
SUPPLY/SERVICE: 3419-N00001761 CONT'D
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0002 7011795696 0002 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3460-N00004594
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Training.
0003 3460-N00004594 2.000 EA $ ________________ $ ________________
IPE - Training
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0003 7011795696 0003 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3460-N00004592
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Technical Data.
PAGE 7 OF 11 PAGES
SUPPLY/SERVICE: 3460-N00004592 CONT'D
0004 3460-N00004592 2.000 LT $ ________________ $ ________________
IPE - Technical Data
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0004 7011795696 0004 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3460-N00004587
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for IUID Tag(s).
0005 3460-N00004587 2.000 EA $ ________________ $ ________________
IPE - IUID Tag
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
PAGE 8 OF 11 PAGES
SUPPLY/SERVICE: 3460-N00004584 CONT'D
ITEM PR PRLI PR PRLI Material Need Ship Date .
0005 7011795696 0005 N/A N/A N/A 04/09/2025
SUPPLIES/SERVICES: 3460-N00004584
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Foundation.
0006 3460-N00004584 2.000 EA $ ________________ $ ________________
IPE - Foundation
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0006 7011795696 0006 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3460-N00004583
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Removal of Existing Equipment.
0007 3460-N00004583 2.000 EA $ ________________ $ ________________
IPE - External Services
PAGE 9 OF 11 PAGES
SUPPLY/SERVICE: 3460-N00004583 CONT'D
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0007 7011795696 0007 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3460-N00004591
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Shipping.
0008 3460-N00004591 2.000 EA $ ________________ $ ________________
IPE - Shipping
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0008 7011795696 0008 N/A N/A N/A 04/09/2026
PAGE 10 OF 11 PAGES
SUPPLY/SERVICE: 3460-N00004586 CONT'D
SUPPLIES/SERVICES: 3460-N00004586
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for Installation.
0009 3460-N00004586 2.000 EA $ ________________ $ ________________
IPE - Installation
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0009 7011795696 0009 N/A N/A N/A 04/09/2026
SUPPLIES/SERVICES: 3460-N00004588
In accordance with Purchase Description VIBB 22-25-1009, Dated 26 March 2025 for OSHA Certification(s).
0010 3460-N00004588 2.000 EA $ ________________ $ ________________
IPE - OSHA
Certification
ACCEPTANCE POINT: DESTINATION
FOB: DESTINATION DELIVERY DATE: 406 DAYS ADO
CONTINUATION SHEET REFERENCE NO. OF DOCUMENT BEING CONTINUED: PAGE 11 OF 11 PAGES
SUPPLY/SERVICE: 3460-N00004588 CONT'D
1400 FARRAGUT AVE
BREMERTON, WA 98314
ITEM PR PRLI PR PRLI Material Need Ship Date .
0010 7011795696 0010 N/A N/A N/A 04/09/2026
Contractor Requirements for Machinery Electrical One Line Diagram, Electrical Data, and Labeling
Machinery Information Required
Voltage
# Phases
Full Load Amperage
Wire size, insulation type, and distance from panel Breaker to Disconnect
Conduit type and size
Disconnect(s) size, type, and fuse description
Current Interruption Rating
Short Circuit Current Rating
Short Circuit Current Rating label applied to machines main control cabinet
Surge protection devices manufacture specifications
Arc Flash Study
Utilize machine information and NAVFAC facility arc flash data and load study information to perform arc flash study
*Note: If breaker requires Amperage change in the Panel/MCC Containing the Device, Contractor provide Breaker Model Number, Manufacturer, Size, Settings (if applicable), Location, and Cable Connections
SPE4A825R0009-0001 Attachment A: Contractor Electrical Data Requirements.