SP12 Portal NII As Built Sprinkler.pdf

PDF 290 KB Posted

Attached to
Portal VACIS Dry Pipe Replacement
Solicitation number
47PJ0025R0031-P
Issued by

About this file

This is an as-built fire sprinkler system design drawing showing detailed piping layouts and specifications for a building. The drawing includes plan views, sections, and details of a sprinkler system with specific pipe sizes (ranging from 1" to 3"), spacing dimensions (typically 10'-6" and 11'-0" intervals), and equipment specifications including Tyco DPV-1 and Ames Maxim M200 components. The sprinkler system covers multiple areas including a mechanical loft at elevation 127'-3" and various ceiling heights ranging from 23'-0" to 29'-0" AFF (Above Finished Floor).

The drawing contains hydraulic calculation information for remote areas with design criteria of .15/1950 square feet for Ordinary Hazard Group I occupancy. It includes detailed hanger specifications compliant with NFPA 13 Chapter 9, trapeze hanger symbols, and drum drip details. The drawing appears to be part of a larger set for a Portal NII (Non-Intrusive Inspection) facility, which relates to the federal contract opportunity for dry pipe replacement work at the Portal, North Dakota Land Port of Entry.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

MECHANICAL LOFT

CLEAR HT.

127' - 3"

100' - 0"

STEEL COLUMN

(BEYOND)

8" CMU

WALL

T.O. CATWALK FRMG.

109' - 10 12"

T.O. LOFT PLATE 2

119' - 9"

ELECTRICAL EQUIPMENT

MAIN F.F.L.

11-0 11-0 11-0 11-0 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 3" 3" 3" 3"

11-0 11-0 11-0 11-0 11-0 11-0 11-0 4-6

-6

-6

-6

-6

-6

-6

-6

-6

-6

-6

-6

-6

1" RN X 2'-6" (TYPICAL)

1" 1" 1" 1" 1" 1" 1"

1" 1" 1" 1" 1"

1" x 1'- 0" (TYPICAL) 1 " RN X 2'-6"" (TYPICAL) 1" x 1'- 0" (TYPICAL)

STARTER PIECESTARTER PIECE

-0

-6

1" 1"

11-0 11-0 11-0 11-0 11-0 11-0 11-0

2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2"

-61"

-61"

-61"

-61"

-01"

-01"

-01"

-01"

-01"

-01"

-61"

-61"

-61"

-61"

-61"

-61"

-01"

-01"

-01"

-01"

-01"

-61"

3" 45 -0

1 1/4" RN X 2'-6"" (TYPICAL) 1 1/4" RN X 2'-6"" (TYPICAL)1 1

4" x 1'-0" (TYPICAL)

STARTER PIECE

3" DN TO RISER

CALC # 4 REMOTE AREA ORD. HZ. GR. I

.15/1950 (ACTUAL 1962 SF)

CALC # 5 REMOTE AREA ORD. HZ. GR. I

.15/1950 (ACTUAL 2050 SF)

5 10

13 18

20 25

23 27

4 9

10 20

16 21

26 29

26 30

33 37 41

6. PIPING MATERIAL: 21

2" THRU 4" GALV. SCH 10 W/ GRV. FTGS

1" THRU 2" GALV. SCH 40 W/ THRD FTGS

7. AREA OF PROTECTION: MAIN FLOOR: 7400 SQ.FT.

MEZZANINE LEVEL: 120 SQ. FT.

8. SYSTEM DESIGN PER NPFA 13 2007 EDITION FOR ORDINARY HZ

GROUP I OCCUPANCY .15/1950 INCLUDING 30% AREA INCREASE

FOR DRY SYSTEM.

9. DRY PIPE SYSTEM CAPACITY @ 230 GALLONS

10. SYSTEM DEMAND: CALC # 4 365.8 GPM @ 55.5 PSI

SPRINKLER HEAD LEGEND

0 VIKING VK410 INSTITUTION HEAD 165 DEGREE 5.6K

62 TYCO TY3131 BRASS UPRIGHT HD 200 DEGREE 5.6K

2 TYCO TY3231 CHR REC PENDANT HD 155 DEGREE 5.6K

0 TYCO TY3331 BRASS HOR SIDEWALLHD 200 DEGREE 5.6K

TYCO DPV-1

AMES MAXIM M200

11-0 11-0 11-0

3" 3" 3" 3" 3"

8-0

HYDRAULIC REFERENCE POINT

1" UP

11-63-0 1" 1"

1" DN

TIE TO RISER

9-04-0 1" 1"

TYPICAL HANGER (ALL HANGERS TO BE IN FULL

COMPLIANCE W/ NFPA 13 9.1)

HANGER SYMBOL - ALL HANGERS TO BE IN COMPLIANCE

WITH NFPA 13 CHAPTER 9

PE 23'-0" AFF

PE 28'-0"AFF

PE

-'0 " A

FF

PE 29'-0" AFF

PE 28'-0" AFF

PE 27'-0" AFF

PE 24'-0" AFF

3"

TRAPEZE HANGER SYMBOL

OPERATION

N.I.I.

WAITING

CALC # 5 364.7 GPM @ 60.8 PSI

PE

-'0 " A

FF

PE

-'0 " A

FF

SHEETSHEET

GENERAL SERVICES ADMINISTRATION

ROCKY MOUNTAIN REGION

P.O. BOX 25546

DENVER FEDERAL CENTER

DENVER, CO 80225-0546

U .S

. P O

R T

O F

EN

TR

Y N

.I.

I B

U

IL

D

IN

G

PO

R

TA

L, N

O R

TH

D

AK

O

TA

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

SP-12

N.I.I. BUILDING

4- 8-

AS

S

H O

W N

AD

VA

N C

ED

F

IR

E

PR

O

TE

C

TI

O

N

PO

B O

X

FA

R

G O

N D

1-

8-

DESIGNER AND PROFESSIONAL ENGINEER

BRUCE K. HALL NORTH DAKOTA PE #5913

DATE: ____________________

AS BUILT