STATEMENT OF WORK
Delano Dining Room A/V System
U.S. MERCHANT MARINE ACADEMY
KINGS POINT, NEW YORK
June 12, 2020
U.S. DEPARTMENT OF TRANSPORTATION
MARITIME ADMINISTRATION
BACKGROUND
The United States Merchant Martine Academy (USMMA) is an agency of the Maritime Administration (MARAD) managed by the United States Department of Transportation.
The USMMA is listed on the National Register of Historic Places. Therefore, all work shall be consistent with the Secretary of the Interior's Standards for the Treatment of Historic Properties (36 CFR part 68) http://www.nps.gov/tps/standards/four-treatments/treatment-guidelines.pdf.
All work shall meet or exceed the standards provided in the Secretary of the Interior’s Standards for Rehabilitation and guidelines for applying the standards published by the National Park Service, U.S. Department of the Interior 36 CFR 67.7 - Standards for rehabilitation.
Objective:
The USMMA is looking for a qualified, licensed and insured contractor to provide labor, all materials, transportation, tools, equipment and supervision for the supplying and installation of the A/V system for Delano dining facility.
Delivery:
The contractor will be responsible for the following:
-Removal and proper disposal of all of the existing A/V equipment which includes 2 screens, 2 projectors, 1 equipment rack with controller and source equipment and all wall mounted speakers. Once all equipment is removed, the contractor will be responsible for patching all walls and ceilings as needed.
-complete installation of all wiring, new A/V equipment, computers where noted, comprehensive documentation, as well as set-up, testing and training.
- locating the new A/V System in an equipment rack which will be free standing near the stage in the dining room.
-locating (6) speakers and speaker systems as shown in the equipment placement drawing.
-locating (6) television monitors and associated equipment as shown in the equipment placement drawing
- Provide plate and connectivity panels as follows:
-Audio (microphone or line level) – XLR type.
-Audio (loudspeaker level) – Neutrik “Speak-On” Type.
-Intercom – ¼ inch diameter tip/ring/sleeve type, or as required by the intercom system. Jack shall be insulated from panel type.
-Video – HDMI type and/or HD BaseT and/or HD/SDI.
-VGA – DE-15HD jack, isolated from panel type, with hex nuts.
-RF – “F” type. Receptacles shall be insulated from panel type.
-Network - RJ-45 type, insulated from panel -CAT-7 and Crestron DM Shielded RJ-45 type, grounded at one end.
-Provide cable types as follows:
-Unless otherwise called for in these specifications and drawings, the following cables, or their approved equals, shall be used in these systems.
The riser drawings contain cable specifications which take priority.
Note: The Contractor shall only use plugs and jacks specifically manufactured and designed for the cable used.
-Audio Applications
A) Microphone/Line Level; fixed installation
BELDEN 8451 Miniature PVC insulated, AWG 22 stranded copper wire twisted pair with 100% foil shield and drain wire, in PVC jacket, 3.51 mm nominal overall diameter.
Plenum Equivalent: Belden 88761
B) Speaker Level; fixed installation; 18 Gauge (70 Volt distribution only)
BELDEN 5300UP PVC insulated AWG 18 high strand count copper twisted pair, individually PVC insulated with Black & White jackets, in an overall PVC insulated Jacket, 4.67 mm nominal overall diameter.
Plenum Equivalent: Belden 82740
C. Speaker Level; fixed installation; 12 Gauge
BELDEN 5000UP/Liberty 12/4 EX PVC insulated AWG 12 high strand count copper twisted pair, individually PVC insulated with Black & White jackets, in an overall PVC insulated Jacket, 7.67 mm nominal overall diameter.
Liberty 12/4 EX shall have 4 conductors with Black, White, Red & Green jackets.
Plenum Equivalent: Belden 6000UE
D) Speaker Level; fixed installation; 10 Gauge
BELDEN 5T00UP PVC insulated AWG 10 high strand count copper twisted pair, individually PVC insulated with Black & White jackets, in an overall PVC insulated Jacket, 9.04 mm nominal overall diameter.
Plenum Equivalent: Belden 6T00UP
-Video Applications
A) Base-band Analog Video
BELDEN 1694A Coaxial video cable, RG-6U, 75 Ohm, equal to or better in high frequency attenuation performance at 100 MHz (-9dB, 100m) as specified, with double braided shield for minimum 98% coverage, in an overall PVC insulated jacket, 8 mm nominal overall diameter.
Plenum Equivalent: Belden 1695A
B) Serial Digital Video
BELDEN 1694A Coaxial video cable, RG-6U, 75 Ohm, equal to or better in high frequency attenuation performance at 100 MHz (-7.6dB, 100m) as specified, with braided shield for minimum 95% coverage and foil shielding for minimum 100% coverage, in an overall PVC insulated jacket, 6 mm nominal overall diameter.
Plenum Equivalent: Belden 1695A
C) HDMI Video Cable
Various manufacturers cable must be certified HDMI 2.1 compliant.
D) Category 7 Cable. (ISO 11801)
BELDEN 74004NH 23awg cable, Category 7 compliant constructions with 4 individually foil shielded twisted pairs surrounded by an overall braid and enclosed within an overall thermoplastic jacket. Sweep Tested: 5 MHz - 3 GHz.
E) Computer Video Cable
West Penn-CDT WP8195 five (5) conductor bundled coaxial video cable, RG- 59U, 75 Ohm, equal to or better in high frequency attenuation performance at 135 MHz (-8.3dB, 100m) as specified. Each sub-unit with double braided shield and individual jackets in Red, Green, Blue, White and Yellow jacket colors, in overall PVC jacket,
19.69 mm overall diameter
Plenum Equivalent: West Penn-CDT WP825195
F) Camera Video Cable; Triaxial
BELDEN 8233, 75 Ohm RG-11, bare copper braid, 96% coverage. Inner jacket of polyethylene between braids; 12.07 mm nominal overall diameter. Bare copper braid, 95% coverage. Sweep Tested: 5 MHz - 3 GHz.
G) Camera Video Cable; Triaxial
BELDEN 1858A, 75 Ohm RG-11, bare copper braid, 95% coverage. Inner jacket of polyethylene between braids; 13.02 mm nominal overall diameter. Bare copper braid, 95% coverage. Sweep Tested: 5 MHz - 850 MHz.
Plenum Equivalent: Belden 1859A
H) RF Antenna Cable
BELDEN 9913, 50 OHM RG-8U, 10 AWG solid .108" bare copper conductor, semi-solid polyethylene insulation, Duobond II® + tinned copper braid shield (90% coverage), PVC jacket.
I ) RF/CATV Applications
a. Horizontal Distribution, <150’ only.
BELDEN 9118 RF Broadband Cable - 75 Ohm Broadband Coaxial Video cable, RG-6, with braided shield for minimum 60% coverage and triple foil shielding for minimum 100% coverage. Sweep Tested: 5 MHz - 1 GHz, Structural Return Loss 20 db minimum. High Frequency Attenuation performance equal to or better than at 1000 MHz (-21.5dB, 100m), as specified Type, in an overall PVC insulated jacket, 6.99 mm overall diameter.
Plenum Equivalent: Belden 1152A
b. Horizontal Distribution, <250’ only.
BELDEN 9064 RF Broadband Cable - 75 Ohm Broadband Coaxial Video cable, RG-11, with braided shield for minimum 77% coverage and triple foil shielding for minimum 100% coverage. Sweep Tested: 5 MHz - 1 GHz, Structural Return Loss 20 db minimum. High Frequency Attenuation performance equal to or better than at 1000 MHz (-13.9dB, 100m), as specified Type, in an overall PVC insulated jacket, 10.16 mm overall diameter.
Plenum Equivalent: Belden 1153A
c. Primary Riser; Horizontal Distribution, > 250’.
COMM-SCOPE P3 500 JCAR RF Broadband Riser Cable - 75 Ohm Broadband Riser cable; meets NEC Article 820 Riser Rating. High Frequency Attenuation performance equal to or better than at 1000 MHz (-7.91 dB, 100m), as specified; 14.22 mm overall diameter.
Note: It is the responsibility of the Audiovisual Contractor to verify, furnish and install the correct CATV cable type, as per the local CATV provider.
J) Remote Control System Applications and Network Applications
a. Device Interconnection; RS-232/RS-422/RS-485 BELDEN 8723 Two twisted pair stranded AWG 22 copper wire, individually jacketed with individual shielding of pairs, in an overall PVC jacket, 4.39 mm nominal overall diameter.
Plenum Equivalent: Belden 88723
b. Network Interconnection; Ethernet, Dante CATEGORY 6, 6+, 6A BELDEN 10GX0021000, Belden 7851a, Four twisted pairs stranded AWG 23 copper wire with shield; in an overall PVC jacket, .295 inch nominal overall diameter.
Plenum Equivalent BELDEN 10GX130041000, Belden 7852a
c. Device Interconnection; with Power, BELDEN 1502R One twisted pair stranded AWG 22 copper wire with shield; one AWG 18 TC unshielded power pair in an overall PVC jacket,
6.35 mm nominal overall diameter.
Plenum Equivalent: Belden 1502P
Note: These cable types are cited to illustrate the type and quality of cable required.
-the newly installed system meets the below performance standards:
Unless restricted by the published specifications of a particular piece of equipment, or unless otherwise required under the Detailed Specifications, the following performance standards shall be met by each system:
1. Audio – General Conditions All performance standards, unless otherwise noted, should be verified under the following conditions:
a. Frequency bandwidth measured should be 20 Hz to 20 kHz.
b. All levels should be referenced to +4 dBu.
c. Gain settings should be “Unity Gain” for line level signals and maximum for microphone preamplifiers.
2. Audio – Measurements
a. Frequency Response (BW) ................ Within plus or minus 0.5dB.
b. Signal to Noise Ratio (S/N) ............... greater than 90dB, using ITU-R 468 Curve.
c. Total Harmonic Distortion (THD) .... less than 0.05% maximum, minimum 5th-order harmonics.
d. THD plus Noise (THD + N) ............... less than 0.05% maximum, using 22 kHz BW or ITU-R 468 Curve.
e. Intermodulation Distortion ............... less than 0.05% maximum, using 60 Hz and 7 kHz at a 4:1 ratio; +4 dBu at 60 Hz. SMPTE method.
f. Equivalent Input Noise (EIN) ........... -130 dBu, 22 kHz BW at maximum gain with terminating input resistance (Rs) of 150 V.
g. Common Mode Rejection (CMR) ...... 40 dB @ 1 kHz.
h. Dynamic Range................................... 120 dB, referenced to +26 dBu and 22 kHz BW.
i. Crosstalk.............................................. -60 dB channel to channel.
3. Audio (Input Levels)
j. Microphone (Nominal) ...................... -50dbu
k. Overload (Minimum gain) ................. -5dbu
l. Maximum Gain ................................... -26dbu
m. Line (Nominal) ................................... +4dbu
n. Overload (Minimum gain) ................. +24bu
o. Maximum Gain ................................... +9dbu
p. Input Common Mode Rejection ........ >100db
4. Audio (Output Levels)
q. Line (Nominal) ................................... +4dbu
r. Maximum ............................................ +24dbu
s. Output Impedance ............................. <0.5 Ohms
t. Load Impedance ................................. >150 Ohms
5. Video (signal)
u. Frequency Response .......................... Within plus or minus 0.5dB, DC to
4.2 MHz.
v. Signal to Noise Ratio .......................... 55 dB minimum (peak to RMS) unweighted, DC to 4.2 MHz
w. Crosstalk.............................................. 45 dB minimum unweighted DC to
4.2 MHz
x. Line and Field Tilt: ............................. 2% maximum.
y. Differential Gain: ................................ 3% maximum.
z. Differential Gain: ................................ 2 degrees maximum.
6. Performance Test Signal Paths The signal paths for the above Performance Standards shall be as follows:
a. Audio From all source inputs (for microphones, audio tape units, video tape units, etc.) through all mixers, switchers, etc., to all signal destinations.
b. Video Signals From all sources of the above signal paths. This shall not exempt the Contractor from the responsibility of checking all paths and outlets for appropriate compliance with the Performance Standards; see section below for detailed requirements.
7. Optical All optical projection systems shall meet the following performance standards:
a. Each of the six (6) television monitors ate to be 98” LED 4K.
The total averaged light output from a projector, in lumens, shall be within plus-or-minus 15% of that specified by the projector manufacturer.
b. The light fall-off from the center of the projected image to all four corners, as measured at the projected image plane, shall not exceed 35% for slide projector images. The light intensity shall be measured at all five positions of the projected image after the projector has been adjusted to provide the light output as specified above.
c. The “corner” location shall be defined as the four points determined by intersecting lines drawn 5% of the distance in from the focused edges of the image.
d. The light meter used for the above measurements shall be a properly calibrated foot-candle (or lux) meter and shall be cosine-corrected.
e. Projectors, lenses, and mirrors shall be solidly mounted and braced, so that there will be no observable movement in the image induced by motor vibration or other mechanical operations.
8. Control System User Interface Control system user interfaces pages shall be designed for this project exclusively.
While there are a great number of design variations possible within the above user interface, the following guidelines shall be adhered to:
a. All panels are to have the time and date as icons, in the same position on every page.
b. All panels are to have a title, indicating the piece of equipment and/or functionality being controlled.
c. No individual component shall be programmed to function atypically.
d. Devices similar in nature shall be programmed to operate with a common format.
e. Final programming shall include capability to remotely control all functions of the audiovisual system. Individual device controls shall provide full manufacturer’s functionality.
f. Provide control capability for every function available on every piece of equipment being controlled by the system. Define and provide “macro” commands for the most used functions.
g. Provide control panel layouts that are consistent from page to page.
h. Functions used during a general presentation shall be accessible with a minimal amount of button presses/page flips.
i. All power functions, or other destructive commands, activated by the users through the user interface shall be intercepted in the programming.
The user shall be provided with the opportunity to cancel out the command prior to any actions being initiated and without disturbing the current operating model.
The contractor shall bear in mind that this work will be taking place in an active dining facility, all work areas are to be kept neat and tidy, and all areas must remain food-safe at all times. IE: any drilling or dust causing work shall be completed with a vacuum to collect dust.
The A/V system will consist of the following major components:
AUDIO SYSTEM shall provide complete Left, Right and Sub coverage of the dining hall. The audio system will be capable of playing back all sources which include VGA and HDMI computer inputs, CATV and Blu-ray player. The audio will be controlled via a rack/podium mounted touch panel. All speaker and microphone wiring shall be concealed in wall mounted panduit which must be painted to match the existing block wall. HDMI and VGA computer inputs shall be located as shown on the attached drawings. Video content routed to the display system will be derived from a choice of possibilities, including computer generated media from the computer input location, a Blu-ray player, a CATV feed. In addition a high resolution camera facing the stage with a full view of the stage and capable of a zoomed in view of a presenter at the podium. Two of the outputs will be sent to distribution systems which will also carry control code.
CONTROL SYSTEM shall be configured such that the touch screen provides simple and intuitive controls. The touch screen will either be rack or podium mounted. The Control Panel layouts will be designed by the A/V contractor and reviewed by the USMMA for input and modification as required prior to the installation. Every aspect of operation of the system is intended to be controllable via the touch screen. Including but not limited to camera controls, audio control, power controls and video switching. All programming and all source code shall be delivered on computer media to the USMMA upon completion of the final acceptance testing and calibration.
ELECTRICAL SYSTEM shall contain a fully isolated ground. It will consist of a minimum of four 20amp circuits on individual breakers to be pulled from a circuit panel behind the stage. All wiring shall be home runs to the panel with no other external sources being powered by the circuit other than the A/V equipment. All circuits should sit on the same phase of electricity.
The electrical system will include an IG duplex outlet for every Television location as well as one for the equipment rack. The duplex outlets and wiring shall be rated for a 20 amp 110vac load. All panduit and conduit shall be mounted plumb and level and be painted to match the existing block wall as best as possible.
ADA ASSISTIVE LISTENING SYSTEM will consist of one stationary RF transmitter with a range of up to 1000’. The RF transmitter will be located in the equipment rack and its antenna will be mounted at the top rear of the equipment rack. The system will also include a minimum of thirty two DSP RF receivers capable of receiving the signal from the RF transmitter. The receivers will include a rechargeable battery along with enough docking stations to charge all of the receivers. The system will include a minimum of thirty two headphones and eight earphone/neck loop lanyards.
EQUIPMENT RACK will consist of a free standing 40 space rack with side panels and locking front and rear doors. The rack will be equipped with all necessary blanks, vents, shelves , power outlets and a power conditioner.
See attached detailed equipment list. All equipment may be substituted with approved equivalent.
Because drawings are, in general, diagrammatic, the Contractor shall coordinate all installations with the USMMA, based on the actual field conditions. The Contractor is fully responsible to provide a completely functional turnkey system and provide all functionality listed in the functional descriptions, plus all designed functions as shown.
The Audiovisual Contractor shall furnish all software necessary to operate software controlled audiovisual sub-systems e.g. remote control system. This software shall, in every case, be provided by the manufacturer(s) of the subsystem, and shall be installed and tested prior to delivery of equipment at site. All un-compiled Source code for DSP and Control system will be turned over as part of the closeout package. All code will become the property of the USMMA.
The Contractor shall generate shop drawings and information for the complete installation and wiring of the system. A final, approved copy shall be placed in a metal pocket mounted on the inside of the rear (or front) door of a designated rack.
The contractor shall provide a System Operation and Maintenance Manual. This manual shall be produced by the Contractor specially for the systems installed under this contract. The “Operation” section shall describe all typical procedures necessary to activate each system to provide for the functional requirements as listed under the Detailed Specifications. The “Maintenance” section shall provide a recommended maintenance schedule with reference to the applicable pages in the manufacturer’s maintenance manuals. Where inadequate information is provided by the manufacturer, the Contractor shall provide the information necessary for proper maintenance.
The Contractor shall provide on-the-job training by a suitably qualified instructor, to personnel designated by the USMMA, to instruct them in the operation and maintenance of the systems.
All training shall take place after the systems are operational, but before the acceptance tests.
All cables, regardless of length, shall be marked with a permanent, self-laminating wrap-around number or letter cable marker at both ends, labels must be computer generated for legibility.
General:
1. The contractor shall furnish all labor and material, transportation and supervision in the performance of all tasks detailed in this statement of work.
2. The Contractor will ensure all parts and materials are suitable for the specified statement of work.
3. Contractor shall ensure that all wiring and systems will be checked and tested.
4. All work is to conform to federal, state and local building regulations and codes.
5. Maintain a work area compliant with safety standards.
6. Area worked on shall be cleaned and secured on a daily basis.
7. Any damage to existing facilities or appurtenances shall be repaired or replaced in kind, by the contractor at no additional cost to the Government.
8. Examine existing conditions prior to any repair activities, a site visit may be scheduled to inspect the site where services are to be performed.
9. Excess material and debris shall be disposed of in accordance with local and state ordinances.
10. No vehicles shall be driven on the sidewalks or grass. Unless granted specific exception due to site access limitations. Repair of landscape, if any, will be the sole responsibility of the contractor.
11. Make every effort to minimize the impact to the daily routine of the Academy.
12. Contractors shall be licensed, bonded and insured as mandated by federal, state and local municipal regulations.
CLOSE OUT:
The contractor shall provide a signed warranty covering defective materials and improper workmanship on any materials provided in this contract.
Materials and labor to be warranted for a minimum of one year after completion of installation, and equipment to be warranted per manufacturer.
CONSIDERATIONS
• Submit schedule showing area to be worked on, dates of work, and estimated timeline for completion of the task(s).
• Maintain communication with the COR (and immediately inform the COR of any unforeseen issues or problems that arise).
• Inform COR of any anticipated disruption in services for construction at least three (3) days in advance
PLACE OF PERFORMANCE
Contractor will perform the task at Delano Dining Facility, USMMA, 300 Steamboat Road, Kings Point, N.Y. 11024
PERIOD OF PERFORMANCE
Work is to be completed within 90 calendar days after NTP is approved. Work is to be performed during normal business hours 0700 to 1630, Monday through Friday unless approval is granted by the Contracting Officer.
ACCRONYMS
CFR Code of Federal Regulations COR Contract Officer Representative EPA The United States Environmental Protection Agency MARAD United States Maritime Administration NEC National Electrical Code ANSI/NFPA 70 NEMA National Electrical Manufacturers Association NFPA National Fire Protection Association NTP Notice to Proceed TBD To Be Determined USMMA Unites States Merchant Marine Academy