USCG AIR STATION CLEARWATER – C130 AIR COMPRESSOR EXHAUST DUCTING PROJECT

SCOPE OF WORK FOR

C130 AIR COMPRESSOR – EXHAUST SYSTEM

DUCTING PROJECT

18 JUN 2020

Facilities Engineering Air Station Clearwater

15100 Rescue Way Clearwater, FL 33762

SCOPE OF WORK

1.1 GENERAL DESCRIPTION - The work includes furnishing all

labor, trades, equipment, materials, tools, engineering, and supervision to fabricate and install an insulated ducted exhaust system for two newly installed pneumatic air compressors. The new exhaust ducting shall consist of two separate ducting systems commencing at the point of the equipment’s exhaust air discharge and then being conveyed to the point of discharge at a wall mounted discharge louver. Any item identified as being furnished by the CG shall be considered as a Government Furnished Item (GFI).

The project includes, but is not limited to:

1.2 All work shall be coordinated through a Contracting Officer Technical Representative (COTR) assigned by the Coast Guard

(CG)

1.2.1 All work shall be performed IAW State and Local Building code, SMACNA, NEC, and OSHA safety standards.

1.2.2 All effected equipment or systems shall be TAGGED

OUT/LOCKED OUT prior to commencing work to it if applicable for the work being performed.

1.2.3 Any damage created by the contractor to building, system(s), equipment, or GFI shall be immediately reported to the COTR. It shall be the responsibility of the contractor to correct (repair and/or replace) any damage created or caused by them.

1.2.4 Any unforeseen equipment/system deficiencies discovered by the contractor in the course of this project shall be brought to the attention of the COTR. The CG shall not be responsible for payment of additional repairs or services without it having been documented or approved by the CG.

1.2.5 Any hot-work, if applicable, shall be pre-approved by the COTR. All hot-work shall have fire suppression (approved type and properly charged fire extinguisher) and a fire watch person immediately available at the source of that hot-work. All hot-work shall be cool to the touch before departing the space in which it was performed.

1.2.6 All ducting shall be of paint grip galvanized steel of the appropriate metal gauge size, minimum 22 GA, and dimensions for the job at hand. A minimum 1 inch WG design table shall be referenced for this project.

1.2.7 All ducting shall be visually inspected for air leaks

and/or deficiencies by a designated CG representative prior to it being covered with any type of paint system or insulation materials.

1.2.8 All ducting shall conform to the recommended design factors being presented with this documents package, see PDF – Design Sketch. It is critical for this ducting to meet the OEM manufacturer’s design notes per General Arrangement, DWG NO. 47520107001, REV C, for the Ingersoll Rand RS30- 37IE. Any deviation, by the contractor, from the design criteria being specified shall be discussed with, and then meet the approval of the CG before a design change is implemented.

1.2.9 Air intake and exhaust louvers have been installed by the CG. These louvers, 3 each, are sized and designed to meet the exhaust ducting design being specified for this project. The manufacturer cut-sheets are provided as per enclosures. The enclosed images were taken prior to the installation of these louvers.

A. Intake Louver – 72” x 72” x 6”, 1 Each B. Exhaust Louver – 42” x 42” x 6”, 2 Each

1.2.10 A full size flexible duct connection shall be provided at the point of the equipment connection and ducting system.

1.2.11 The ducting system shall be supported with appropriate metal strapping and anchored to the overhead of appropriate anchors for the material in which it’s anchored to. The support system will provide ducting rigidity and prevent any vibration to other surfaces or components when the equipment is running.

1.2.12 The duct design shall provide a sloping pitch (minimum ½ inch) to provide for condensate run-off that is to discharge towards the wall mounted louver.

1.2.13 A metal plenum with a slopped bottom shall be provided between the duct discharge and exhaust louver. The plenum depth shall be sized so as to not to affect the design criteria being specified.

1.2.14 The application of code approved mastic (duct

sealant), gray in color, shall be used to seal all ducting joints and seams. All areas of mastic application shall be taped off using 2 inch painter’s tape so that the mastic being applied is within the taped areas so as to provide a neat and clean appearance. All tape shall be removed prior to the ducting being covered with anything.

1.2.15 A Test & Balance (T&B) shall be performed by an

independent qualified agency to ensure that the ducting specifications have been met for this project, see enclosure for testing requirements. A copy of the T&B report shall be provided to the CG. The T&B testing should be performed before covering the ducting system with insulation.

1.2.16 The exhaust ducting system shall be prepared to

receive the application of elastomer insulation sheets. An approved solvent shall be used to wipe down all exterior duct surfaces to ensure the proper adhesion of all adhesive products. All surfaces shall be clean, dry, and oil free.

The MFG instructions shall be followed for the type elastomer adhesive product being used.

1.2.17 The duct’s insulation system shall be of 2 inch black

flexible closed-cell elastomer thermal insulation either in sheet or roll form. The 25/50 NFPA flame spread and smoke developed index rating shall apply. The elastomer sheets shall cover all the exposed surfaces of the ducting system.

1.2.18 The closed cell elastomer insulation shall receive a

top-coat paint system. It’s the responsibility of the contractor to safe guard the room’s interior and equipment within that space from over-spray, spills, or drippings from all products, i.e. paint, glues, solvents.

1.2.19 The duct insulation system shall be top-coated with a

sprayed on paint coating (weather barrier top-coat) system being white in color and approved for closed-cell elastomer type insulation. The coating product shall be applied IAW MFG’s instructions providing for consistent uniformity and thickness on its entirety.

1.3 PROJECT PERFORMANCE TIME - The total project time shall be estimated to determine the number of calendar days from the Notice to Proceed. Base work hours are 0700 to 1500, Monday thru Friday. Contractor may work outside these work hours with prior approval from the COTR.

1.4 LOCATION - The project address is:

U.S. Coast Guard Air Station Clearwater 15100 Rescue Way Clearwater, FL 33762

1.5 Project Location - The actual location of equipment and

performance of work will be at the C130 Hangar’s air compressor space. The following equipment model number identifies the newly installed compressors requiring the exhaust ducting.

A. System 1 – Air Compressor, Ingersoll Rand, Model –

RS30IE125460

B. System 2 - Air Compressor, Ingersoll Rand, Model –

RS30IE125460

1.6 INSPECTION PRIOR TO BID - Prospective bidders are

encouraged to visit the site. Contractor is responsible for verifying all job requirements to fulfill this project.

Arrangements to visit the site can be made by contacting:

A. CWO Timberlake – 727.423.7586 B. CPO Jon Suermann – 618.444.0959 C. CIV Clint Anstead – 352.362.1918

1.7 AVAILABILITY OF UTILITIES SERVICES

1.7.1 Reasonable amounts of [Electricity, Water, etc.] will be made available to the Contractor without charge.

1.7.2 The Contractor shall, if applicable, pay all costs incurred in connecting, converting, and transferring the utilities to the work. The Contractor shall be responsible for making connections to domestic water lines, providing transformers, and for disconnections. The COTR shall designate the outlets available to the Contractor.

1.8 COORDINATION - The Contractor shall coordinate with the

COTR to minimize interference with Coast Guard operations or personnel.

1.9 CONTRACTOR USE OF PREMISES - The Contractor will be working on a Coast Guard operational military installation. The Contractor shall become familiar with and obey the installation’s fire, traffic, and security regulations.

Personnel shall not stray from the immediate area of work nor direct avenues of ingress and egress unless authorized in advance by the COTR.

1.10 STORAGE AREA - The Contractor will be provided with a

storage area in a location determined by the COTR. The Contractor shall be responsible for restoring the area to its original condition at the completion of the work. The Contractor shall be responsible for repair of any damage incurred to buildings or pavement as a result of storage activities.

1.11 WEATHER AND STORM PROTECTION - Should warnings of inclement weather, gale force winds or stronger be issued, the Contractor shall take every practicable precaution to minimize danger to person, the work, the equipment being serviced, and effected adjacent property. Precautions shall include, but not be limited to, closing all openings, removing all loose materials, tools and equipment from exposed locations, tarp covering opened or exposed equipment, capping exposed open fittings, and removing or securing fencing, scaffolding and other temporary work as applicable.

1.12 ENVIRONMENTAL PROTECTION - No construction debris or other materials shall be allowed to remain on the facility.

Contractor shall provide necessary barriers or use other methods to prevent collection of debris.

1.13 DELIVERY AND STORAGE - Equipment and materials shall be

carefully handled, properly stored, and adequately protected to prevent damage before and during installation, in accordance with the manufacturer’s recommendations.

Damaged or defective items shall be replaced. Location of storage and staging area shall be designated by COTR. The Contractor shall be responsible for the security of all their materials and equipment.

1.14 RECEIPT OF MATERIALS - Shipment of equipment, materials, and supplies shall be addressed to the Contractor – not the Government. The Contractor must be on hand to accept shipments; the Government will not accept shipments.

1.15 CLEANUP - The Contractor shall keep the work area, including storage areas, free from accumulations of waste materials on a daily basis and comply with all federal, state, and local regulations pertaining to the storage, transport, and disposal of wastes generated by them. The Contractor shall not use Coast Guard waste disposal facilities including garbage cans, trash piles, or dumpsters.

1.16 UTILITY OUTAGES - Before interrupting or shutting down any utility, the Contractor shall make a request for the interruption to the COTR at least two (2) working days before the anticipated interruption. The Contractor shall identify the utility, reason for the interruption, proposed time of interruption, and duration of interruption. The Contractor shall not interrupt utilities until authorized by the COTR.

1.17 REFERENCE PUBLICATIONS AND STANDARDS - Except where a

specific date or edition number is listed, reference to a publication or standard in this specification shall mean the edition in effect on the date of the Solicitation.

1.18 SECURITY

1.18.1 Working Personnel List – The Contractor shall provide

the COTR with a list of names of all personnel who will be working on the site. The Contractor may submit a revised list at any time during the project. Only personnel on the approved listing will be allowed on the site.

1.18.2 Personnel Identification – All personnel shall carry

proper identification (ID) when on site. Proper ID is defined as either the individual’s driver license, or a company-issued ID. The ID must be laminated and show facial picture of the individual. Individuals without proper ID will be escorted off the Coast Guard premises.

1.19 WARRANTIES - All warranties and/or guarantees, either

implied or expressed, for individual equipment shall be endorsed to the Government. All work performed by the contractor shall be warrantied for a period of one year upon completion of this service/repair. The contractor shall provide all labor and materials to correct any deficiencies having been determined as a result of poor craftsmanship or a failure of materials provided by them.

1.20 FINAL INSECTION AND ACCEPTANCE - The Contractor shall give the COTR at least 48 hours’ notice for final inspection of work being completed.

Figure 1 - Air Compressor Mechanical Room

Figure 2 - Intake Louver Location

Figure 3 - Exhaust Louver Location

Figure 4 - Air Compressor(s) Layout

Figure 5 - Air Compressor Layout

END OF SCOPE OF WORK

Enclosures:

1. PDF – General Arrangement RS30-37IE, DWG NO. 47520107001, REV

C

2. PDF – Design Sketch with specifications

3. PDF – Coast Guard Louver – Submittal

4. PDF - EVH660D Louver – Submittal

5. PDF – TAB requirements

8 7 6 5 4 3 2 1

8 7 6 5 123

D

C

B

A

D

C

A

B

COPYRIGHT @ 2018

Ingersoll Rand

ALL RIGHTS RESERVED

CAD GENERATED DRAWING,

NO MANUAL REVISIONS ALLOWED

DRAWING CONFORMS TO

ASME Y14.5M - 1994

DO NOT SCALE DRAWING

PROPRIETARY NOTICE

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

UNLESS OTHERWISE SPECIFIED:

- REMOVE ALL BURRS AND SHARP CORNERS

- WELD SYMBOLS TO BE IN ACCORDANCE

WITH ANSI/AWS A2.4

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND IS

GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY RECEPTION

AND RETENTION OF THE DRAWING ACCEPTS THE DRAWING IN CONFIDENCE

AND AGREES THAT, EXCEPT AS AUTHORIZED IN WRITING BY

INGERSOLL-RAND CO. IT WILL (1) NOT USE THE DRAWING OR ANY COPY

THEREOF OR THE CONFIDENTIAL OR TRADE SECRET INFORMATION

THEREIN; (2) NOT COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS

EITHER THE DRAWING OR THE CONFIDENTIAL OR TRADE SECRET

INFORMATION THEREIN; AND (4) UPON COMPLETION OF THE NEED TO

RETAIN THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

WARNING: THE EXPORT OR REEXPORT OF THIS DRAWING OR A PRODUCT PRODUCED

BY THIS DRAWING IS SUBJECT TO U.S. EXPORT ADMINISTRATION REGULATIONS

AND OTHER APPLICABLE GOVERNMENT RESTRICTIONS OR REGULATIONS.

THIRD ANGLE PROJECTION

DWG NO.

PART NO.

ESTIMATED WEIGHT

(KG UNLESS OTHERWISE SPECIFIED)A1

NAME

SIZE

MODEL SHEET

REVISION

SCALE

R

GENERAL ARRANGEMENT

TOLERANCES

ALL DIMENSIONS ARE IN

MILLIMETERS

[INCHES (IF SHOWN)]

UNSPECIFIED TOLERANCES:

ANGLES

.X

WHOLE :

13.0[.50] 6.0[.25]

Ingersoll-Rand Industrial Technologies

REVISIONS

APP'DDRAWNDATEDESCRIPTIONECNREVZONE

J.GERAKT.RAGHU2015OCT02ORIGINAL RELEASE1002760A

P.POLASEKT.RAGHU2015DEC08MODIFIED OUTDOOR MODIFICATION TOP PANEL.1016087BSHT6

C.FRAZIERA.DHANA2018JUN12DIM R951 WAS R951.

[37.5] [27.5] 1303716C3-C3

GENERAL ARRANGEMENT,

RS30-37IE GENERAL ARRANGEMENT, RS30-37IE

SEE NOTE 47520107001 47520107001 C

0.20 RS30-37IE 9 OF 1

For Internal Use:Model=47520107001|ASSEM|C.0|Dhananjaya A L|12-Jun-18 02:10:06 PM|Open<>Drawing=47520107001|DRAW|C.1|Dhananjaya A L|12-Jun-18 05:38:04 PM|Open

C.1

DRAWN DATE

T.RAGHU 2015MAY26

CHECKED DATE

S.KRIZEK 2015MAY26

APPROVED DATE

S.KRIZEK 2015MAY26

DRAWING TYPE

General Arrangement Drawing

NOMENCLATURE

CUSTOMER CONNECTION

ITEM DESCRIPTION COMMENTS

A DISCHARGE AIR 1.5 INCH (FEMALE)

B ELECTRICAL INLET BLANK PLATE SUPPLIED

C PACKAGE AIR INLET (COMPRESSOR)

D PACKAGE AIR EXHAUST (COMPRESSOR)

E AIR INLET (COMPRESSION MODULE)

F PACKAGE AIR INLET (DRYER)

G PACKAGE AIR EXHAUST (DRYER)

H CONDENSATE DRAIN

(MOISTURE SEPARATOR)

.375 INCH (FEMALE)

THIS CONNECTION IS NOT USED ON

NO MOISTURE SEPARATOR UNITS.

J CONDENSATE DRAIN (FILTER) .375 INCH (FEMALE)

K CONDENSATE DRAIN (DRYER) .375 INCH (FEMALE)

NOTES :

1. WEIGHT (APPROXIMATE): RS30IE (NO DRYER) - 1090 KG (2403 LBS)

RS37IE (NO DRYER) - 1140 KG (2513 LBS)

RS30IE (DRYER) - 1265 KG (2789 LBS)

RS37IE (DRYER) - 1315 KG (2899 LBS)

2. COOLING AIR FLOW: 108 M3/MIN (3826 CFM) MAXIMUM.

3. PIPE CONDENSATE DRAIN LINES SEPARATELY TO AN OPEN

DRAIN DUE TO DIFFERENCES IN DRAIN PRESSURES. READ

OPERATIONS MANUAL AND CHECK LOCAL REGULATIONS.

4. LUBRICANT FILL QUANTITY: 24 LITRES (6.3 US GALLONS)

5. RECOMMENDED CLEARANCE ON THREE SIDES 915 MM (36 INCHES)

SIDE WITH ELECTRICAL BOX 1067 MM (42 INCHES) OR MINIMUM AS

REQUIRED BY LATEST NATIONAL ELECTRICAL CODE OR APPLICABLE

LOCAL CODES.

6. EXTERNAL PIPING SHOULD NOT EXERT ANY UNRESOLVED MOMENTS

OR FORCES ON UNIT. USE PIPE OF EQUAL OR GREATER SIZE AT DISCHARGE

LOCATION OF UNIT.

7. THERE SHOULD BE NO PLASTIC OR PVC PIPING ATTACHED TO THIS

UNIT OR USED FOR ANY LINES DOWNSTREAM.

8. REMOVE THE ISOLATION MOUNT RESTRAINTS BEFORE THE INITIAL START.

THE RESTRAINTS CAN BE DISCARDED.

9. FIELD INSTALLED DUCTING TO AND FROM COMPRESSOR CANNOT ADD MORE

THAN 6MM (.25 INCH) OF WATER TOTAL AIR RESISTANCE.

10. UNIT HAS AN INTERNAL DISCHARGE CHECK VALVE, EXTERNAL CHECK VALVE

NOT REQUIRED. ISOLATION VALVE REQUIRED WITHIN 915 MM (36 INCHES)

OF THE COMPRESSOR DISCHARGE.

11. COMPRESSOR SHOULD BE BOLTED TO THE FLOOR WITH FOUR M18 (3/4 INCH) BOLTS

USING HOLES SHOWN ON SHEET 4. SEAL BASE TO FLOOR PER INSTALLATION MANUAL.

12. DO NOT PIPE INTO A COMMON HEADER WITH A RECIPROCATING COMPRESSOR. UNLESS

RECIP COMPRESSOR UTILIZES A DISHCHARGE PULSATION DAMPENER.

13. DENOTES APPROXIMATE CENTER OF GRAVITY.

14. SIZING OF ELECTRICAL COMPONENTS NOT SUPPLIED BY INGERSOLL-RAND IS THE

RESPONSIBILITY OF THE CUSTOMER AND SHOULD BE DONE IN ACCORDANCE WITH

THE INFORMATION ON THE COMPRESSOR DATA PLATE, NATIONAL AND LOCAL ELECTRIC CODES.

15. A BLANK GLAND PLATE IS PROVIDED FOR ELECTRICAL POWER INLET AS INDICATED.

16. WHEN INSTALLED INDOORS IN A CONFINED SPACE, THE COOLING AIR INLET OR

EXHAUST MUST BE DUCTED AWAY FROM UNIT TO PREVENT RECIRCULATION OF HOT EXHAUST AIR.

17. - ALL 60 Hz CONNECTIONS ARE NPT (UNLESS SPECIFIED OTHERWISE)

- ALL 50 Hz CONNECTIONS ARE BSPT (UNLESS SPECIFIED OTHERWISE)

THIRD ANGLE PROJECTION

12-Jun-2018 05:38:54 (model C.0/C.1)

ASCW - GENERAL ARRANGEMENT DWG, REV C

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.15 9 OF 2

FRONT

LEFT END

REAR

RIGHT END

12-Jun-2018 05:38:54 (model C.0/C.1)

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

[76.7]

[63.3] [63.3]

[7.1]

[31.0]

[12.5]

[45.4]

[46.6]

[8.8] [8.8]

[17.2]

[7.2] [7.2]

[18.4]

[.2]

(TYPICAL FOR ALL

LATCHED DOORS)

8.5 [.3] 8.5 [.3]

[2.9] [2.9]

[6.2] [6.2]

[24.4] [24.4]

[41.1]

[22.6]

R760 [29.9]

R951 [37.5]

R632 [24.9]

R722 [28.4]

[33.7]

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.13 9 OF 3

OPTION: NON - TAS

SEE DETAIL B

C

D

FRONT VIEW

D

D

TOP VIEW

SEE DETAIL A

C

C

LEFT END VIEW

DETAIL A

SCALE 1.500

DETAIL B

SCALE 1.000

12-Jun-2018 05:38:54 (model C.0/C.1)

AIR FLOW

A

IR

F

LO

W

H

H

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

[76.7]

[63.3] [63.3]

[64.4] [64.4]

[7.1]

[31.0]

[33.7]

[12.5]

[46.6]

[45.4]

[7.2] [7.2]

[18.4]

[8.8] [8.8]

[17.2]

[30.6] [30.6]

[18.1]

[11.8]

[8.0]

[20.9]

[12.5]

[17.7]

[6.2] [6.2]

[3.0]

[5.9]

[.3] [.3] 4

[.2]

(TYPICAL FOR ALL

LATCHED DOORS)

[.2]

(TYPICAL FOR ALL

LATCHED DOORS)

[38.8]

[24.0]

[27.2] [27.2]

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.13 9 OF 4

C

D

FRONT VIEW

TOP VIEW

LEFT END VIEW

F

G

SEE DETAIL D

D

D

OPTION: WITH TAS

G

G

C

F

F

C

SEE DETAIL C

DETAIL C

SCALE 1.500DETAIL D

SCALE 1.000

AIR FLOW

A

IR

F

LO

W

AIR FLOW

A

IR

F

LO

W

12-Jun-2018 05:38:54 (model C.0/C.1)

HJK

KJH

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

[27.2]

[24.8]

[1.0]

[43.4]

4X 20 [.8]

[23.5]

(BOTH SIDES)

2X 191 [7.5]

(BOTH SIDES)

[24.8]

(BOTH SIDES)

[21.9]

[3.4]

[.5]

[.8]

[6.9]

[11.0]

[8.7]

[36.2]

[15.4]

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.13 9 OF 5

E

E

SEE DETAIL E

REAR VIEW

BOTTOM VIEW

A

A

LEFT END VIEW

B

B

DETAIL E

SCALE 0.750

12-Jun-2018 05:38:54 (model C.0/C.1)

E

B

A

A

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

[78.2]

[8.8]

[17.2]

[7.4]

[17.8]

[8.7]

[45.4]

[71.9]

[46.0]

[77]

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.13 9 OF 6

FRONT VIEW

LEFT END VIEW

GENERAL ARRANGEMENT WITH

OPTIONAL OUTDOOR MODIFICATION

(OPTION IS NOT AVAILABLE FOR DRYER OR VSD UNITS)

D

FRONT

LEFT END

C

D

C

C

RIGHT END VIEW

AIR FLOW

AIR FLOW

12-Jun-2018 05:38:54 (model C.0/C.1)

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

663.5 [26.1]

151.5 [6.0]

390.5 [15.4]

2337.5 [92.0]

[10.0]

[17.6]

194.5 [7.7]

[21.3]

[46.0]

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.20 9 OF 7

LEFT END VIEW

GENERAL ARRANGEMENT WITH

OPTIONAL HIGH DUST PRE-FILTER - NO DRYER

(OPTION IS NOT AVAILABLE FOR VSD UNITS)

FRONT

LEFT END

C

D

C

C

12-Jun-2018 05:38:54 (model C.0/C.1)

A

IR

F

LO

W

AIR FLOW

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

[26.8]

[21.4]

[8.5] [8.5]

[33.0] [33.0]

[10.0] [10.0]

[17.6]

2337.5 [92.0]

390.5 [15.4]

151.5 [6.0] 151.5 [6.0]

1455.5 [57.3]

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.20 9 OF 8

GENERAL ARRANGEMENT WITH

OPTIONAL HIGH DUST PRE-FILTER - WITH DRYER

(OPTION IS NOT AVAILABLE FOR VSD UNITS)

LEFT END VIEW

FRONT

LEFT END

DG

C

F

FRONT VIEW

C & F

C

F

A

IR

F

LO

W

A

IR

F

LO

W

AIR FLOW

AIR FLOW

12-Jun-2018 05:38:54 (model C.0/C.1)

D

C

B

A

D

C

A

B

PROPRIETARY NOTICE

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET

INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND

IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY

RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE

DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS

AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)

NOT USE THE DRAWING OR ANY COPY THEREOF OR THE

CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT

COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE

DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION

THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN

THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL

COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

NAME

A1

SCALE SHEET

REVISIONSIZE

NOMENCLATURE

DWG NO.

PART NO.

3.0 [.1]

(THIS VALUE NEEDS TO

BE ADDED TO ALL

HEIGHT DIMENSIONS

WHEN THIS OPTION

IS PURCHASED)

3.0 [.1]

(THIS VALUE NEEDS TO

BE ADDED TO ALL

HEIGHT DIMENSIONS

WHEN THIS OPTION

IS PURCHASED)

GENERAL ARRANGEMENT,

RS30-37IE

GENERAL ARRANGEMENT, RS30-37IE

47520107001

47520107001 C

0.20 9 OF 9

BOTTOM VIEW

GENERAL ARRANGEMENT WITH

OPTIONAL CONTAINMENT BASE

SEE DETAIL F

FRONT

LEFT END

DETAIL F

SCALE 0.300

12-Jun-2018 05:38:54 (model C.0/C.1)

ASCW - DESIGN SKETCH W/ SPECS

EVH-660D 6 in. Frame, high performance WDR

APPLICATION & DESIGN

EVH-660D is a Florida Product Approved and Miami-Dade Qualified stationary vertical blade wind driven rain extruded aluminum louver designed to protect air intake and exhaust openings in building exterior walls. EVH-660D is tested in accordance with AMCA 500-L Air Performance, Water Penetration and Wind Driven Rain. EVH-660D is tested in accordance with AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile Level D and Enhanced Protection, Missile Level E). EVH-660D is tested in accordance with AMCA 550 Test Method for High Velocity Wind Driven Rain Resistant Louvers. EVH-660D is licensed to bear the AMCA seal allowing design professionals to select and apply with confidence.

EVH-660D is tested and qualified per the following Florida test protocols: TAS 201 (Large Missile Impact), TAS 202 (Uniform Static Air Pressure), TAS 203 (Cyclic Wind Loading) and TAS 100A (Wind Driven Rain). Per Miami-Dade EVH-660D may be installed in locations where the room behind the louver is NOT designed to drain water into the room or the room will house non-water resistant or water proof equipment components or supplies.

Florida Product Approval Number: FL16785.1 Miami-Dade NOA Number: 17-0807.20

PRODUCT DETAILS

Frame: 6 in. x 0.095 in. Frame Thickness Frame Type: Flanged, 1.5 in., Exterior Blades: 0.063 in. Fixed Blade Thickness Material: Aluminum Sizing: Rough Opening Shape: Rectangular Construction: Mechanically Fastened Impact Qualified: Enhanced Lev E

OPTIONS & ACCESSORIES

Finish: Acroflur (50% Kynar), Military Blue (GF109) Bird Screen: 0.75 in. x 0.05 in., Flat Expanded Aluminum, Internal, Match Louver Finish Mounting: Continuous Angles Union Label: No Preference Warranty: 1 year Standard Product Warranty

5YearsStandard Finish Warranty

Internal View

SUMMARY

ID # TAG QTY W (in.) H (in.)

FREE

AREA

(ft2)

FREE

AREA

SECT.

WIDE

SECT.

HIGH

SECT.

SHIP

INSTALL

METHOD

5-1 Intake 1 60 90 16.90 45.1 2 1 2 N/A 5-2 Exhaust 2 42 42 5.36 43.7 1 1 2 N/A

02/27/2020Printed Date:

Coast Guard Louvers 2.25.20Job:

Louvers 2.27.20Mark:

EVH-660DModel:

Generated by: rpurner@stanweaver.com CAPS 4.31.1712 C:\Users\rpurner\Documents\CAPS\Jobs\Coast Guard Louvers 2.25.20.gfcj Page 1 of 5

ASCW - COAST GUARD LOUVERS - SUBMITTAL

PERFORMANCE

ID # TAG APPLICATION VOLUME (CFM) PRESSURE DROP

(in. wg)

FREE AREA

VELOCITY (ft/min) BPWP (ft/min)

5-1 Intake Intake 7,652 0.04 442 1,250

5-2 Exhaust Exhaust 3,815 0.07 687 1,250

**Calculated pressure drop does not include the effects of screens, filters or other accessories

Total Louver Qty: 3 Total Weight (lb): 687 Louver Area (ft2): 62

Total Ship Sect.: 4 **Weight shown is an estimate only based on the default base product configuration without options or accessories.

The maximum design wind load is 150 PSF. Please refer to the product data submittal information for installation instructions. Any additional structural reinforcing members or materials not otherwise shown as "By Greenheck" shall be considered by others. Unless indicated otherwise the following are NOT included in the quote provided: structural steel, anchors into surrounding substrate or structure, shims, backer rod, sealant, dissimilar material isolation, field measuring, installation, flashing, trim, enclosures, blankoff panels, mullion covers, hinged frames, removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints, taxes, PE stamped structural calculations or job specific engineered submittal drawings.

Options and accessories including, but not limited to, screens, filter racks, louver doors, and blankoff panels are not subject to structural analysis unless indicated otherwise by Greenheck.

02/27/2020Printed Date:

Coast Guard Louvers 2.25.20Job:

Louvers 2.27.20Mark:

EVH-660DModel:

Generated by: rpurner@stanweaver.com CAPS 4.31.1712 C:\Users\rpurner\Documents\CAPS\Jobs\Coast Guard Louvers 2.25.20.gfcj Page 2 of 5

Louvers Product Limited Warranty Thank you for purchasing Greenheck louvers. Greenheck warrants this equipment to be free from defect in material and workmanship for a period of 1 year from the date of product shipment. Any units or parts, which prove defective during the warranty period, will be repaired or replaced at our option when returned to our factory, transportation prepaid. Unless agreed upon otherwise Greenheck will not be held responsible for costs associated with removal or installation of product(s).

The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty will be void if payment from Customer is not received within a commercially reasonable time frame. GREENHECK MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is extended solely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Customer.

In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability for and product failure claims.

Failure to pay Greenheck in full for original services will automatically make this warranty null and void.

Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s) replaced or repaired under this limited warranty shall be limited to the remainder of the original warranty period. Greenheck reserves the right to reasonable field access to diagnose and repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things as purchase order forms or acceptance forms, unless otherwise agreed upon by Greenheck.

This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to, those within project specifications.

All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail, postage prepaid, return receipt requested to: Greenheck, Attn: Louver Sales, 525 Western Road, Schofield, WI 54476.

By proceeding to use our products and services on your project, you accept the terms of these limited warranties.

02/27/2020Printed Date:

Coast Guard Louvers 2.25.20Job:

Louvers 2.27.20Mark:

EVH-660DModel:

Generated by: rpurner@stanweaver.com CAPS 4.31.1712 C:\Users\rpurner\Documents\CAPS\Jobs\Coast Guard Louvers 2.25.20.gfcj Page 3 of 5

Louvers Architectural Finish Limited Warranty

Kynar/Hylar and Mica (70% PVDF) Paint Greenheck warrants the finish of Kynar/Hylar (70% PVDF) paint for a period of 5 years from the date of product shipment when applied to aluminum louvers or aluminum architectural products. Greenheck warrants that for 5 years after the date of product shipment the applied finish:

A) Will not chip, crack or peel (lose adhesion) but does not include minute fracturing, which may occur in proper fabrication of building parts.

B) Will not chalk in excess of ASTM D-4214-89 number 8 rating, determined by the procedure outlined in ASTM D-4214-89 specification test.

C) Will not change color more than five (5) Delta-E Hunter units (square root of the sum of Delta L, Delta A and Delta B) as determined by ASTM method D-2244. It is acknowledged that fading or color changes may not be uniform if the surfaces are not equally exposed to the sun and elements.

Metallic and Mica colors are exempt in the warranty from item C but will hold the L value within 5 Delta E or the L scale of the Hunter E unit system.

Exotic colors will receive a full 10 year warranty if they have the recommended clear coat applied. However, Exotic colors are excluded from the 20 year warranty.

Any units or parts, which prove defective during the warranty period, will be repaired or replaced at our option when returned to the factory, transportation prepaid. Unless agreed upon otherwise Greenheck will not be held responsible for costs associated with installation or removal of product(s).

Greenheck limited warranties are not applicable when failure is caused by events that cannot be controlled by Greenheck.

These include, but are not limited to, Acts of God, fire or other casualty or physical damage; Government restrictions; Acts of aggression; Harmful fumes or foreign substances in the atmosphere; Improper storage or packaging of the parts prior to installation; Product failure due to improper usage and/or application; Failure to provide reasonable and routine maintenance and/or improper maintenance, including, but not limited to the use of chemical cleaning agents not in accordance with AAMA recommendations or failure to use a systematic maintenance cleaning program in areas of high salt concentration; Corrosive atmosphere found in the interior of buildings, which effect the interior surface of material;

Standing or ponding water on the metal; Excessive building movements; Work performed or materials supplied by others;

Improper treatment of finished material; Corrosion of the metal substrate; Incompatibility between materials, including, but not limited to, Galvanic corrosion due to contact with adjacent dissimilar metals such as stainless steel; Damage to the painted metal occasioned by moisture or other contamination detrimental to the finish because of improper storage of the finished metal prior to installation as outlined in AAMA Publication 10, “Care and handling of Architectural Aluminum From Shop to Site."

The legal remedies described in this Limited Warranty are the sole exclusive remedy of Customer. This limited warranty will be void if payment from Customer is not received within a commercially reasonable time frame. GREENHECK MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This limited warranty is extended solely to the Customer. It is nontransferable and non-assignable, and the Customer shall not permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Customer.

In the event of material breach by the Customer of any of the conditions of this warranty, Greenheck shall have no liability for and product failure claims.

Failure to pay Greenheck in full for original services will automatically make this warranty null and void.

Greenheck will not be held liable for incidental or consequential damages of any kind. The limited warranty of product(s) replaced or repaired under this limited warranty shall be limited to the remainder of the original warranty period.

Greenheck reserves the right to reasonable field access to diagnose and repair any product alleged to be defective. This limited warranty may not be modified by anyone and may not be changed by such things as purchase order forms or acceptance forms, unless otherwise agreed upon by Greenheck.

This limited warranty is provided in lieu of any other warranty requirements or obligations, including, but not limited to, those within project specifications.

All notices and claims given under or pursuant to this agreement shall be in writing and sent by certified or registered mail, postage prepaid, return receipt requested to: Greenheck, Attn: Louver Sales, 525 Western Road, Schofield, WI 54476.

By proceeding to use our products and services on your project, you accept the terms of these limited warranties.

02/27/2020Printed Date:

Coast Guard Louvers 2.25.20Job:

Louvers 2.27.20Mark:

EVH-660DModel:

Generated by: rpurner@stanweaver.com CAPS 4.31.1712 C:\Users\rpurner\Documents\CAPS\Jobs\Coast Guard Louvers 2.25.20.gfcj Page 4 of 5

AMCA

Greenheck Fan Corporation certifies that the louvers shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance, water penetration, and wind-driven rain ratings.

Greenheck Fan Corporation certifies that the product shown herein is approved to bear the AMCA Listing Label. The ratings shown are based on tests and procedures performed in accordance with AMCA Publications and comply with the requirements of the AMCA Listing Label Program.

02/27/2020Printed Date:

Coast Guard Louvers 2.25.20Job:

Louvers 2.27.20Mark:

EVH-660DModel:

Generated by: rpurner@stanweaver.com CAPS 4.31.1712 C:\Users\rpurner\Documents\CAPS\Jobs\Coast Guard Louvers 2.25.20.gfcj Page 5 of 5

Application and Design

EVH-660D is a Florida Product Approved and Miami-Dade Qualified stationary vertical blade wind driven rain extruded aluminum louver designed to protect air intake and exhaust openings in building exterior walls. EVH-660D is tested in accordance with AMCA 500-L Air Performance, Water Penetration and Wind Driven Rain. EVH-660D is tested in accordance with AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile Level D and Enhanced Protection, Missile Level E). EVH-660D is tested in accordance with AMCA 550 Test Method for High Velocity Wind Driven Rain Resistant Louvers.

EVH-660D is licensed to bear the AMCA seal allowing design professionals to select and apply with confidence. EVH-660D is tested and qualified per the following Florida test protocols: TAS 201 (Large Missile Impact), TAS 202 (Uniform Static Air Pressure), TAS 203 (Cyclic Wind Loading) and TAS 100A (Wind Driven Rain). Per Miami-Dade EVH-660D may be installed in locations where the room behind the louver is NOT designed to drain water penetrating into the room or the room will house non-water resistant or water proof equipment components or supplies.

Standard Construction Frame � � � � � � � � � � Heavy gauge extruded 6063T5 aluminum, 6 in. x 0.095 in. nominal wall thickness

Blades � � � � � � � � � � Vertical rain resistant design, heavy gauge extruded 6063T5 aluminum, 0.063 in. nominal wall thickness, positioned on approximately 0.75 in. centers

Construction . . . . . Mechanically fastened

Birdscreen � � � � � � � 3/4 in. x 0.051 flattened expanded aluminum removable frame, inside mount (rear)

Finish � � � � � � � � � � � Mill

Anchor Clips � � � � � Heavy gauge extruded aluminum, mill finish, continuous mounting angels (head and sill only)

Minimum Rough Opening Size � � � � 12 in. W x 12 in. H

Maximum Rough Opening Size � � � � Unlimited W x 120 1/2 in. H

Maximum Rough Opening Single Section Size � � � � � 48 1/2 in. W x 120 1/2 in. H

Options (at additional cost)

• A variety of bird and insect screens

• Blank-off panels

• Extended sill

• Filter racks

• Flanged frame

• Security bars

• Factory attached VCD-40 damper

• A variety of architectural finishes including:

Clear anodize Integral color anodize Baked enamel Kynar

*Width and height dimensions furnished approximately 1/2 inch under size.

Miami-Dade Qualified Wind-Driven Rain Louver

Florida Product Approval No.: 16785.1 Miami-Dade, FL NOA No.: 17-0807.20 EXP. 10/4/22

AMCA 540 and 550 Listed TDI Approval No.: LVR-07

Maximum Wind-load: 150 PSF

EVH-660D

NOTE: Lifting lugs will be shipped with all units over 10 sq. ft.

ASCW - EVH660D LOUVER - SUBMITTAL

EVH-660DPERFORMANCE DATA

Florida Product Approval No.: 16785.1

Miami-Dade, FL NOA No.: 17-0807.20 EXP. 10/4/22 AMCA 540 and 550 Listed TDI Approval No.: LVR-07

Maximum Wind-load: 150 PSF

The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through 0.01 oz. of water (penetration) per sq. ft. of louver free area.

*The beginning point of water penetration for Model EVH-660D is above 1250 fpm free area velocity. These performance ratings do not guarantee a louver to be weather-proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.

Airflow Resistance (Standard Air - �075 lb/ft3)

Model EVH-660D resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information. (Test Figure 5.5-6.5)

Weather louvers shall be classified by their ability to reject simulated rain. The table shows different classifications based on the maximum simulated rain penetration per square meter (square feet) of louver. Water penetration rating at a given louver face velocity is determined by the water penetration while the louver is subjected to a selected simulated rainfall rate and wind velocity.

Wind-Driven Rain Performance

Discharge Loss Coefficient Class (Intake) = 2

Water Penetration Test Size 48 in� x 48 in� Test Duration of 15 min�

Discharge Loss Coefficient Classifications Wind-driven Rain

Penetration ClassesClass Discharge Loss Coefficient

1 0.4 and Above Class Effectiveness

2 0.3 to 0.399 A 1 to 0.99

3 0.2 to 0.299 B 0.989 to 0.95

4 0.199 and Below C 0.949 to 0.80

D Below 0.80

Greenheck Fan Corporation certifies that the EVH-660D louvers shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance, water penetration, and wind-driven rain ratings.

Greenheck Fan Corporation certifies that the EVH-660D louvers shown herein are approved to bear the AMCA Listing Label. The Ratings shown are based on tests and procedures performaned in accordance with AMCA Publications and comply with the requirements of the AMCA Listing Label Program. The AMCA Listing Label applies to Wind Borne Debris Impact Resistant and High Velocity Rain Resistant Louvers.

75 mm/h (3 in./hr) Rainfall & 13 m/s (29 mph) Wind Velocity

202 mm/h (8 in./hr) Rainfall & 22 m/s (50 mph) Wind Velocity

Free Area Velocity Ventilation Air Core

Velocity Water Penetration Free Area Velocity

Ventilation Air Core Velocity

Water Penetration

(fpm) (m/s) (fpm) (m/s) Effective Class (fpm) (m/s) (fpm) (m/s) Effective Class

0.0 (0) 0.0 (0) A 0.0 (0) 0.0 (0) A

0.9 (185) 0.5 (98) A 0.9 (185) 0.5 (98) A

1.9 (371) 1.0 (197) A 1.9 (371) 1.0 (197) A

2.8 (556) 1.5 (295) A 2.8 (556) 1.5 (295) A

3.8 (742) 2.0 (394) A 3.8 (742) 2.0 (394) A

4.7 (927) 2.5 (492) A 4.7 (927) 2.5 (492) A

5.7 (1113) 3.0 (591) A 5.7 (1113) 3.0 (591) A

6.6 (1298) 3.5 (689) A 6.6 (1298) 3.5 (689) A

7.5 (1483) 4.0 (787) A 7.5 (1483) 4.0 (787) A

8.5 (1669) 4.5 (886) A 8.5 (1669) 4.5 (886) A

9.4 (1852) 5.0 (983) 100.0 A 9.4 (1856) 5.0 (985) 100.0 A

EVH-660DPERFORMANCE DATA

Free Area Chart (sq. ft.)

Core Area Chart (sq. ft.)

Florida Product Approval No.: 16785.1 Miami-Dade, FL NOA No.: 17-0807.20 EXP. 10/4/22

AMCA 540 and 550 Listed TDI Approval No.: LVR-07

Maximum Wind-load: 150 PSFLouver Height Inches

Louver Width in Inches

12 18 24 30 36 42 48

12 0.17 0.34 0.52 0.70 0.88 1.06 1.23

18 0.30 0.63 0.95 1.27 1.60 1.92 2.24

24 0.44 0.91 1.38 1.84 2.31 2.78 3.25

30 0.58 1.19 1.80 2.42 3.03 3.65 4.26

36 0.71 1.47 2.23 2.99 3.75 4.51 5.27

42 0.85 1.75 2.66 3.56 4.47 5.37 6.28

48 0.98 2.03 3.09 4.14 5.19 6.24 7.29

54 1.12 2.32 3.51 4.71 5.90 7.10 8.29

60 1.26 2.60 3.94 5.28 6.62 7.96 9.30

66 1.39 2.88 4.37 5.85 7.34 8.83 10.31

72 1.53 3.16 4.79 6.43 8.06 9.69 11.32

78 1.67 3.44 5.22 7.00 8.78 10.55 12.33

84 1.80 3.73 5.65 7.57 9.49 11.42 13.34

90 1.94 4.01 6.08 8.14 10.21 12.28 14.35

96 2.08 4.29 6.50 8.72 10.93 13.14 15.36

102 2.21 4.57 6.93 9.29 11.65 14.01 16.37

108 2.35 4.85 7.36 9.86 12.37 14.87 17.37

114 2.48 5.13 7.78 10.43 13.08 15.73 18.38

120 2.62 5.42 8.21 11.01 13.80 16.60 19.39

Louver Height Inches

Louver Width in Inches

12 18 24 30 36 42 48

12 0.44 0.73 1.03 1.33 1.62 1.92 2.22

18 0.80 1.35 1.90 2.44 2.99 3.54 4.09

24 1.17 1.97 2.77 3.56 4.36 5.16 5.95

30 1.54 2.59 3.63 4.68 5.73 6.77 7.82

36 1.91 3.20 4.50 5.80 7.09 8.39 9.69

42 2.27 3.82 5.37 6.91 8.46 10.01 11.56

48 2.64 4.44 6.24 8.03 9.83 11.63 13.42

54 3.01 5.06 7.10 9.15 11.20 13.24 15.29

60 3.38 5.67 7.97 10.27 12.56 14.86 17.16

66 3.68 6.19 8.69 11.20 13.70 16.21 18.71

72 4.05 6.81 9.56 12.32 15.07 17.83 20.58

78 4.42 7.42 10.43 13.43 16.44 19.44 22.45

84 4.79 8.04 11.30 14.55 17.81 21.06 24.32

90 5.15 8.66 12.16 15.67 19.17 22.68 26.18

96 5.52 9.28 13.03 16.79 20.54 24.30 28.05

102 5.89 9.89 13.90 17.90 21.91 25.91 29.92

108 6.26 10.51 14.77 19.02 23.28 27.53 31.79

114 6.62 11.13 15.63 20.14 24.64 29.15 33.65

120 6.99 11.75 16.50 21.26 26.01 30.77 35.52

EVH-660DINSTALLATION DETAILS

Maximum Size and Installation Information Model EVH-660D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the installation instructions shown herein.

Model EVH-660D is qualified for installation within concrete/masonry, steel stud, structural steel or wood framed building conditions. Model EVH-660D is structurally calculated to withstand positive and negative wind-loads up to 150 PSF. The maximum single section width is 48 in. The maximum single section height is 120 in.

While the maximum section height is limited to 120 in., the width may be unlimited as multiple sections may be installed side by side in accordance with installation instructions. Structural reinforcing members along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck.

Options and are not subject to structural analysis unless indicated otherwise by Greenheck.

Minimum Rough Opening Size

12 in� W x 12 in� H

Maximum Rough Opening Single Section Size

48 1/2 in� W x 120 1/2 in� H

Florida Product Approval No.: 16785.1 Miami-Dade, FL NOA No.: 17-0807.20 EXP. 10/4/22

AMCA 540 and 550 Listed TDI Approval No.: LVR-07

Maximum Wind-load: 150 PSF

PRODUCT DETAILS EVH-660D

Miami-Dade, FL NOA No.: 17-0807.20 EXP. 10/4/22 AMCA 540 and 550 Listed TDI Approval No.: LVR-07

Maximum Wind-load: 150 PSF

Optional VCD-40 Control Damper

FASTENER CHART EVH-660D

Miami-Dade, FL NOA No.: 17-0807.20 EXP. 10/4/22 AMCA 540 and 550 Listed TDI Approval No.: LVR-07