This document is a Statement of Work (SOW) for a federal contract opportunity to perform emergency life safety repairs at the Fort Harrison VA Regional Office (VARO). The key objectives are to:
-
Replace approximately 600 feet of leaking dry sprinkler system piping in the attic area, in compliance with NFPA 13 standards. This includes providing design, materials, equipment, installation, inspection, and testing of the new automatic sprinkler system.
-
Replace the failed fire alarm control panel in the facility in accordance with NFPA standards.
-
Repair the leaking roof, which experiences annual leaks during the winter/spring season, to prevent further water damage. The contractor will perform an infrared roof moisture survey, remove and replace only the necessary sections of the existing PVC single-ply roofing membrane, and provide a 5-year warranty against leaks.
The contractor will be responsible for all labor, materials, and safety/security requirements. The period of performance is 120 days from the award/kickoff meeting. Inspection, testing, and training requirements are also detailed in the SOW.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C10D24Q0207 0001.pdf | ||
| wage determination.pdf | ||
| 36C10D24Q0207.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fort Harrison VA Regional Office
Statement of Work
Emergency Life Safety Repairs
TABLE OF CONTENTS
1 Introduction
1.2 Background
1.3 Scope
2 General Requirements
2.1 Non-Personal Services
2.2 Business Relations
2.3 Contract Administration and Management
2.3.1 Contract Management
2.3.2 Contract Administration
2.4 Subcontract Management
2.5 Contractor Personnel, Disciplines, and Specialties
2.6 Location and Hours of Work
2.7 Travel
3 Performance Requirements
3.1 Dry pipe sprinkler repair
3.2 Roof repair
4 Special Requirements
4.1 Security
4.2 Safety
4.3 Government Furnished Materials
4.4 Environmental Requirements
4.5 Applicable Directives
4.6 Quality
4.6.1 Quality Control
TABLE OF CONTENTS
4.6.2 Quality Assurance Surveillance Plan (QASP)
5 Deliverables
6 Related Documents
7 Submittals
8 Preparation for Re-Roofing
9 Flashing and sheet metal
Statement of Work (SOW)
Life Safety Repairs
1 Introduction The Fort Harrison VA Regional Office, VARO is in need of awarding a contract to repair three life safety issues; leaking dry sprinkler line pipes, replace fire control panel and leaking roof.
1.1 Background
Dry Pipe - For the past year the Fort Harrison VARO has been spending considerable amount of dollars in repairs to the dry pipe system. Due to the age of the pipe’s condensation has accumulated in the pipes. Over time small pin holes develop due to rusting and when that happens the air pressure drops, and the air compressor comes on trying to establish the correct pressure. Over time the compressor comes on/off numerous times during the day that then leads to compressor malfunction. When the holes get too large, and the compressor cannot reestablish the pressure in the line the system charges and alerts the local fire department. All the water must then be drained, and the pin holes repaired before the system can be repressurized. Even though a nitrogen system has been installed the pin holes continue to develop. One nitrogen compressor (less than year old) has already been replaced.
Fire Alarm Control Panel - failed recent quarterly Fire Alarm Inspection
Roof - each year during the winter/spring season numerous leaks develop inside the FHM VARO. This is due to possible ineffective installation of the roof system specifically where the flat roof and the hip roof join. Melting snow (water) gets under the flashing at this joint and during the re-freeze of that water during the night heaving results making the damage worse.
More water gets under the flashing and eventually a leak results in the attic area. The water then gets absorbed by the insultation (possible mold environment) and eventual comes through the ceiling tiles. Often the ceiling tile holds the water until the tile breaks and falls inside the office space. This area of the roof needs to be investigated and repaired.
1.2 Scope
GENERAL - Contractor will provide all parts, labor, and materials to replace the dry pipeline (fire line) and repair damaged roof of the Fort Harrison VARO. Repairs to the file dry pipeline will be within NFPA 13 Sprinkler Systems standards and all roof repairs will be within local, state, and federal construction standards. Replace Fire Control Panel IAW NFPA standards.
2 General Requirements This section describes the general requirements for this effort. The following sub-sections provide details of various considerations on this effort.
2.1 Non-Personal Services
The Government shall neither supervise contractor employees nor control the method by which the contractor performs the required tasks. Under no circumstances shall the Government assign tasks to, or prepare work schedules for, individual contractor employees. It shall be the responsibility of the contractor to manage its employees and to guard against any actions that are of the nature of personal services or give the perception of personal services. If the contractor believes that any actions constitute, or are perceived to constitute personal services, it shall be the contractor's responsibility to notify the Contracting Officer (CO) immediately.
2.2 Business Relations
The contractor shall successfully integrate and coordinate all activity needed to execute the requirement. The contractor shall manage the timeliness, completeness, and quality of problem identification. The contractor shall provide corrective action plans, proposal submittals, timely identification of issues, and effective management of subcontractors. The contractor shall seek to ensure customer satisfaction and professional and ethical behavior of all contractor personnel.
2.3 Contract Administration and Management
The following subsections specify requirements for contract, management, and personnel administration.
2.3.1 Contract Management
The contractor shall establish clear organizational lines of authority and responsibility to ensure effective management of the resources assigned to the requirement. The contractor must maintain continuity between the Support Operations Division, SSD at 3633 Veterans Drive, Fort Harrison, MT 59636, and the contractor's corporate offices.
2.3.2 Contract Administration
The contractor shall establish processes and assign appropriate resources to effectively administer the requirement. The contractor shall respond to Government requests for contractual actions in a timely fashion. The contractor shall have a single point of contact between the Government and Contractor personnel assigned to support contracts or task orders. The contractor shall assign work effort and maintaining proper and accurate time keeping records of personnel assigned to work on the requirement.
2.4 Subcontract Management
The contractor shall be responsible for any subcontract management necessary to integrate work performed on this requirement and shall be responsible and accountable for subcontractor performance on this requirement. The prime contractor will manage work distribution to ensure there are no Organizational Conflict of Interest (OCI) considerations. Contractors may add subcontractors to their team after notification to the Contracting Officer (CO) or Contracting Officer Representative (COR). Cross teaming may or may not be permitted.
2.5 Contractor Personnel, Disciplines, and Specialties
The contractor shall accomplish the assigned work by employing and utilizing qualified personnel with appropriate combinations of education, training, and experience. The contractor shall match personnel skills to the work or task with a minimum of under/over employment of resources. The contractor shall ensure the labor categories as defined in the Labor Categories document (see base contract), labor rates, and man-hours utilized in the performance of each task of this SOW issued hereunder will be the minimum necessary to accomplish the task.
The Contractor shall provide the necessary resources and infrastructure to manage, perform, and administer the contract.
2.6 Location and Hours of Work
Accomplishment of the results contained in this SOW requires work at 3633 Veterans Drive, Fort Harrison, MT 59636. Normal workdays are Monday through Friday except US Federal Holidays. This work is to be performed between the hours of 7am and 5pm. Weekend work may be authorized with prior approval (48hrs) with the COR. Period of Performance for this project is 60 days from NTP date. This does not include premobilization activities such as ordering parts.
2.6.1 – Period of Performance (POP).
The POP for this project is 120 days from the date agreed to by the CO and Contractor at the Award / Kick off meeting. This will allow the contractor to order and receive supplies and equipment required for successful completion of the project.
2.6.2 – Order of performance This project included both repairs of the roof and replacement of the fire detection and alarm system. Due to weather conditions the roof project will be performed first. This is not to say that supplies and equipment for the fire detection and alarm system should be postponed until the roof repairs are completed. The entire POP for both events together is 120 days as determined from the award / kickoff meeting.
2.7 Travel
The contractor is responsible for all travel related costs in the performance of this contract.
There are no government travel reimbursements authorized.
3 Performance Requirements The following section specifies the Performance Objectives and Performance Elements for the contract.
3.1 Dry pipe sprinkler repair.
Contractor will provide all materials and labor to safely remove and replace approximal 600 feet of metal pipe from the attic area. Contractor will conduct safety and risk assessment in order to efficiently remove metal pipe without causing damage or injury to existing space or employees respectively. Contractor will be responsible for removing all pipe from the property and dispose of IAW federal, city, and state environmental law(s).
Performance Standards
a) Standard: Compliant with federal, state, and local laws and regulations
AQL: Post inspection passed IAW NFPA 13 Standard for the Installation of Sprinkler Systems Deliverables A001 Post Construction Inspection and commission of system
3.1.1 General
Provide design, materials, equipment, installation, inspection, and testing of the automatic sprinkler system in accordance with the requirements of NFPA 13.
1. Perform hydraulic calculations in accordance with NFPA 13 utilizing the Area/Density method, including all applicable design area increases.
2. Sprinkler Protection: Sprinkler hazard classifications shall be in accordance with NFPA 13.
The hazard classification examples of uses and conditions identified in the Annex of NFPA 13 shall be mandatory. Request clarification from the Government for any hazard classification not identified.
3. Dry-pipe Sprinkler System Volume:
a. Contractor shall indicate the calculated volume of each system on the sprinkler system shop drawings.
b. For dry-pipe sprinkler systems with volumes greater than 1893 L (500 gal) up to 2839 L (750 gal), provide a quick opening device unless water delivery time calculations indicate the quick opening devices is not required.
c. For dry-pipe sprinkler systems with volumes greater than 2839 L (750 gal), provide calculations for water delivery time. Calculations shall demonstrate compliance with NFPA 13.
4. Nitrogen Generator Plant: Coordinate sizing of nitrogen generator and air compressor with the nitrogen generator manufacturer.
5. Hydraulic Calculations: Calculated demand including hose stream requirements shall fall no less than 10 percent below the available water supply curve.
Performance Standards
a) Standard: Compliant with federal, state, and local laws and regulations
AQL: Post inspection passed IAW NFPA 13 Standard for the Installation of Sprinkler Systems
3.1.2 Submittals
1. Qualifications:
a. Provide a copy of the installing contractors // fire sprinkler // and state // contractor’s license.
b. Provide a copy of the NICET certification for the NICET Level III or Level IV Sprinkler Technician who prepared and signed the detailed working drawings unless the drawings are stamped by a Registered Professional Engineer licensed in the field of Fire Protection Engineering.
c. Provide documentation showing that the installer has been actively and successfully engaged in the installation of commercial automatic sprinkler systems for the past ten years.
2. Drawings: Submit detailed 1:100 (1/8 inch) scale (minimum) working drawings conforming to the Plans and Calculations chapter of NFPA 13. Drawings shall include graphical scales that allow the user to determine lengths when the drawings are reduced in size. Include a plan showing the piping to the water supply test location.
3. Manufacturers Data Sheets: Provide data sheets for all materials and equipment proposed for use on the system. Include listing information and installation instructions in data sheets. Where data sheets describe items in addition to those proposed to be used for the system, clearly identify the proposed items on the sheet.
4. Calculation Sheets:
a. Submit hydraulic calculation sheets in tabular form conforming to the requirements and recommendations of the Plans and Calculations chapter of NFPA 13.
b. For dry-pipe sprinkler systems with volumes more than 2838 L (750 gal), submit calculations for dry-pipe system water delivery time in accordance with NFPA 13.
5. Valve Charts: Provide a valve chart that identifies the location of each control valve.
Coordinate nomenclature and identification of control valves with COR. Where existing nomenclature does not exist, the chart shall include no less than the following: Tag ID No., Valve Size, Service (control valve, main drain, aux. drain, inspectors test valve, etc.), and Location.
6. Final Document Submittals:
a. A complete set of as-built drawings showing the installed system with the specific interconnections between the system switches and the fire alarm equipment. Provide a complete set in the formats as follows. Submit items 2 and 3 below on a compact disc or as directed by the COR.
1) One full size (or size as directed by the COR) printed copy.
2) One complete set in electronic pdf format.
3) One complete set in AutoCAD format or a format as directed by the COR.
b. Material and Testing Certificate: Upon completion of the sprinkler system installation or any partial section of the system, including testing and flushing, provide a copy of a completed Material and Testing Certificate as indicated in NFPA 13. Certificates shall be provided to document all parts of the installation.
c. Operations and Maintenance Manuals that include step-by-step procedures required for system startup, operation, shutdown, and routine maintenance and testing. The manuals shall include the manufacturer's name, model number, parts list, and tools that should be kept in stock by the owner for routine maintenance, including the name of a local supplier, simplified wiring and controls diagrams, troubleshooting guide, and recommended service organization, including address and telephone number, for each item of equipment.
d. One paper copy of the Material and Testing Certificates and the Operations and Maintenance Manuals above shall be provided in a binder. In addition, these materials shall be provided in pdf format on a compact disc or as directed by the COR.
e. Provide one additional copy of the Operations and Maintenance Manual covering the system in a flexible protective cover and mount in an accessible location adjacent to the riser or as directed by the COR.
Performance Standards
a) Standard: Verify / Validate
3.1.3 Piping & Fittings.
Dry-pipe sprinkler systems shall comply with the requirements of NFPA 13.
1. Piping and fittings for private underground water mains shall be in accordance with NFPA 13.
a. Pipe and fittings from inside face of building 300 mm (12 in.) above finished floor to a distance of approximately 1500 mm (5 ft.) outside building: Ductile Iron, flanged fittings and 316 stainless steel bolting.
b. Piping and fittings for sprinkler systems shall be in accordance with NFPA 13.
2. Plain-end pipe fittings with locking lugs or shear bolts are not permitted.
3. Piping sizes 50 mm (2 inches) and smaller shall be black steel Schedule 40 with threaded end connections.
4. Piping sizes 65 mm (2 inches) and larger shall be black steel Schedule 10 with grooved connections. Grooves in Schedule 10 piping shall be rolled grooved only.
VALVES
1. General:
a. Valves shall be in accordance with NFPA 13.
b. Do not use quarter turn ball valves for 50 mm (2 inch) or larger drain valves.
1. Control Valve:
1. Shall be a manually operated outside stem and yoke (OS&Y) type.
2. Dry-pipe Valve:
1. Shall be a latching differential type.
2. Shall be complete with trim piping, valves, fittings, pressure gauges, priming water fill cup, velocity drip check, drip cup, and other ancillary components as required for proper operation.
3. For dry-pipe sprinkler systems with volumes more than 1893 L (500 gal), provide a quick opening device unless water delivery time calculations have proven no quick opening device is required.
Shall be capable of external reset.
For Fire Department Connections
a. Check Valve: Shall be of the swing type with a flanged cast iron body and flanged inspection plate.
b. Automatic Ball Drips: Cast brass 20 mm (3/4 inch) in-line automatic ball drip with both ends threaded with iron pipe threads.
c. Backflow Preventer: Provide backflow preventer in accordance with Section 22 05 23, GENERAL-DUTY VALVES FOR PLUMBING PIPING. Provide means to forward flow test the backflow preventer in accordance with NFPA 13.
Performance Standards
3.1.4 Sprinklers.
1. All sprinklers shall be FM approved. All sprinklers shall be either upright type, dry pendent type, or dry sidewall type.
2. Temperature Ratings: In accordance with NFPA 13 except that sprinklers in elevator shafts and elevator machine rooms shall be no less than intermediate temperature rated and sprinklers in generator rooms shall be no less than high temperature rated.
3. Provide sprinkler guards in accordance with NFPA 13 and when the elevation of the head is less than 7 feet 6 inches above finished floor. The sprinkler guard shall be listed or approved for use with the corresponding sprinkler.
Performance Standards
3.1.5 Supervisory Nitrogen System.
GENERAL
Nitrogen generation and supply system shall be in accordance with a Nitrogen Generator Plant:
1. Provide a nitrogen supply system in accordance with the manufacturers requirements. The system shall provide at least 98% nitrogen within the system piping.
2. The nitrogen generator shall be complete with, but not limited to, air compressor, air treatment filtration, nitrogen storage tank, relief valves, check valves, isolation valves, pressure regulator, air maintenance device, and all necessary pressure controls and gauges.
3. The air compressor shall be sized to pressurize the sprinkler system to 275 kPa (40 psi) within 30 minutes.
4. Nitrogen concentration shall be automatically monitored for each dry-pipe sprinkler zone.
a. The nitrogen monitoring device shall provide a digital readout of the nitrogen concentration for each connected dry-pipe sprinkler zone.
b. The nitrogen monitoring device shall sample the nitrogen concentration at least once a day.
c. Where the nitrogen concentration is below 98%, a trouble signal shall be sent to the fire alarm system (normally open contact) and/or the building management system.
5. A nitrogen system trouble alarm will sound when nitrogen system is in the bypass mode.
Where the nitrogen system is in bypass mode, a trouble signal shall be sent to the fire alarm system (normally open contact) and/or the building management system.
6. The nitrogen generator plant shall be wall or skid mounted.
Purging Device:
1. The purging device shall shut automatically once the nitrogen concentration in the dry-pipe system piping reaches 98%.
2. The purging device shall be of the same manufacturer as the nitrogen generator.
Performance Standards
3.1.6 Supervisory Air System / Air Pressure Maintenance Device .
Provide an air supply system in accordance with NFPA 13 and the manufacturers requirements.
The air supply system shall be sized to pressurize the sprinkler system to 275 kPa (40 psi) .within 30 minutes
Air Compressor: Compressor shall be tank mounted, single stage oil-free type, air-cooled, electric-motor driven, equipped with a check valve, shutoff valve, automatic drain on drip leg, and pressure switch for automatic starting and stopping. Pressure switch settings to start and stop the compressor shall be as required by system conditions. A safety relief valve shall be provided. 2.8 air pressure maintenance device
Air Pressure Maintenance Device: Air pressure maintenance device shall be UL listed or FM approved and shall automatically reduce supply air pressure to provide the pressure required to be maintained in the piping system. The device shall have a cast bronze body and valve housing complete with diaphragm assembly, spring, filter, ball check to prevent backflow, 1.6 mm (1/16 inch) restriction to prevent rapid pressurization of the system, and adjustment screw.
The device shall be capable of reducing an inlet pressure of up to 680 kPa (100 psig) to a fixed outlet pressure adjustable to 70 kPa (10 psig).
Performance Standards
3.1.7 Installation.
1. Installation shall be accomplished by the licensed contractor. Provide a qualified technician, experienced in the installation and operation of the type of system being installed, to supervise the installation and testing of the system.
2. Installation of Piping: Accurately cut pipe to measurements established by the installer and work into place without springing or forcing. In any situation where bending of the pipe is required, use a standard pipe-bending template. Conceal piping in spaces that have finished ceilings. In stairways, locate piping as near to the ceiling as possible to prevent tampering by unauthorized personnel and to provide a minimum headroom clearance of 2250 mm (seven feet six inches). Piping shall not obstruct the minimum means of egress clearances required by NFPA 101. Pipe hangers, supports, and restraint of system piping, and seismic bracing shall be installed accordance with NFPA 13.
3. Welding: Conform to the requirements and recommendations of NFPA 13.
4. Pitching of Pipe: Conform to the requirements of NFPA 13.
5. Drains: Provide drips and drains, including low point drains, in accordance with NFPA 13.
Pipe drains to discharge at safe points outside of the building. Do not provide a direct drain connection to sewer system or discharge into sinks.
6. Supervisory Switches: Provide supervisory switches for sprinkler control valves to monitor closure of the valve and for high and low system supervisory air/nitrogen pressure to monitor abnormal system pressures.
G. Pressure Alarm Switches: Install alarm pressure switches in easily accessible locations.
7. Inspector's Test Connection: Install and supply in conformance with NFPA 13, and discharge to the exterior of the building. Locate test connection in an area not susceptible to mechanical damage. For dry-pipe sprinkler systems more than 2800 L (750 gal), provide the number of equivalent sprinkler outlets as calculated for water delivery time in accordance with NFPA 13.
8. Affix cutout disks, which are created by cutting holes in the walls of pipe for non-threaded pipe connections, to the respective pipe connection near to the pipe from where they were cut.
9. Provide escutcheon plates for exposed piping passing through walls, floors, or ceilings.
10. Clearances: For systems requiring seismic protection, piping that passes through floors or walls shall have penetrations sized 50 mm (2 inches) nominally larger than the penetrating pipe for pipe sizes 25 mm (1 inch) to 90 mm (3 inches) and 100 mm (4 inches) nominally larger for penetrating pipe sizes 100 mm (4 inches) and larger.
11. Sleeves: Provide for pipes passing through masonry or concrete. Provide space between the pipe and the sleeve in accordance with NFPA 13. Seal this space with a UL Listed through penetration fire stop material in accordance with Section 07 84 00, FIRESTOPPING. Where core drilling is used in lieu of sleeves, also seal space around penetrations. Seal penetrations of walls, floors, and ceilings of other types of construction, in accordance with Section 07 84 00, FIRESTOPPING.
12. For each fire department connection, provide the symbolic sign given in NFPA 170 and locate 2400 to 3000 mm (8 to 10 feet) above each connection location. Size the sign to 450 by 450 mm (18 by 18 inches) with the symbol being at least 350 by 350 mm (14 by 14 inches).
13. Firestopping shall be provided for all penetrations of fire resistance rated construction.
Firestopping shall comply with Section 07 84 00, FIRESTOPPING.
14. Painting of Pipe: In finished areas where walls and ceilings have been painted, paint primed surfaces with two coats of paint to match adjacent surfaces, except paint valves and operating accessories with two coats of gloss red enamel. Exercise care to avoid painting sprinklers.
Painting of sprinkler systems above suspended ceilings and in crawl spaces is not required.
Painting shall comply with Section 09 90 00, PAINTING. Any painted sprinkler shall be replaced with a new sprinkler.
15. Locate sprinkler cabinet adjacent to the dry-pipe sprinkler system riser or as directed by
COR.
16. Sprinkler System Signage: Provide rigid sprinkler system signage in accordance with NFPA 13 and NFPA 25. Sprinkler system signage shall include, but not limited to, the following:
a. Identification Signs:
a. Provide signage for each control valve, drain valve, sprinkler cabinet, and inspector’s test.
b. Provide valve tags for each operable valve. Coordinate nomenclature and identification of operable valves with COR. Where existing nomenclature does not exist, the Tag Identification shall include no less than the following: (FP-B-F/SZ-#) Fire Protection, Building Number, Floor Number/Smoke Zone (if applicable), and Valve Number. (E.g., FP-500-1E-001) Fire Protection, Building 500, First Floor East, Number 001.)
b. Instruction/Information Signs:
1. Provide signage for each control valve to indicate valve function and to indicate what system is being controlled.
2. Provide signage indicating the number and location of low point drains.
c. Hydraulic Placards:
a. Provide signage indicating hydraulic design information. The placard shall include location of the design area, discharge densities, required flow and residual pressure at the base of riser, occupancy classification, hose stream allowance, flow test information, and installing contractor. Locate hydraulic placard information signs at each dry-pipe valve.
17. Repairs: Repair damage to the building or equipment resulting from the installation of the sprinkler system by the installer at no additional expense to the Government.
18. Interruption of Service: There shall be no interruption of the existing sprinkler protection, water, electric, or fire alarm services without prior permission of the Contracting Officer Representative. Contractor shall develop an interim fire protection program where interruptions involve in occupied spaces. Request in writing at least one week prior to the planned interruption.
Performance Standards
3.1.8 Replace Fire Control Panel.
FIRE DETECTION AND ALARM
PART 1 - GENERAL
DESCRIPTION
1. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated system ready for operation. It shall include, but not be limited to, alarm initiating devices, alarm notification appliances, control units, fire safety control devices, annunciators, power supplies, and wiring as shown on the drawings and specified. The fire alarm system shall not be combined with other systems such as building automation, energy management, security, etc.
2. Fire alarm systems shall comply with requirements of the most recent VA FIRE PROTECTION DESIGN MANUAL and NFPA 72 unless variations to NFPA 72 are specifically identified within these contract documents by the following notation: "variation". The design, system layout, document submittal preparation, and supervision of installation and testing shall be provided by a technician that is certified NICET level III or a registered fire protection engineer. The NICET certified technician shall be on site for the supervision and testing of the system. Factory engineers from the equipment manufacturer, thoroughly familiar and knowledgeable with all equipment utilized, shall provide additional technical support at the site as required by the COR. Installers shall have a minimum of 2 years’ experience installing fire alarm systems.
3. Fire alarm signals:
a. Building 167 shall have an automatic digitized voice fire alarm signal with emergency manual voice override to notify occupants to evacuate. The digitized voice message shall identify the area of the building (smoke zone) from which the alarm was initiated.
b. Building 167 shall have a general evacuation fire alarm signal in accordance with ASA S3.41 to notify all occupants in the respective building to evacuate.
4. Alarm signals (by device), supervisory signals (by device) and system trouble signals (by device not reporting) shall be distinctly transmitted to the main fire alarm system control unit located at the front of bld 167 as well as the fire department.
5. The main fire alarm control unit shall automatically transmit alarm signals to a listed central station using a digital alarm communicator transmitter in accordance with NFPA 72.
SCOPE
1. A fully addressable fire alarm system shall be designed and installed in accordance with the specifications and drawings. Device location and wiring runs shown on the drawings are for reference only unless specifically dimensioned. Actual locations shall be in accordance with NFPA 72 and this specification.
2. All existing fire alarm equipment, wiring, devices and sub-systems that are outdated and not IAW current NFPA guidelines shall be removed and replaced. All existing fire alarm conduit not reused shall be removed.
3 Existing fire alarm bells, chimes, door holders, 120VAC duct smoke detectors, valve tamper switches and waterflow/pressure switches may be reused only if the equipment:
a. Is UL listed or FM approved
b. Is compatible with new equipment being installed
c. Is verified as operable through contractor testing and inspection
d. Is warranted as new by the contractor.
4. Existing 120 VAC duct smoke detectors, waterflow/pressure switches, and valve tamper switches reused by the Contractor shall be equipped with an addressable interface device compatible with the new equipment being installed.
5. Existing reused equipment shall be covered as new equipment under the Warranty specified herein.
6. Basic Performance:
a. Alarm and trouble signals from the building fire alarm control panel shall be digitally encoded by UL listed electronic devices onto a multiplexed communication system.
b. Response time between alarm initiation (contact closure) and recording at the main fire alarm control unit (appearance on alphanumeric read out) shall not exceed 5 seconds.
c. The signaling line circuits (SLC) between building fire alarm control units shall be wired Style 7 in accordance with NFPA 72. Isolation shall be provided so that no more than one building can be lost due to a short circuit fault.
d. Initiating device circuits (IDC) shall be wired Style C in accordance with NFPA 72.
e. Signaling line circuits (SLC) within the facility shall be wired Style 4 in accordance with NFPA 72. Individual signaling line circuits shall be limited to covering 22,500 square feet (2,090 square meters) of floor space or 3 floors whichever is less.
f. Notification appliance circuits (NAC) shall be wired Style Y in accordance with NFPA 72.
APPLICABLE PUBLICATIONS
1. The publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. The publications are referenced in text by the basic designation only and the latest editions of these publications shall be applicable.
2. National Fire Protection Association (NFPA):
NFPA 13 ................. Standard for the Installation of Sprinkler Systems, 2010 edition
NFPA 14 .................. Standard for the Installation of Standpipes and Hose Systems, 2010 edition
NFPA 20 .................. Standard for the Installation of Stationary Pumps for Fire Protection, 2010 edition
NFPA 70 National Electrical Code (NEC), 2010 edition
NFPA 72 National Fire Alarm Code, 2010 edition
NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems, 2009 edition
NFPA 101 Life Safety Code, 2009 edition
3. Underwriters Laboratories, Inc. (UL): Fire Protection Equipment Directory
4. Factory Mutual Research Corp (FM): Approval Guide, 2007-2011
E. American National Standards Institute (ANSI):
S3.41 Audible Emergency Evacuation Signal, 1990 edition, reaffirmed 2008
5. International Code Council, International Building Code (IBC), 2009 edition
PART 2 PRODUCTS
EQUIPMENT AND MATERIALS, GENERAL
1. All equipment and components shall be new and the manufacturer's current model. All equipment shall be tested and listed by Underwriters Laboratories, Inc. or Factory Mutual Research Corporation for use as part of a fire alarm system. The authorized representative of the manufacturer of the major equipment shall certify that the installation complies with all manufacturers requirements and that satisfactory total system operation has been achieved.
FIRE ALARM CONTROL UNIT
1. General:
a. Building 167 shall be provided with a fire alarm control unit and shall operate as a supervised zoned fire alarm system.
b. Each power source shall be supervised from the other source for loss of power.
c. All circuits shall be monitored for integrity.
d. Visually and audibly annunciate any trouble condition including, but not limited to main power failure, grounds and system wiring derangement.
e. Transmit digital alarm information to the main fire alarm control unit.
2. Enclosure:
1. The control unit shall be housed in a cabinet suitable for both recessed and surface mounting. Cabinet and front shall be corrosion protected, given a rust-resistant prime coat, and manufacturer's standard finish.
2. Cabinet shall contain all necessary relays, terminals, lamps, and legend plates to provide control for the system.
3. Operator terminal at main control unit:
a. Operator terminal shall consist of the central processing unit, display screen, keyboard and printer.
b. Display screen shall have a minimum 15-inch (380 mm) diagonal non-glare screen capable of displaying 24 lines of 80 characters each.
c. Keyboard shall consist of 60 alpha numeric and 12 user/functional control keys.
d. Printer shall be the automatic type, printing the date, time and location for all alarm, supervisory, and trouble conditions.
4. Power Supply:
a. The control unit shall derive its normal power from a 120 volt, 60 Hz dedicated supply connected to the emergency power system. Standby power shall be provided by a 24 volt DC battery as hereinafter specified. The normal power shall be transformed, rectified, coordinated, and interfaced with the standby battery and charger.
b. The door holder power shall be arranged so that momentary or sustained loss of main operating power shall not cause the release of any door.
c. Power supply for smoke detectors shall be taken from the fire alarm control unit.
d. Provide protectors to protect the fire alarm equipment from damage due to lightning or voltage and current transients.
e. Provide new separate and direct ground lines to the outside to protect the equipment from unwanted grounds.
5. Circuit Supervision: Each alarm initiating device circuit, signaling line circuit, and notification appliance circuit, shall be supervised against the occurrence of a break or ground fault condition in the field wiring. These conditions shall cause a trouble signal to sound in the control unit until manually silenced by an off switch.
6. Supervisory Devices: All sprinkler system valves, standpipe control valves, post indicator valves (PIV), and main gate valves shall be supervised for off-normal position. Closing a valve shall sound a supervisory signal at the control unit until silenced by an off switch. The specific location of all closed valves shall be identified at the control unit. Valve operation shall not cause an alarm signal. Low air pressure switches and duct detectors shall be monitored as supervisory signals. The power supply to the elevator shunt trip breaker shall be monitored by the fire alarm system as a supervisory signal.
7. Trouble signals:
a. Arrange the trouble signals for automatic reset (non-latching).
b. System trouble switch off and on lamps shall be visible through the control unit door.
8. Function Switches: Provide the following switches in addition to any other switches required for the system:
a. Remote Alarm Transmission By-pass Switch: Shall prevent transmission of all signals to the main fire alarm control unit when in the "off" position. A system trouble signal shall be energized when switch is in the off position.
b. Alarm Off Switch: Shall disconnect power to alarm notification circuits on the local building alarm system. A system trouble signal shall be activated when switch is in the off position.
c. Trouble Silence Switch: Shall silence the trouble signal whenever the trouble silence switch is operated. This switch shall not reset the trouble signal.
d. Reset Switch: Shall reset the system after an alarm, provided the initiating device has been reset. The system shall lock in alarm until reset.
e. Lamp Test Switch: A test switch or other approved convenient means shall be provided to test the indicator lamps.
f. Drill Switch: Shall activate all notification devices without tripping the remote alarm transmitter. This switch is required only for general evacuation systems specified herein.
g. Door Holder By-Pass Switch: Shall prevent doors from releasing during fire alarm tests. A system trouble alarm shall be energized when switch is in the abnormal position.
h. HVAC/Smoke Damper By-Pass: Provide a means to disable HVAC fans from shutting down and/or smoke dampers from closing upon operation of an initiating device designed to interconnect with these devices.
9. Remote Transmissions:
1. Provide capability and equipment for transmission of alarm, supervisory and trouble signals to the main fire alarm control unit.
2. Transmitters shall be compatible with the systems and equipment they are connected to such as timing, operation and other required features.
10. Remote Control Capability: The building fire alarm control unit shall be installed and programmed so that each must be reset locally after an alarm, before the main fire alarm control unit can be reset. After the local building fire alarm control unit has been reset, then the all system acknowledge, reset, silence or disabling functions can be operated by the main fire alarm control unit
11. System Expansion: Design the control units and enclosures so that the system can be expanded in the future (to include the addition of 20 percent more alarm initiating, alarm notification and door holder circuits) without disruption or replacement of the existing control unit and secondary power supply.
ANNUNCIATION
1. Annunciator, Alphanumeric Type (System):
a. Shall be a supervised, LCD display containing a minimum of 2 lines of 40 characters for alarm annunciation in clear English text.
b. Message shall identify building number, floor, zone, etc on the first line and device description and status (pull station, smoke detector, waterflow alarm or trouble condition) on the second line.
c. The initial alarm received shall be indicated as such.
d. A selector switch shall be provided for viewing subsequent alarm messages.
e. The display shall be UL listed for fire alarm application.
f. Annunciators shall display information for all buildings connected to the system. Local building annunciators, for general evacuation system buildings, shall be permitted when shown on the drawings and approved by the COTR.
2. Printers:
a. System printers shall be high reliability digital input devices, UL approved, for fire alarm applications. The printers shall operate at a minimum speed of 30 characters per second.
The printer shall be continually supervised.
b. Printers shall be programmable to either alarm only or event logging output.
a. Alarm printers shall provide a permanent (printed) record of all alarm information that occurs within the fire alarm system. Alarm information shall include the date, time, building number, floor, zone, device type, device address, and condition.
b. Event logging printers shall provide a permanent (printed) record of every change of status that occurs within the fire alarm system. Status information shall include date, time, building number, floor, zone, device type, device address and change of status (alarm, trouble, supervisory, reset/return to normal).
c. System printers shall provide tractor drive feed pins for conventional fan fold 8-1/2" x 11" (213 mm x 275 mm) paper.
d. The printers shall provide a printing and non-printing self test feature.
e. Power supply for printers shall be taken from and coordinated with the building emergency service.
f. Each printer shall be provided with a stand for the printer and paper.
g. Spare paper and ribbons for printers shall be stocked and maintained as part of the one year guarantee period services in addition to the one installed after the approval of the final acceptance test.
ALARM NOTIFICATION APPLIANCES
1. Bells:
a. Shall be electric, single-stroke or vibrating, heavy-duty, under-dome, solenoid type.
b. Unless otherwise shown on the drawings, shall be 6 inches (150 mm) diameter and have a minimum nominal rating of 80 dBA at 10 feet (3,000 mm).
c. Mount on removable adapter plates on outlet boxes.
d Bells located outdoors shall be weatherproof type with metal housing and protective grille.
e. Each bell circuit shall have a minimum of 20 percent spare capacity.
2. Speakers:
a. Shall operate on either 25 VRMS or 70.7 VRMS with field selectable output taps from 0.5 to 2.0W and originally installed at the 1/2 watt tap. Speakers shall provide a minimum sound output of 80 dBA at 10 feet (3,000 mm) with the 1/2 watt tap.
b. Frequency response shall be a minimum of 400 HZ to 4,000 HZ.
c. Four inches (100 mm) or 8 inches (200 mm) cone type speakers ceiling mounted with white colored baffles in areas with suspended ceilings and wall mounted in areas without ceilings.
3 Strobes:
a. Xenon flash tube type minimum 15 candela in toilet rooms and 75 candela in all other areas with a flash rate of 1 HZ. Strobes shall be synchronized where required by the National Fire Alarm Code (NFPA 72).
b. Backplate shall be red with 1/2 inch (13 mm) permanent red letters. Lettering to read "Fire", be oriented on the wall or ceiling properly, and be visible from all viewing directions.
c. Each strobe circuit shall have a minimum of 20 percent spare capacity.
d. Strobes may be combined with the audible notification appliances specified herein.
4. Fire Alarm Horns:
a. Shall be electric, utilizing solid state electronic technology operating on a nominal 24
VDC.
b. Shall be a minimum nominal rating of 80 dBA at 10 feet (3,000 mm).
c. Mount on removable adapter plates on conduit boxes.
d. Horns located outdoors shall be of weatherproof type with metal housing and protective grille.
e. Each horn circuit shall have a minimum of 20 percent spare capacity.
ALARM INITIATING DEVICES
1. Manual Fire Alarm Stations:
a. Shall be non-breakglass, address reporting type.
b. Station front shall be constructed of a durable material such as cast or extruded metal or high impact plastic. Stations shall be semi-flush type.
c. Stations shall be of single action pull down type with suitable operating instructions provided on front in raised or depressed letters, and clearly labeled "FIRE."
d. Operating handles shall be constructed of a durable material. On operation, the lever shall lock in alarm position and remain so until reset. A key shall be required to gain front access for resetting, or conducting tests and drills.
e. Unless otherwise specified, all exposed parts shall be red in color and have a smooth, hard, durable finish.
2. Smoke Detectors:
a. Smoke detectors shall be photoelectric type and UL listed for use with the fire alarm control unit being furnished.
b. Smoke detectors shall be addressable type complying with applicable UL Standards for system type detectors. Smoke detectors shall be installed in accordance with the manufacturer's recommendations and NFPA 72.
c. Detectors shall have an indication lamp to denote an alarm condition. Provide remote indicator lamps and identification plates where detectors are concealed from view. Locate the remote indicator lamps and identification plates flush mounted on walls so they can be observed from a normal standing position.
d. All spot type and duct type detectors installed shall be of the photoelectric type.
e. Photoelectric detectors shall be factory calibrated and readily field adjustable. The sensitivity of any photoelectric detector shall be factory set at 3.0 plus or minus 0.25 percent obscuration per foot.
f. Detectors shall provide a visual trouble indication if they drift out of sensitivity range or fail internal diagnostics. Detectors shall also provide visual indication of sensitivity level upon testing. Detectors, along with the fire alarm control units shall be UL listed for testing the sensitivity of the detectors.
3. Heat Detectors:
a. Heat detectors shall be of the addressable restorable rate compensated fixed-temperature spot type.
b. Detectors shall have a minimum smooth ceiling rating of 2,500 square feet (230 square meters).
4 Water Flow and Pressure Switches:
a. Wet pipe water flow switches and dry pipe alarm pressure switches for sprinkler systems shall be connected to the fire alarm system by way of an address reporting interface device.
SUPERVISORY DEVICES
1. Duct Smoke Detectors:
a. Duct smoke detectors shall be provided and connected by way of an address reporting interface device. Detectors shall be provided with an approved duct housing mounted exterior to the duct, and shall have perforated sampling tubes extending across the full width of the duct (wall to wall). Detector placement shall be such that there is uniform airflow in the cross section of the duct.
b. Interlocking with fans shall be provided in accordance with NFPA 90A and as specified hereinafter under Part 3.2, "TYPICAL OPERATION".
c. Provide remote indicator lamps, key test stations and identification nameplates (e.g.
"DUCT SMOKE DETECTOR AHU-X") for all duct detectors. Locate key test stations in plain view on walls or ceilings so that they can be observed and operated from a normal standing position.
2. Sprinkler and Standpipe System Supervisory Switches:
a. Each sprinkler system water supply control valve, riser valve or zone control valve, and each standpipe system riser control valve shall be equipped with a supervisory switch.
Standpipe hose valves, and test and drain valves shall not be equipped with supervisory switches.
b. PIV (post indicator valve) or main gate valve shall be equipped with a supervisory switch.
c. Valve supervisory switches shall be connected to the fire alarm system by way of address reporting interface device.
d. The mechanism shall be contained in a weatherproof die-cast aluminum housing that shall provide a 3/4 inch (19 mm) tapped conduit entrance and incorporate the necessary facilities for attachment to the valves.
e. The entire installed assembly shall be tamper-proof and arranged to cause a switch operation if the housing cover is removed or if the unit is removed from its mounting.
f. Where dry-pipe sprinkler systems are installed, high and low air pressure switches shall be provided and monitored by way of an address reporting interface devices.
PART 3 - EXECUTION
INSTALLATION:
1. Installation shall be in accordance with NFPA 70, 72, 90A, and 101 as shown on the drawings, and as recommended by the major equipment manufacturer.
2. Existing devices that are reused shall be properly mounted and installed. Where devices are installed on existing shallow backboxes, extension rings of the same material, color and texture of the new fire alarm devices shall be used.
3. All fire detection and alarm system devices, control units and remote annunciators shall be flush mounted when located in finished areas and may be surface mounted when located in unfinished areas. Exact locations are to be approved by the COTR.
4. Speakers shall be ceiling mounted and fully recessed in areas with suspended ceilings.
Speakers shall be wall mounted and recessed in finished areas without suspended ceilings.
Speakers may be surface mounted in unfinished areas.
5. Strobes shall be flush wall mounted with the bottom of the unit located 80 inches (2,000 mm) above the floor or 6 inches (150 mm) below ceiling, whichever is lower. Locate and mount to maintain a minimum 36 inches (900 mm) clearance from side obstructions.
6. Manual pull stations shall be installed not less than 42 inches (1,050 mm) or more than 48 inches (1,200 mm) from finished floor to bottom of device and within 60 inches (1,500 mm) of a stairway or an exit door.
7. Where possible, locate water flow and pressure switches a minimum of 12 inches (300 mm) from a fitting that changes the direction of the flow and a minimum of 36 inches (900 mm) from a valve.
8. Mount valve tamper switches so as not to interfere with the normal operation of the valve and adjust to operate within 2 revolutions toward the closed position of the valve control, or when the stem has moved no more than 1/5 of the distance from its normal position.
TYPICAL OPERATION
1. Activation of any manual pull station, water flow or pressure switch, heat detector, kitchen hood suppression system, gaseous suppression system, or smoke detector shall cause the following operations to occur:
a. Operate the emergency voice communication system in Buildings 167. For sprinkler protected buildings, flash strobes continuously only in the zone of alarm. For buildings without sprinkler protection throughout, flash strobes continuously only on the floor of alarm.
b. Continuously sound a temporal pattern general alarm and flash all strobes in the building in alarm until reset at the local fire alarm control unit in Buildings 167.
c. Release ALL the magnetic door holders after the alert signal.
d. Transmit a separate alarm signal, via the main fire alarm control unit to the fire department.
e. Unlock the electrically locked exit doors within the zone of alarm.
2. Operation of a smoke detector at a corridor door used for automatic closing shall also release only the magnetic door holders on that floor.
3. Operation of duct smoke detectors shall cause a system supervisory condition and shut down the ventilation system and close the associated smoke dampers as appropriate.
4.…