This document is a Statement of Work (SOW) for fire suppression system repairs at the United States Coast Guard Base Miami Beach. The SOW details comprehensive repair requirements for fire suppression systems in Buildings 3, 4, 9, and 16, including replacing waterflow switches, butterfly control valves, OS&Y valves, piping components, fire pump components, and jockey pump. Specific tasks include removing and replacing various valves, pipes, couplings, riser clamps, and performing system testing and maintenance.
The solicitation (70Z028-25-Q-0024170) is a small business set-aside with a firm fixed-price construction contract. Quotes are due by 3 p.m. on August 22, 2025, with an anticipated award date of August 30, 2025. The contract requires contractors to provide all labor, materials, and equipment, with performance expected to commence within 10 business days after award. Prospective bidders are strongly encouraged to conduct a site visit and submit past performance documentation. Evaluation will be based on lowest price, technically acceptable criteria, considering past performance and cost factors.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Applicable Clauses.pdf | ||
| fl215.txt | TXT text file |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF HOMELAND SECURITY
UNITED STATES COAST GUARD
BASE MIAMI BEACH
SPECIFICATIONS
FOR
Repair Fire Suppression System
GENERAL: United States Coast Guard Base Miami Beach is accepting proposals for qualified individuals or firms to repair fire suppression system located at BLDG 3, 4, 9 & 16. Prior to submitting a quote, it is mandatory to examine the scope of work, and it’s highly encouraged to visit the facility to take field measurements, evaluations, etc., and become familiar with existing conditions under which the work will be performed. After the award of contract, a pre-conference will be held prior to starting the work at Coast Guard Base Miami Beach.
LOCATION:
United States Coast Guard Base Miami Beach 100 MacArthur Causeway Miami, FL 33139
EXAMINATION OF SITE: It is HIGHLY ENCOURAGED that bidders carefully inspect the workplace and verify work necessary to complete the job. Prospective bidders arrange for a tour of the job site by calling the point of contact, Mr. Boris Abello at (305) 535-4564 or by e-mail at Boris.Abello@uscg.mil, at least 3 working days in advance.
I. CONTINUITY OF FACILITIES OPERATIONS: Schedule work to minimize interference with the facility’s normal operations. Normal operating hours are from 6:30am to 3:00pm Monday through Friday except federal holidays. Any work during other hours shall be requested in writing at least 5 working days in advance and must be approved by the Contracting Officer.
II. NOTIFICATION OF START/COMPLETION: The Contractor shall notify the Coast Guard one week prior to start of work, the start and projected completion date.
III. COAST GUARD CONTRACTING OFFICER REPRESENTATIVE: The Contractor shall contact the Contracting Officer’s Representative (COR) to coordinate all construction efforts onboard Coast Guard Facilities.
Mr. Boris Abello- COR Boris.Abello@uscg.mil 305-535-4564 CWO Ryan Romesberg-PWO Ryan.T.Romesberg@uscg.mil 305-535-4547 LT Benjamin Gonski- FE Benjamin.A.Gonski@uscg.mil 305-535-4589
IV. RECYCLING AND DISPOSAL OF REFUSE: Minor refuse, excess or waste materials resulting from construction operations may be disposed of in base dumpsters. All disposals shall be done in accordance with federal, state, and local laws and regulations. All bulk waste shall be disposed of in contractor provided dumpsters.
V. SAFETY: During the execution of this contract, the Contractor shall conform to the rules and regulations as set forth by OSHA Safety and Health Standards, 29 CFR Part 1926 - Safety and Health Regulations for Construction. The contractor shall have a written safety plan as required in FAR 5.236-13. The plan shall unequivocally assign responsibility and authority for safety to the superintendent by name. Immediate notification to the Contracting Officer’s Representative of lost time due to accidents is required. Provide two copies of workman’s compensation accident reports by noon of the day following the accident. The Coast Guard reserves the right to bar any workers or supervisors from the premises should they be documented as violating set safety standards and regulations.
VI. INSPECTION: The Contracting Officer’s Representative has the right to reject defective workmanship or materials or work not performed as per the project specifications. Only the mailto:Boris.Abello@uscg.mil
Contracting Officer or his/her representative may accept work performed by the contractor.
VII. OPERATIONS AND STORAGE: The contractor is to take whatever steps necessary to ensure that his materials are protected. The Coast Guard has no responsibility for receipt, storage, or protection of contractor’s materials. All equipment, materials and supplies shall be addressed to the contractor. The Coast Guard will not accept shipments. The contractor is responsible for the protection of existing structures, utilities, work and vegetation. Any damage shall be repaired at the contractor’s expense.
VIII. CONTRTACTOR IDENTIFICATION: The contractor and subcontractor personnel shall always wear company identification and carry personal identification.
IX. EXISTING UTILITIES: The Contractor shall field verify all utility locations before commencing work. This shall include, but not be limited to, the use of visual, sonic, electronic or magnetic detection devices. Contractor shall be responsible for repairing any utilities damaged during construction at no additional cost to the Government.
X. REGULATIONS WHILE ONBOARD COAST GUARD BASE MIAMI BEACH:
1. Daily colors and the raising/lowering of the American flag will take place every morning at 0800 and every evening at sunset. All personnel on Base will face the main flagpole & maintain silence and all vehicles & equipment will halt during these brief events.
2. The construction site shall always be maintained in a clean condition. This included daily clean-ups of the construction and storage areas (FAR 52.236-12). The site shall be well lit and well barricaded/cordoned off as appropriate.
3. Contractors are welcome to eat breakfast & lunch at Base in the base galley at cost.
Breakfast is served from 0630-0730 daily & lunch will be served from 1130-1230 daily in the galley. All personnel desiring meal service shall be in clean, non-soiled clothing.
The Coast guard reserves the right to refuse service to anyone it deems not hygienically acceptable.
4. There is one smoking area on base located in the central northern parking lot covered by the tiki hut. No smoking is permitted anywhere else on base.
5. Contractors are welcome to utilize the Base’s Exchange store; however, contracted personnel are prohibited from purchasing any uniform, alcohol or tobacco products.
6. Traffic Regulations:
a) 10 mph speed limit
b) No use of cell phones is permitted while driving vehicles or operating heavy machinery.
c) All personnel shall obey all marked traffic signals including stop signs & stop lights.
7. Absolutely no firearms or weapons of any kind are allowed onboard Base Miami Beach.
8. Only American citizens and permanent resident aliens are allowed onboard Base Miami
Beach Facilities. Absolutely no foreign nationals are permitted on the premises.
9. Notice shall be given to the Coast Guard’s representative 1 week in advance of any planned power, water, sewage or lighting outages.
10. The contractor shall provide a consolidated list of all contracted personnel including their driver’s license numbers (or other valid gov’t issued ID number) who will be working on Base Miami Beach Facilities either the day of or prior to the notice to proceed date.
11. Contractors are welcome to utilize the restrooms on the 1st decks of Buildings 3, 4, and 7 providing they are clean and do not track mud, dirt or any other debris into the restrooms.
12. Should warnings of gale force or stronger winds, or other inbound natural disasters be issued, the contractor shall take every practicable precaution to minimize the danger to persons, to the work, and the adjacent property. These precautions include closing all openings, removing all loose materials, tools and equipment from exposed locations, and removing or securing scaffolding, securing field trailers, and other appropriate equipment and other temporary work.
13. No personnel other than the Contracting Officer has the authority to alter the terms of any contract or to issue any change orders.
14. All contractor vehicles, equipment and gear onboard Coast Guard properties are always subject to search. Additionally, contractors are subject to orders to evacuate the property at any time.
15. Due to the compact & dense nature of operations & support functions ongoing on-board Base Miami Beach all efforts within reason to minimize the size and footprint of the contractor’s lay down area shall be taken. Contractors shall carpool as much as possible to minimize the number of vehicles needing parking on Base. At a minimum, the ratio of contractors to contractor vehicles shall be no less than 2:1.
16. All piers and waterfront bulkheads on Base Miami Beach are restricted in some form. If contractors need to bring heavy equipment (cranes, forklifts, 18 wheelers, man-lifts, construction equipment, backhoes, excavators or other equipment heavier than standard sedans) closer than 40’ to any pier or waterfront bulkhead on Base to complete their project, the contractor shall submit a request for information (RFI) to the COR at least 1 week in advance.
17. The entrance bridge to Base Miami Beach is an HS20-44 rated bridge. Contractor cannot exceed this rating. If the combined vehicle, trailer, and payload weight is over 50,000 lbs.
the contractor shall submit an RFI to the COR at least 1 week in advance.
XI. SCOPE OF WORK:
1. Below work will be completed onboard at Base Miami Beach.
2. Contractor shall provide ALL labor and materials necessary to complete the project.
3. Contractor shall comply with submittal requirements if applicable.
4. Contractor shall protect all equipment and merchandise in work locations.
5. Contractor shall secure water to BLDG 3 fire suppression system using isolation valves.
6. Contractor shall replace two (2) waterflow switches and (2) butterfly control valves located on the 1st, 2nd and 3rd deck of BLDG 3.
7. Contractor shall repack two (2) 6” OS&Y valves on fire backflow located on the West side of BLDG 3, stair risers.
8. Contractor shall remove and replace approx. 30’ of 4” standpipe located on the West side of BLDG 3, stair risers.
9. Contractor shall remove and replace three (3) 4” couplings located on the West side of
BLDG 3, stair risers.
10. Contractor shall remove and replace six (6) 4”x2- 1/2” mechanical Tees located on the
West side of BLDG 3, stair risers.
11. Contractor shall remove and replace six (6) 2-1/2” couplings located on the West side of
BLDG 3, stair risers.
12. Contractor shall remove and replace four (4) 4” riser clamps located on the West side of
BLDG 3, stair risers.
13. Contractor shall remove and replace approx. 42” of 2-1/2” fire sprinkler pipe located on the West side of BLDG 3, stair risers.
14. Contractor shall energize water and ensure no leaks on newly plumbed components.
15. Contractor will ensure water is secure by way of isolation valves for fire pump located in the fire pump room at BLDG 3.
16. Contractor shall provide and connect a temporary fire pump if the existing fire pump and/or fire water system will be out of service for more than 8 hours. After work hours and overnight, the building must have adequately pressurized fire water; under no circumstances will the building be left without adequate fire water overnight or after work hours.
17. Contractor shall disconnect all electrical power to the existing fire pump and lock out, tag out.
18. Contractor shall remove casing.
19. Contractor shall remove 4 swing bolts and 4 nuts and replace them with 4 new swing bolts and 4 new nuts.
20. Contractor will remove 5 inboard and 5 outboard Teflon packings and replace it with 5 new inboard and 5 new outboard Teflon packings.
21. Contractor shall remove 2 inboard and 2 outboard bearings and replace them with 2 new inboard and 2 new outboard bearings.
22. Contractor shall grease new bearings.
23. Contractor shall replace all old gaskets with new gaskets.
24. Contractor shall remove 6” OS&Y valve on suction side and all related fittings.
25. Contractor shall replace with new 6” OS&Y Valve on suction side and all new related fittings.
26. Contactor shall remove ¾” 175 PSI CRV valve and all related drain CPVC piping.
27. Contractor shall replace with new ¾” 175 PSI CRV valve and all new related drain
CPVC piping.
28. Contractor shall replace 2 suction gauges and replace with 2 new suction gauges.
29. Contractor shall replace 2 discharge gauges and replace them with 2 new discharge gauges.
30. Contractor shall replace 2 controller gauges and replace them with 2 new controller gauges.
31. Contractor shall unclog ball drip valve.
32. Contractor shall reconnect all power to pump and remove the lockout/tag out and re-energize water supply to pump.
33. Contractor shall test run for 10 minutes.
34. Contractor shall perform flow test on the tuned-up pump through the test headers with hose monsters. USCG personnel shall be present while test is performed.
35. Contractor shall ensure that fire pump operates in a smooth efficient manner, has no leaks present, and motor and controller operate properly as designed.
36. All installations shall be completed in accordance with all applicable manufacturers’ instructions and/or recommendations.
37. Contractor shall provide operations and maintenance training on the system to include controls to Facilities Engineering staff.
38. Contractor shall troubleshoot fire pump control panel and ensure proper operation or provide report with deficiencies and corrective action.
39. Contractor shall secure water by way of isolation valve at BLDG 16.
40. Contractor shall remove and replace one (1) 4” butterfly valve and all related piping and fittings located on the backflow suction side at BLDG 16.
41. Contractor shall energize water and ensure there are no leaks in the newly plumbed area.
42. Contractor shall secure water by way of isolation valve at BLDG 9.
43. Contractor shall remove and replace jockey pump.
44. Contractor shall remove and replace pressure switch on pump controller.
45. Contractor shall test system ensuring proper operation and maintained pressure or troubleshoot further providing report of deficiencies and corrective action.
46. Contractor shall reenergize water and ensure proper operation and no leaks.
47. Contractor shall provide operation and maintenance manuals for newly installed jockey pump.
48. Contractor shall be responsible for the removal of all trash and debris from project area upon completion.
All work must be approved by the Contracting Officer’s Representative.
XII. SUBMITTALS: If applicable, submittals shall be approved before procurement, fabrication, or delivery of items to the job site. Partial submittals will not be accepted and will be returned without review. Submittals shall include the manufacturer's name, trade name, catalog model or number, nameplate data, size, layout dimensions, capacity, project specification and paragraph reference, applicable Federal, Military, industry and technical society references, and other information necessary to establish contract compliance of each item the Contractor proposes to furnish. Failure to furnish required submittals can be cause rejection of the material.
Approval of submittals shall not relieve the contractor his obligation to comply with the contract specifications and drawings.
1. Manufacturer's Installation Instructions (3 each)
Where installation procedures or any part hereof are required to be in accordance with the instructions of the manufacturer for the material being installed, printed copies of these instruction and/or recommendations shall be furnished to the Contracting Officer prior to installation. Installation of the item will not be allowed until the instruction and/or recommendations are received. Failure to furnish these documents can cause rejection of the material. With this submittal, explicitly identify in writing any differences between manufacturer's instructions and the requirements specified herein.
2. Operation and Maintenance Manuals (3 each)
Furnish an operation and maintenance manual section for each item of equipment.
Furnish three copies of the complete manual bound in hardback binders. Furnish one complete manual prior to the time that equipment tests are performed and furnish the remaining manuals before the contract is completed. Inscribe the following identification on the cover: the words "OPERATION AND MAINTENANCE MANUAL", the name and location of the equipment, the name of the contractor, and the contract number. The manual shall include the names, addresses, and telephone numbers of each subcontractor installing equipment, and of the local representatives for each item of equipment. The manual shall have a table of contents and be assembled to conform to the table of contents with the tab sheets placed before instructions covering the subject. The instructions shall be legible and easily read, with large sheets of drawings folded in. The manual shall include: a complete description of the system, wiring and control diagrams with data to explain detailed operation and control of each item of equipment; a control sequence describing start-up, operation and shut-down instructions; installation instructions; maintenance instructions; lubrication schedule including type, grade, temperature range, and frequency; safety precautions, diagrams, and illustrations; test procedures; performance data; and parts list. The parts lists for equipment shall indicate the sources of supply, recommended spare parts, and the service organization, which is reasonably convenient for the project site. The manual shall be complete in all respects for equipment, controls, accessories, and associated appurtenances provided. Submit an electronic copy of Operation and Maintenance Manuals with all documents scanned to PDF format on a CD-ROM disk.
3. Operating Instructions (3 each)
Furnish manufacturer's operating instructions for the principal mechanical and electrical components, for use by operating personnel. A copy shall be provided in each of the three operations and maintenance manuals. The fourth copy shall be laminated between thermoplastic sheets and affixed where directed by COR adjacent to each item of equipment. Operating instructions shall not face when exposed to sunlight and shall be secured to prevent easy removal or peeling. The operating instructions shall include wiring diagrams, control diagrams, and control sequences for each principal item of equipment. The instructions shall describe the functions of the equipment, its most economical operation, start-up and shutdown procedures, procedures to follow in the event of failure, normal maintenance practices, and caution and warning notices. Submit an electronic copy of Operating Instructions with all documents scanned to PDF format on a CD-ROM disk.
XIII: WARRANTY: Submit three signed copies of Manufacturer’s Product Warranty for entrance system as follows:
1. Warranty Period: One year from date of completion of the project, provided that the limited warranty begins in no event later than six months from date of shipment by manufacturer. Ensure warranty language is identical to “as approved” version of the sample warranty submitted and returned from the COR and one year warranty for labor.