SoW B1204 lift pump purchase_v1.pdf
PDF 79 KB Posted
- Attached to
- Lift Station Pump - Offutt AFB, NE Federal contract opportunity
- Solicitation number
- FA460024Q0126
About this file
This document is a Statement of Need (SoN) for the purchase of a new lift station pump and motor for Offutt Air Force Base in Nebraska. The key details are:
The government is seeking to purchase a new submersible sewage lift station pump and motor with the following specifications: 460/230V, 3-phase, 60 Hz, 32.3/64.6 Amps, 1777 RPM, 25 HP. The new pump must have a 6-inch discharge outlet, maximum flow of 151 GPM at 105 feet of head, and weigh no more than 940 lbs. The pump and motor shall have NEMA L ratings, NEMA B motor, MG1 and IEC 60034-30 efficiency, and Class H insulation. The unit must have a closed-loop cooling system with non-toxic glycol/water mixture. The contractor will not be responsible for installation, but must provide a minimum 1-year warranty. The government is not requiring the new pump to match the existing Sulzer model.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA460024Q0126 - Combo Solicitation SAM - Lift Pump_Final.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Need
Project Title: B1204 lift station pump purchase NextGen Work Task #: WT 14883939
1. Objectives:
The scope of work is to purchase and provide a new lift station pump and motor. The existing pump is a Sulzer model ABS XFP-PE3-150G-CB1.7-PE185_4G-FM, (this is for informational purpose only. The government is not requiring that the new pump be replaced with the same brand or model).
The new pump and motor shall be submersible sewage type rated at 460/230V, 3ph, 60 Hz, at 32.3/64.6 Amp, 1777 rpm, and 25 hp. The new unit shall be rated NEMA L, with a motor rating of NEMA B, MG1, and IEC 60034-30 efficiency. Motor insulation shall be class H. The unit shall have a closed loop cooling system filled with a non-toxic glycol/water mixture. The new pump shall have a discharge outlet of 6”, a max flow of 151 gpm at 105’ head, and shall weigh no greater than 940 lbs.
The Contractor shall not be installing the new equipment.
The Contractor shall provide at least a 1-year warranty on all new materials.