SOW Attachment 10 - Site Self-Assessment X-Matrix.xlsx

XLSX spreadsheet 19 KB Posted

Attached to
C1DA--693-22-700 EHRM Infrastructure Upgrades Design Wilkes-Barre, PA VAMC
Solicitation number
36C77622R0071
Issued by

About this file

This pre-solicitation notice seeks Statements of Qualifications from firms for a design contract with the Department of Veterans Affairs. The project involves upgrading infrastructure at the Wilkes-Barre VA Medical Center in Pennsylvania to support a new Electronic Health Record Modernization system. Design services include assessing electrical, HVAC, communications, security and evaluating an on-site data center. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses. The period of performance for design completion is 301 calendar days from notice of award. Construction period services such as responding to requests for information, site visits and as-built documentation are optional line items. Statements of Qualifications are due May 12th and are limited to 50 pages. Firms will be evaluated on qualifications, capacity, experience, past performance and local knowledge. The highest rated firms will be invited to provide written responses on project management, challenges and design approach.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

XMatrix Summary

StationLocationNameBuildingRoomCablingPatch PanelsFiberPowerBondingUPSDedicated CoolingTempHumidityRacks SensorsSpaceNotes
693Wilkes-Barre VAWilkes-Barre VA1AG-38XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1CB-4AXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1N1-129XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1A1-30XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1N2-55XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1A2-66XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C2-106BXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1A3-07XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C3-57BXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1A4-40XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1N4-89XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C4-57BXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C5-57BXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C6-58XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C7-55XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C8-54BXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C9-44XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C10-30XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1C11-29XXXXXXXXXXNOverify port count/equipment
693Wilkes-Barre VAWilkes-Barre VA1AG-26BXXXXXXXXXXXroom dimensions
693Wilkes-Barre VAWilkes-Barre VA1N3-93NONONONONONONONONONONOdoes not exist, out of scope
693Wilkes-Barre VAWilkes-Barre VA1C1-22BXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1204XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA1N3-96XXXXXXXXXXXroom dimensions
693Wilkes-Barre VACommunity Living Center272-148XXXXXXXXXXX
693Wilkes-Barre VACommunity Living Center273-149XXXXXXXXXXX
693Wilkes-Barre VACommunity Living Center274-96AXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA2112XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA3111XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA55-110XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA6134XXXXXXXXXXX96 portsno port count
693Wilkes-Barre VAWilkes-Barre VA35IT ClosetXXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA421C-32XXXXXXXXXXX
693Wilkes-Barre VAWilkes-Barre VA11EG-30XXXXXXXXXXX
VAMC TOTALS3333333333333333333333321
StationLocationNameBuildingRoomCablingPatch PanelsFiberPowerBondingUPSDedicated CoolingTempHumidityRacks SensorsSpaceNotes
693Wilkes-Barre VAAllentown VA Outpatient ClinicAOPC217XXNONOXXXXXXNOmay be adequate
693Wilkes-Barre VASayre VA Outpatient ClinicSOPC163XXNONOXXXXXXX
693Wilkes-Barre VAWilliamsport Outpatient ClinicWOPCIT ClosetXXNONOXXXXXXX
693Wilkes-Barre VATobyhanna Army DeptTOBYIT ClosetXXNONOXXXXXXX
693Wilkes-Barre VANorthhampton County Outpatient ClinicNorthamptonIT ClosetXXNONOXXXXXXX
693Wilkes-Barre VAColumbia County Outpatient ClinicBerwick114NONONONOXXXXXXNOmay be adequate
693Wilkes-Barre VAWayne County Outpatient ClinicHonesdale144NONONONONONONONONONONO
StationData CenterBuildingBuildingRoomSpaceHVACCable DistroWANUPSNOTES
1C1-20XXXXXunorthodox room dimension fairly narrow considering length, room size appears to be small compared to rack count (750sq ft vs 37 racks). HVAC adequate if they can find space for JSA/FDSS. UPS adequate for critical load but no redundancy.
General Notes
X~included in scope of NRM project
NO~not included in scope
TR Notes
Cabling:
Fiber:
Power:
Data Center Notes
WAN Demarc in old PBX room C1-22E (10 ft away)

Riverbed/Netscout and Core switches are in the DC. DC C1-21A and C1-22A is open space with 8in raised Floors and approx 9ft clearance from floor to ceiling Most interior cable/fiber distribution is below, exterior is above. Air distribution is below issues wiith cooling/distribution C1-21B has vista imaging, 4 full racks, own dedicated split system

2000 sq ft total including PBX (C1-21A, 22A, 21B, 21C, C1-22E) 1500 excluding PBX (C1-22E) no WAN diversity on current dedicated lines, there is a possible diverse physical path but isn't being used and not sure if useable by the LEC

*CRACs: Primary CRAC @ 52kW can support extra 10kW (22+10=32kW) (based on numbers) but have aged out 22 yrs old redundant system newer (2020) and @ 60kW

*Power:
UPS @ 72kW pulling 22kW so Power is sufficient enough to accept JSA/FDSS (22+10 =32kW) (located in basement)

UPS has no redundancy and also serves Biomed equipment

Is the Data Center able to accept the JSA and FDSS at the time of scoping?
JSA - ReadinessSpace good, CRAC numbers are adequate but definitely has distribution issues, UPS Good but no redundancy
FDS -ReadinessSpace good, CRAC numbers are adequate but definitely has distribution issues, UPS Good but no redundancy