STATEMENT OF WORK
SOUTHWEST REGIONAL MAINTENANCE CENTER
Technical Support
1. BACKGROUND
SWRMC has an APC Rack Mount Symmetra LS chassis with servers installed. The current air conditioning unit installed in the server stack is an InRow RD 300mm Air Cooled 208-230V 60 Hz (Serial Number: UK1124211552, Product ACRD100). The AC unit has malfunctioned and needs to be repaired in order to ensure the servers do not overheat.
An inspection of the unit resulted in the following findings:
· Unit had low suction pressure alarm. Problem with refrigerant pressure.
· Sight glass is flushing and the moisture indicator shows contamination (brown instead of green).
· Cooling equipment is off line.
1. SCOPE
Repair one (1) APC ACRD 100 air conditioning unit (Serial Number: UK1124211552). The Contractor shall provide the repair services and parts. The contractor shall recertify the InRow RD 300mm Air Cooled 208-230V 60 Hz (Serial Number: UK1124211552, Product ACRD100) air conditioning unit with Schneider Electric.
1. REQUIREMENTS
The contractor shall:
1. Repair one (1) InRow RD 300mm Air Cooled 208-230V 60 Hz (Serial Number: UK1124211552, Product ACRD100) air conditioning unit and ensure form and function to the current APC Rack Mount Symmetra LS chassis. The repair shall result in the InRow RD 300mm Air Cooled 208-230V 60 Hz (Serial Number: UK1124211552, Product ACRD100) air conditioning working seamlessly within the APC Rack Mount Symmetra LS chassis and shall not degrade any part of the current system.
1. Vendor shall recover the total charge and leak test unit.
1. Conduct pressure test to verify there are no leaks in the system. Leaks must be repaired if found.
1. Repair technician must be a Schneider Electric certified technician.
1. Contractor shall recertify the APC ACRD 100 (Serial Number: UK1124211552) with Schneider Electric once repaired.
1. Vendor shall provide a report or certificate to show the unit has been recertified with Scheider Electric.
1. PERIOD OF PERFORMANCE
Upon Awarded – 20 May 2022
1. PLACE OF PERFORMANCE
Southwest Regional Maintenance Center, San Diego, CA, Building 3339, 2nd Floor, Room 200