Project No. PWF-01801-0P Purchase LED Lighting & Associated Equipment
USAG Fort Devens Devens MA 01434
SPECIFICATIONS
LED LIGHTING AND ASSOCIATED EQUIPMENT
SOUTH POST LED LIGHTING
PART 1
1.1 GENERAL
Lighting systems in various buildings require lifecycle replacement to more efficient LED systems. The contractor shall provide the LED lighting fixtures, fixture integrated controls, standalone occupancy sensor controls, LED lamps, and start-up support as listed here within. These items are being purchased as a lot as listed on the Bill of Materials.
This is a material-only project, all installation will be performed by Fort
Devens in-house labor. Equipment needed to install the fixtures is limited to those items specifically identified in the model # within the bill of materials.
Product 2.2.3 is eligible for distributor-level incentives through the utility sponsored MassSave Program, as the installation location is served National
Grid Electric. Fort Devens shall provide the necessary National Grid account information upon request.
1.2 SUBMITTALS
Product Data
Prior to ordering equipment, submit manufacturer product and performance data, installation instructions, operations and maintenance instructions, and warranties for each item listed in the Bill of
Materials. Owner shall complete submittal review within 5 business days of submission.
PART 2 PRODUCTS
2.1 General Equipment Requirements
All new LED fixtures, fixture retrofit kits, and LED lamps are required to be listed by the Design Lights Consortium,and must meet DLC
Technical requirements for Indoor luminaires or Indoor Retrofit Kits.
All LED fixtures, fixture integrated controls, and LED lamps must come with a minimum manufacturer’s equipment warranty of 5 years, and shall be UL Listed. The warranty is for materials only and does not include labor for replacement of defective product.
2.2 Bill of Materials (LOT)
Item Qty Manufacturer and Model #
2.2.1 41
METALUX BAA-VHB-24-W-UNV-L840-CD-SVPD3-U-HBAYC-CHAIN/SET/U
HIGH BAY LED FIXTURE WITH INTEGRATED OCCUPANCY SENSOR AND
DIMMING CONTROL (OR EQUAL)
2.2.2 16
METALUX BAA-VHB-24-W-UNV-L840-CD-SVPD3-U-VHB-SPM HIGH BAY
LED FIXTURE WITH INTEGRATED OCCUPANCY SENSOR AND DIMMING
CONTROL (OR EQUAL)
2.2.3 16
METALUX BAA-SSLED-LD5-24-M-UNV-L840-CD-2-TCB/SHK=PC3/120-
SVPD3-U HIGH BAY LED FIXTURE WITH INTEGRATED OCCUPANCY
SENSOR AND DIMMING CONTROL (OR EQUAL)
2.2.4 4
COOPER LIGHTING ISHH-01 INTEGRATED SENSOR PROGRAMMING REMOTE
(OR EQUAL)
2.2.5 8
METALUX TAA-24-FPX-47-L840-HE LED FLAT PANEL FIXTURE 2’X 4’,
40K (OR EQUAL)
2.2.6 2
4WSNLED-LD4-44SL-F-UNV-L840-CD1-U WRAP-AROUND LED FIXTURE
(OR EQUAL)
2.2.7 1 LUMARK AXCS3ARL EXTERIOR LED FIXTURE (OR EQUAL)
2.2.8 220 ARCHIPLELAGO LIGHTING LT8F41541UE 4’ T8 LED Lamp (OR EQUAL)
2.2.9 10 ARCHIPLELAGO LIGHTING LT8F41541UE 2’ T8 LED Lamp (OR EQUAL)
2.2.10 1
WATTSTOPPER DT-300-U (DUAL TECHNOLOGY CELING MOUNT OCCUPANCY
SENSOR), WATTSTOPPER BZ-50-U (RELAY PACK) (OR EQUAL)
2.2.11 1
WATTSTOPER DW-100-W-U WALL SWITCH DUAL TECH OCC SENSOR (OR
EQUAL)
2.2.12 1
SIX (6) HOURS ON-SITE TRAINING IN TWO (2) THREE (3) HOUR
SESSIONS ON CONFIGURATION OF FIXTURE INTEGRATED CONTROLS
INCLUDED IN ITEMS 2.2.1, 2.2.2, 2.2.3, AND 2.2.4. TRAINING
SHALL BE BY MANUFACTURER’S REPRESENTATIVES WITH DETAILED
KNOWLEDGE OF THE PROJECT CONTROLS.
2.2.1 Linear High-Bay LED Lighting Fixtures and associated equipment
LED light fixture designed for high-bay application. Fixture requirements include:
Buy American Act preferred cULus listed for damp locations
-40°C to 55°C ambient environments with 0-10V drivers
RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards
DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium
24,000 lumen package, minimum 80 Color Rendering Index (CRI), 4000K
Correlated Color Temperature (CCT)
Chain mounting kit
Integrated occupancy and daylight dimming sensor with 1200 sq ft coverage, suitable for 15-40’ mounting height. Integrated controls shall be capable of configuration via a hand-held remote control.
Controls shall be capable of high-level trim, daylight dimming, and bi-level dimming based on occupancy. Output levels for occupied, standby, and unoccupied shall be custom set using the remote configurator. No network lighting controls are permitted.
Minimum 5-year manufacturer’s material warranty
2.2.2 Linear High Bay LED Lighting Fixtures and associated equipment
LED light fixture designed for high-bay application. Fixture requirements include:
Buy American Act compliant
-40°C to 55°C ambient environments with 0-10V drivers
RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards
DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium
24,000 lumen package, minimum 80 Color Rendering Index (CRI), 4000K
Correlated Color Temperature (CCT)
Single mounting point kit
Integrated occupancy and daylight dimming sensor with 1200 sq ft coverage, suitable for 15-40’ mounting height. Integrated controls shall be capable of configuration via a hand-held remote control.
Controls shall be capable of high-level trim at customized level,and bi-level dimming based on occupancy. Output levels for occupied, standby, and unoccupied shall be custom set using the remote configurator.
2.2.3 Round High Bay LED Lighting Fixtures and associated equipment
Buy American Act compliant
-40°C to 55°C ambient environments with 0-10V drivers
RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards
DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium
24,000 lumen package, minimum 80 Color Rendering Index (CRI), 4000K
Correlated Color Temperature (CCT)
Single mounting point kit
Integrated occupancy and daylight dimming sensor with 1200 sq ft coverage, suitable for 15-40’ mounting height. Integrated controls shall be capable of configuration via a hand-held remote control.
Controls shall be capable of high-level trim, daylight dimming, and bi-level dimming based on occupancy. Output levels for occupied, standby, and unoccupied shall be custom set using the remote configurator.
This line item is eligible for distributor-level incentives through the utility sponsored MassSave Program, as the installation location is served
National Grid Electric. Fort Devens will supply all required electric account information upon request.
2.2.4 Handheld Remote Control for configuration of fixture integrated controls
Handheld infrared remote controller for programming of integral SVPD3 occupancy and dimming controllers on high bay fixtures in items 2.2.1 through
Capabilities must include the ability to set:
Occ sensor delays and sensitivity
Daylight dimming control
Occupied, standby, and unoccupied light level settings, time delays
Network lighting control systems are not acceptable.
2.2.5 Flat Panel LED Fixture
TAA compliant
UL listed
DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium
4700 lumen, 4000K CCT, minimum 80% CRI lumen package
Fixture depth less than 3”
Minimum 5-year material warranty
2.2.6 LED Wrap Around Fixture
TAA compliant
UL listed, suitable for damp location
Cold-rolled steel construction for fixture chassis
DesignLights Consortium® Qualified and classified for DLC Standard a
4400 lumen, 4000K CCT, minimum 80% CRI lumen package
2.2.7 Wall mount exterior LED floodlight
Buy American Act Compliant
UL listed for wet locations
Cast aluminum construction
DesignLights Consortium® Qualified and classified for DLC Standard and DLC Premium
Refractive lens
Minimum of 140 lumens per watt
Equipped with integral photocell for dusk to dawn control
Knuckle mounting with ½” NPT threaded pipe
2.2.8 T8 LED lamp, ballast bypass, 4’
Compatible to Ballast (UL-A) and Bypass (UL-B) T8 retrofit applications, with UL0B being either single or double ended.
Compatible with both shunted and non-shunted lamp-holders
DesignLights Consortium® Qualified and classified for DLC Standard
Suitable for enclosed, dry, and damp locations
4100K CCT, minimum 80% CRI, minimum 1200 lumens
140 minimum lumens per watt
2.2.9 T8 LED lamp, ballast bypass, 2’
Compatible to Ballast (UL-A) and Bypass (UL-B) T8 retrofit applications, with UL-B being either single or double ended.
Compatible with both shunted and non-shunted lamp-holders
DesignLights Consortium® Qualified and classified for DLC Standard
Suitable for enclosed, dry, and damp locations
4100K CCT, minimum 80% CRI, minimum 1200 lumens
140 minimum lumens per watt
2.2.10 Ceiling mount occupancy sensor, dual technology, with relay
Buy American Act Compliant (occupancy sensor only)
360-degree sensing utilizing both ultrasonic and passive infrared (PIR) occupancy detection.
Coverage area up to 1000 square feet
Adjustable sensitivity, time delay
Walk-through mode with shorter delay
Auxiliary contracts for use
Relay pack for switching of line voltage loads, universal line voltage
2.2.11 Wall-mount occupancy sensor, dual technology
Buy American Act Compliant (occupancy sensor only)
180-degree sensing utilizing both ultrasonic and passive infrared (PIR) occupancy detection.
Adjustable sensitivity, time delay
Walk-through mode with shorter delay
Auto-on and manual-on operating mode options
2.2.12 Factory Trained Lighting Controls Start-up Support
Upon completion of the installation by others, provide two (2) sessions of up to three (3) hours each of training/start-up support for the fixture integrated controls in items 2.2.1, 2.2.2, 2.2.3, and 2.2.4.
Training/support will be provided by fixture manufacturer representatives for Massachusetts with detailed knowledge of the controls’ configuration and operation.
Fort Devens will coordinate the first visit after new high-bay fixtures have been installed and powered in the first building; the second visit will be arranged after the remaining two buildings are completed.
-- End of Section --