Statement of Objectives for HVAC Server Room Maintenance and Support for the Selective Service System
Solicitation number
SOO_2024_0001_SSS
Issued by
Not on record

About this file

This document is a Statement of Objectives (SOO) for a federal contract opportunity to provide HVAC server room maintenance and support services for the Selective Service System (SSS) at their headquarters in Arlington, VA.

The SOO outlines the government's objectives and requirements for a contractor to perform routine maintenance, emergency repairs, preventive measures, energy efficiency improvements, periodic testing and inspection, and repair/replacement of HVAC components for the 2 HVAC units servicing the SSS server room. The contractor will be required to meet performance metrics related to response time, system uptime, maintenance completion, and energy savings. The government anticipates awarding a firm-fixed price contract with a 12-month base period and up to two 12-month option periods. Proposals are due by June 27, 2024. Participating contractors must be registered in SAM.gov.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Source Selection Information — See FAR 2.101 and 3.104

STATEMENT OF OBJECTIVES (SOO)

Selective Service System (SSS)

IT Directorate

Project Title: HVAC Server Room Maintenance and Support Project

Arlington, VA

June 13, 2024 https://www.acquisition.gov/far/part-2#FAR_2_101 https://www.acquisition.gov/far/part-3#FAR_3_104

INSTRUCTIONS TO VENDORS CONCERNING THE SOO

Project Title: HVAC Server Room Maintenance and Support Project

PROGRAM OBJECTIVES:

1. The purpose of this Statement of Objectives (SOO) is to obtain a contractor/business partner to support the maintenance support and repair of the existing HVAC server room (2 units) at the Selective Service System National Headquarters located in Arlington, VA. The successful contractor shall be responsible for all the specifications and requirements described herein.

2. Accordingly, please provide your narrative quote describing to the Government how you would meet the specifications and objectives with the desired outcomes.

3. Contractor questions related to this SOO shall be submitted by Thursday, June 20th at 2:00 PM, Eastern Standard Time (EST) to the SSS Contract Specialist, Cane Toussaint, at Cane.Toussaint@sss.gov and the SSS Contracting Officer, Georgette Hendricksen, at Georgette.Hendricksen@sss.gov

4. Final contractor submittals in response to this SOO shall be submitted by Thursday, June 27th at 2:00 PM EST to the above contracting representatives.

5. Participating contractors shall be registered in SAM.gov https://www.acquisition.gov/far/part-2#FAR_2_101 https://www.acquisition.gov/far/part-3#FAR_3_104 mailto:Cane.Toussaint@sss.gov mailto:Georgette.Hendricksen@sss.gov

Statement of Objectives (SOO) for the

HVAC Server Room Maintenance and Support Project

1.0 Purpose

The Selective Service System (SSS) IT Directorate requires a vendor develop an innovative solution to provide routine maintenance, troubleshooting, emergency repairs, preventive measures, and energy efficient methods and support to the HVAC Server Room (2 units) located at SSS National Headquarters at 1501 Wilson Blvd, Suite 700, Arlington, Virginia.

2.0 Background

The Selective Service System's (SSS) mission is to register men and maintain a system that, when authorized by the President and Congress, rapidly provides personnel in a fair and equitable manner while managing an alternative service program for conscientious objectors. The agency registers approximately 2 million men annually.

The SSS has approximately 120 full-time employees to support its National Headquarters, three regional headquarters, and our Data Management Center in geographically dispersed areas. The agency also has up to 56 state directors, and part-time employees representing the 50 states, Guam, the Northern Mariana Islands, Puerto Rico, the U.S. Virgin Islands, America Samoa, the District of Columbia, and New York City.

3.0 Scope

The HVAC Server Room should continue to function trouble-free at the optimum temperatures for maintaining the IT equipment housed in this facility. The Government is seeking a vendor capable of performing the following outcomes: 1) Routine Maintenance; 2) Emergency Repairs; 3) Preventive Measures; 4) Energy Efficiency; 5) Periodic Testing and Inspection and 6) Preventive Maintenance; 7) Response to Trouble Calls; Repair and Replacement of components, parts and supplies as needed and warranty criteria.

4.0 Performance objectives (required results)

The capable vendor shall perform HVAC service room maintenance and support services that provide for the following:

1. Routine Maintenance:

o Regularly inspect and service air conditioning units as per manufacturer guidelines.

o Clean filters, coils, and condenser units.

o Lubricate moving parts.

o Check refrigerant levels and adjust as needed.

o Verify electrical connections and controls.

2. Emergency Repairs:

o Respond promptly to any system breakdowns or malfunctions.

o Diagnose issues and perform necessary repairs.

o Ensure minimal downtime for critical areas.

3. Preventive Measures:

o Implement measures to prevent system failures.

o Identify potential issues and address them proactively.

o Recommend system upgrades or replacements when necessary.

4. Energy Efficiency:

o Optimize system performance to reduce energy consumption.

o Advise on energy-saving practices.

o Monitor and adjust thermostat settings.

4.1 Test and Inspect

Inspect and test equipment to determine its operating condition and efficiency. Typical activities include:

Testing - for excessive vibration; motor winding resistance; refrigerant charge; fan RPM;

refrigerant oil (acid); water condition; flue gas analysis; safety controls; combustion and draft;

crankcase heaters; control system(s), etc.

Inspecting - for worn, failed or doubtful parts; mountings; drive couplings; oil level; rotation;

soot; flame composition and shape; pilot and igniter; steam, water, oil and/or refrigerant leaks, etc.

4.2 Preventive Maintenance

Clean, align, calibrate, tighten, adjust, and lubricate equipment. These activities are intended to extend the equipment’s life and assure proper operating condition and efficiency. Typical activities include:

- Cleaning coil surfaces; fan impellers and blades; electrical contacts; burner orifices; passages and nozzles; pilot and igniter; cooling tower baffles, basin, sump, and float; chiller, condenser, and boiler tubes, etc.

- Aligning belt drives; drive couplings; etc.

- Calibrating safety controls; temperature and pressure controls, etc.

- Tightening electrical connections; mounting bolts; pipe clamps; refrigerant piping fittings;

damper sections, etc.

- Adjusting belt tension; refrigerant charge; super heat; fan RPM; water chemical feed and feed rate; burner fuel/air ratios; gas pressure; set point of controls and limits; compressor cylinder unloaders; damper close-off; sump floats, etc.

- Lubricating motors; fan and damper bearings; valve stems; damper linkages; fan vane linkages, etc.

4.3 Repair and Replace: Locating, ordering, expediting required replacements to repair or remove and replace broken, worn and/or doubtful components and or parts.

4.4 Trouble Calls: Unscheduled work resulting from abnormal or emergency conditions.

4.5 Components: Parts and Supplies - Components, parts, and supplies required to keep the equipment operating properly and efficiently with warranty conditions.

4.6 PERFORMANCE METRICS

The contractor’s performance will be evaluated based on the following metrics:

1. Response Time: Timely response to emergency repair requests.

2. System Uptime: Minimizing system downtime due to failures.

3. Maintenance Completion: Adherence to scheduled maintenance tasks.

4. Energy Savings: Demonstrated improvements in energy efficiency.

5. Scheduling for service calls (scheduled and unscheduled work).

4.7 OPERATING CONSTRAINTS

The contractor shall:

• Comply with safety regulations and industry standards.

• Coordinate maintenance schedules with facility occupants.

• Maintain accurate records of all services performed.

5.0 Type of Contract Contemplated

The Government anticipates a firm-fixed price contract award.

6.0 Period of Performance

The period of performance of this contract is on/about the end of June 2024 for a twelve-month base period with up to two 12-month option periods.

7.0 Place of Performance

Selective Service System National Headquarters 1501 Wilson Blvd, Suite 700 Arlington, VA 22209

8.0 Government information

Please see the specification document identifying the existing HVAC server room specifications (2 units) at Attachment 1

9.0 Contractor-Provided Draft Quality Control Plan (QCP) - The vendor shall provide a quality control plan to address the maintenance and support requirements.

10.0 Meetings

For all meetings, the contractor shall be responsible for providing meeting materials and administrative/facilitation support. Meetings will be conducted at either the SSS

National Headquarters Office at 1501 Wilson Blvd or through an alternative method of communication (such as a teleconference), as approved by the Contracting Officer (CO) and/or the Project Manager.

10.1 Post-Award Kickoff Meeting

Within 5 business days after contract award, the government will conduct a post-award kickoff meeting at the SSS National Headquarters Office (specific date and time to be mutually agreed upon).

10.2 Intermittent Project Status Reviews

At the sole discretion of the government, intermittent project status reviews may be conducted on an informal basis (by telephone or teleconference) or in person at the SSS National Headquarters office with 2 days advance notice as approved by the CO or Project Manager.

10.3 Monthly Project Status Reviews

Monthly status meetings to be conducted on the <insert date or description, e.g., first Monday> of each month. The contractor is responsible for reporting the previous month’s activities (including any risks, issues, or concerns, and actual or recommended actions for their mitigation), and projected activities for the following month.

10.4 Program Management Review

The government will conduct <insert monthly, quarterly, etc.> program management reviews at <insert location>, to review the progress of the program, identify any risks, issues, or concerns, and provide feedback on the contractor’s progress and performance. The contractor shall provide written data and verbal presentations as to the financial status of the <insert name of program> (projected vs. incurred costs), any identified any risks, issues, or concerns (and their mitigation or its plans for their mitigation.]

Notice to Vendors:

All information and data related to this project that the contractor gathers or obtains shall be both protected from unauthorized release and considered the property of the government. The Contracting Officer will be the sole authorized official to release verbally or in writing any data, draft deliverables, final deliverables, or any other written or printed materials pertaining to this contract. Press releases, marketing material, or any other printed or electronic documentation related to this project must not be publicized without the written approval of the Contracting Officer.

Document Revision History

(Post-award: for Modifications / Changes) Mod.

No. Description of Changes Requested

By Approved

By Date

None Initial version

Note: The document revision history is most useful for tracking changes in a major acquisition;

it may not be needed for less complex acquisitions. Pre-award, it can be used internally by the agency to track the origin of and/or changes to specific requirements (not included in the solicitation when released). Post-award, it can be used to provide a centralized list of changes incorporated by modification.]

SPLIT-SYSTEM HEAT PUMP

PLA-A.EA Series

MANUEL D’UTILISATION

Pour une utilisation correcte sans risques, veuillez lire le manuel d’utilisation en entier avant de vous servir du climatiseur.

OPERATION MANUAL

For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit.

MANUAL DE INSTRUCCIONES

Lea este manual de instrucciones hasta el final antes de poner en marcha la unidad de aire acondicionado para garantizar un uso seguro y correcto.

POUR L’UTILISATEUR

FOR USER

PARA EL USUARIO

English

Français

Español

VG79Y607H01_IM.indb 1 21-Nov-22 16:14:16

ATTACHMENT 1

en

Contents

1. Safety Precautions

► Before installing the unit, make sure you read all the “Safety Precautions”.

►The“SafetyPrecautions”provideveryimportantpointsre-
gardingsafety.Makesureyoufollowthem.
►Pleasereporttoortakeconsentbythesupplyauthoritybefore
connectiontothesystem.

Symbols used in the text Warning:

Describesprecautionsthatshouldbeobservedtopreventdangerof
injuryordeathtotheuser.

Caution:

Describes precautions that should be observed to prevent damage to the unit.

Symbols used in the illustrations : Indicates a part which must be grounded.

Caution:

•Donotuseanysharpobjecttopushthebuttons,asthismaydam-
agetheremotecontroller.

• Never block or cover the indoor or outdoor unit’s intakes or outlets.

Disposing of the unit When you need to dispose of the unit, consult your dealer.

Warning:

•Thereappliancesarenotaccessibletothegeneralpublic.
•Theunitmustnotbeinstalledbytheuser.Askthedealeroran
authorizedcompanytoinstalltheunit.Iftheunitisinstalledim-
properly,waterleakage,electricshockorfiremayresult.

• Do not alter the unit. It may cause fire, electric shock, injury or water leakage.

•Donotstandon,orplaceanyitemsontheunit.
•Donotsplashwaterovertheunitanddonottouchtheunitwith
wethands.Anelectricshockmayresult.
•Donotspraycombustiblegasclosetotheunit.Firemayresult.
•Donotplaceagasheateroranyotheropen-flameappliancewhere
itwillbeexposedtotheairdischargedfromtheunit.Incomplete
combustionmayresult.
•Donotremovethefrontpanelorthefanguardfromtheoutdoor
unitwhenitisrunning.
•Whenyounoticeexceptionallyabnormalnoiseorvibration,stop
operation,turnoffthepowerswitch,andcontactyourdealer.
•Neverinsertfingers,sticksetc.intotheintakesoroutlets.
•Ifyoudetectoddsmells,stopusingtheunit,turnoffthepower
switchandconsultyourdealer.Otherwise,abreakdown,electric
shockorfiremayresult.
•ThisairconditionerisNOTintendedforusebychildrenorinfirm
personswithoutsupervision.
•Youngchildrenmustbesupervisedtoensurethattheydonotplay
withtheairconditioner.
•Iftherefrigerationgasblowsoutorleaks,stoptheoperationofthe
airconditioner,thoroughlyventilatetheroom,andcontactyour

dealer.

•Thisapplianceisintendedtobeusedbyexpertortrainedusersin
shops,inlightindustryandonfarms,orforcommercialusebylay

persons.

•Thisappliancecanbeusedbychildrenagedfrom8yearsand
aboveandpersonswithreducedphysical,sensoryormentalca-
pabilitiesorlackofexperienceandknowledgeiftheyhavebeen
givensupervisionorinstructionconcerninguseoftheappliance
inasafewayandunderstandthehazardsinvolved.Childrenshall
notplaywiththeappliance.Cleaningandusermaintenanceshall
notbemadebychildrenwithoutsupervision.
•Thisapplianceisnotintendedforusebypersons(includingchil-
dren)withreducedphysical,sensoryormentalcapabilities,or
lackofexperienceandknowledge,unlesstheyhavebeengiven
supervisionorinstructionconcerninguseoftheappliancebya
personresponsiblefortheirsafety.

• Children should be supervised to ensure that they do not play with the appliances.

•Wheninstallingorrelocating,orservicingtheairconditioner,use
onlythespecifiedrefrigerantwrittenonoutdoorunittochargethe
refrigerantlines.Donotmixitwithanyotherrefrigerantanddo
notallowairtoremaininthelines.
Ifairismixedwiththerefrigerant,thenitcanbethecauseofab-
normalhighpressureintherefrigerantline,andmayresultinan
explosionandotherhazards.
Theuseofanyrefrigerantotherthanthatspecifiedforthesystem
willcausemechanicalfailureorsystemmalfunctionorunitbreak-
down.Intheworstcase,thiscouldleadtoaseriousimpediment
tosecuringproductsafety.
•Thisunitshouldbeinstalledinroomswhichexceedthefloor
spacespecifiedinoutdoorunitinstallationmanual.Referto
outdoorunitinstallationmanual.
•Donotusemeanstoacceleratethedefrostingprocessortoclean,
otherthanthoserecommendedbythemanufacturer.
•Theapplianceshallbestoredinaroomwithoutcontinuouslyop-
eratingignitionsources(forexample:openflames,anoperating
gasapplianceoranoperatingelectricheater).
•Donotpierceorburn.
•Beawarethatrefrigerantsmaynotcontainanodour.

Note:

Thephrase“Wiredremotecontroller”inthisoperationmanualrefersonlytothePAR-41MAA.(Ifyouneedanyinformationforthe
otherremotecontroller,pleaserefertotheinstructionbookincludedineachremotecontroller.)

1. Safety Precautions

2. Parts Names

3. Operation

4. Timer

5. Emergency Operation for Wireless Remote-controller

6. Care and Cleaning

7. Trouble Shooting

8. Specifications

VG79Y607H01_IM.indb 1 21-Nov-22 16:14:16

2. Parts Names

■ Indoor Unit

PLA-A▪EA8

Fan steps 4 steps Vane Auto with swing Louver – Filter Long-life Filter cleaning indication 2,500 hr Enter the model setting number for the indoor unit you want to operate. 001

Air outlet Filter

Air intakeVane

Wired remote controller Wireless remote controller

MENU ON

OFFRETURN SELECT

HOLD

Remote controller (Optional parts)

VG79Y607H01_IM.indb 2 21-Nov-22 16:14:17

2. Parts Names

■ Wired Remote Controller

The functions of the function buttons change depending on the screen.

Refertothebuttonfunctionguidethatappearsatthebottomofthe
LCDforthefunctionstheyserveonagivenscreen.
Whenthesystemiscentrallycontrolled,thebuttonfunctionguide
thatcorrespondstothelockedbuttonwillnotappear.

▌1 [ON/OFF] button Press to turn ON/OFF the indoor unit.

▌2 [SELECT/HOLD] button Press to save the setting.

When the Main menu is displayed, pressing this button will enable/dis-able the HOLD function.

▌3 [RETURN] button Press to return to the previous screen.

▌4 [MENU] button Press to bring up the Main menu.

▌5 Backlit LCD Operation settings will appear.

When the backlight is off , pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen.

When the backlight is off , pressing any button turns the backlight on and does not perform its function. (except for the [ON/OFF] button)

▌6 ON/OFF lamp This lamp lights up in green while the unit is in operation. It blinks while the remote controller is starting up or when there is an error.

▌7 Function button [F1] Main display: Press to change the operation mode.

Menu screen: The button function varies with the screen.

▌8 Function button [F2] Main display: Press to decrease temperature.

Main menu: Press to move the cursor left.

Menu screen: The button function varies with the screen.

▌9 Function button [F3] Main display: Press to increase temperature.

Main menu: Press to move the cursor right.

▌0 Function button [F4] Main display: Press to change the fan speed.

Controller interface

MENU ON

OFFRETURN SELECT

HOLD

4 3 2 1

7 8 9 0

Function buttons

Main display

Menu screen Function guide

Main menu

Fri

Room

Set temp.

Mode Temp. Fan

Cool Auto

Main Main menu

Energy saving

Main display:

Cursor

Operation Vane·Louver·Vent. (Lossnay) High power Comfort

RETURN

7 8 9 0

7 8 9 0

7 8 9 0

VG79Y607H01_IM.indb 3 21-Nov-22 16:14:17

2. Parts Names

The main display can be displayed in two different modes: “Full” and “Basic”. The factory setting is “Full”. To switch to the “Basic” mode, change the setting on the Main display setting. (Refer to operation manual included with remote controller.)

<Full mode>

* All icons are displayed for explanation.

<Basic mode>

Display

Fri

Cool

Mode Temp. Fan

Set temp. Auto

Fri

Mode Temp. Fan

Room

Cool Set temp. Auto

▌1 Operation mode

▌2 Preset temperature

▌3 Clock

▌4 Fan speed

▌5 Button function guide Functions of the corresponding buttons appear here.

▌6 Appears when the ON/OFF operation is centrally controlled.

▌7 Appears when the operation mode is centrally controlled.

▌8 Appears when the preset temperature is centrally controlled.

▌9 Appears when the filter reset function is centrally controlled.

▌0 Indicates when filter needs maintenance.

▌1 Room temperature

▌2 Appears when the buttons are locked.

▌3 Appears when the On/Off timer or Auto-off timer function is enabled.

appears when the timer is disabled by the centralized control system.

appears when the HOLD function is enabled.

2!

$ 2

▌4 Appears when the Weekly timer is enabled.

▌5 Appears while the units are operated in the energy-save mode. (Will not appear on some models of indoor units)

▌6 Appears while the outdoor units are operated in the silent mode.

(This indication is not available for CITY MULTI models)

▌7 Appears when the built-in thermistor on the remote controller is acti-vated to monitor the room temperature (1).

appears when the thermistor on the indoor unit is activated to monitor the room temperature.

▌8 Indicates the vane setting.

▌9 Indicates the louver setting.

Indicates the ventilation setting.

Appears when the preset temperature range is restricted.

Appears when an energy-saving operation is performed using a “3D i- See sensor” function.

▌# Centrally controlled Appears for a certain period of time when a centrally-controlled item is operated.

▌$ Preliminary error display An error code appears during the preliminary error.

Most settings (except ON/OFF, mode, fan speed, temperature) can be made from the Main menu. (Refer to Page 8.)

32$ 45 6 7 8

VG79Y607H01_IM.indb 4 21-Nov-22 16:14:19

■ Wireless Remote-Controller

2. Parts Names

Temperature setting The units of temperature can be changed. For details, refer to the Installation Manual.

Not available Appears when a non-supported func-tion is selected.

Battery replacement indicator Appears when the remaining battery power is low.

Vane setting Step 1 Step 2 Step 3 Step 4 Step 5 Swing Auto

Fan speed setting Auto

3D i-see Sensor (Air distribution) Default Direct Indirect When Direct or Indirect is selected, the vane setting is set to “Auto”.

Set Temperature buttons

Weekly timer ON/OFF button

Set Time button (Sets the time)

Airflow button (Changes up/down airflow direction)

Mode button (Changes operation mode)

Timer ON button

Timer OFF button

OFF/ON button

Fan Speed button (Changes fan speed)

SET/SEND button

CANCEL button

Up/Down buttons

Menu button i-see button

Reset button

Remote controller display

Battery replacement indicator

Transmission area

Not available

Operation mode Cool Dry

Fan Auto

Heat

Note:

Inthisoperationmanual,theterm“Wirelessremotecontroller”refersonlytothePAR-SL101A-E.Ifyouneedanyinformationforother
remotecontrollers,refertotheoperationmanualthatisincludedwiththegrille,whichincludesaremotecontroller,ortheoperation
manualthatisincludedwiththeoptionalremotecontroller.

VG79Y607H01_IM.indb 5 21-Nov-22 16:14:21

2. Parts Names

■ Outdoor unit

Power

Earth

Service Panel

Indoor-Outdoor Connection wire

Ref. Pipes

Notes (Only for wireless remote controller):

■ When using the wireless remote controller, point it towards the receiver on the indoor unit.

■ If the remote controller is operated within approximately 3 minutes after power is supplied to the indoor unit, the indoor unit may beep twice as the unit is performing the initial automatic check.

■ The indoor unit beeps to confirm that the signal transmitted from the remote controller has been received. Signals can be received up to approximately 7 meters in a direct line from the indoor unit in an area 45° to the left and right of the unit. However, illumination such as fluorescent lights and strong light can affect the ability of the indoor unit to receive signals.

■ To avoid misplacing the remote controller, install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use.

Warning:

■ Do not dispose of the controller by yourself.

• Consult your dealer in case of disposal.

■ Never modify or repair the controller by yourself.

• Any deficiency caused by your modification or repair may result in an electric shock or fire.

Consult your dealer about repairs.

■ Stopoperationiftheoperationlamponthecontroller’sreceiverblinksorifan
abnormalityoccurs.

• Leaving the controller in these conditions can lead to fire or breakdown. Report such conditions to your dealer.

■ Neverallowthealkalinebatteriestoshort-circuit.Neverdisassemble,heatorplacethem
infire.

• Doing so can cause the strong alkaline liquid to leak and possibly enter your eyes or cause the batteries to explode or heat up, resulting in personal injuries, burning or mechanical breakdowns. If strong alkaline liquid comes in contact with your skin or clothes, wash it off with clean water. If it gets in to your eyes, wash them with clean water and consult a doctor immediately.

Caution:

■ Do not drop the controller.

• Doing so may cause the case to crack and may disable control.

■ Do not wash with water.

• Doing so may cause an electric shock or breakdown.

■ Do not touch any control button with wet hands.

• Doing so may cause an electric shock or breakdown.

■ Do not press any control button with a sharp object.

• Doing so may cause an electric shock or breakdown.

■Incorrectuseofbatteriescancauseliquidleakage,explosionorheatingandmayresult
inbreakdownorpersonalinjury.Adheretothefollowing.

(1) Do not recharge the batteries.

(2) Insert the batteries in the correct direction.

(3) Do not mix a new battery with an old battery or batteries of different types.

(4) Remove the batteries immediately when they have run out.

Battery installation/replacement

1. Remove the top cover, insert two LR6 AA batteries, and then install the top cover.

2. Press the Reset button.

Two LR6 AA batteries Insert the negative (–) end of each battery first. Install the batteries in the correct directions (+, –) !

Press the Reset button with an object that has a narrow end.

Top cover

After battery installation/replacement, please set clock.

Without setting clock, you cannot use a part of function of remote controller.

VG79Y607H01_IM.indb 6 21-Nov-22 16:14:21

3. Operation

■ About the operation method, refer to the operation manual that comes with each remote controller.

3.1. Turning ON/OFF

[ON] [OFF]

■ Operation status memory Remote controller setting

Operation mode Operation mode before the power was turned off Preset temperature Preset temperature before the power was turned off Fan speed Fan speed before the power was turned off

■ Settable preset temperature range Operation mode Preset temperature range Cool/Drying 67 - 87 ºF/19 - 30 ºC Heat 63 - 83 ºF/17 - 28 ºC Auto 67 - 83 ºF/19 - 28 ºC Fan/Ventilation Not settable

Note:

EvenifyoupresstheON/OFFbuttonimmediatelyaftershuttingdowntheoperationisprogress,theairconditionerwillnotstartforabout3minutes.
Thisistopreventtheinternalcomponentsfrombeingdamaged.

3.2. Mode Selection

Press the [F1] button to go through the oper-ation modes in the order of “Cool”, “Drying”, “Fan”, “Auto”, and “Heat”. Select the desired operation mode.

Cool Drying Fan

Auto Heat

• Operation modes that are not available to the connected outdoor unit models will not appear on the display.

What the blinking mode icon means The mode icon will blink when other indoor units in the same refrigerant system (connected to the same outdoor unit) are already operated in a different mode. In this case, the rest of the unit in the same group can only be operated in the same mode.

Automatic operation

■ According to a set temperature, cooling operation starts if the room tem-perature is too hot and heating operation starts if the room temperature is too cold.

■ During automatic operation, if the room temperature changes and re-mains 2.0 °C, 4 °F or more above the set temperature for 15 minutes, the air conditioner switches to cool mode. In the same way, if the room temperature remains 2.0 °C, 4 °F or more below the set temperature for 15 minutes, the air conditioner switches to heat mode.

Informationformultisystemairconditioner(Outdoor
unit:MXZseries)
■Multisystemairconditioner(Outdoorunit:MXZseries)can
connecttwoormoreindoorunitswithoneoutdoorunit.According
tothecapacity,2ormoreunitscanoperatesimultaneously.

• When you try to operate 2 or more indoor units with 1 outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected.

The other indoor units that will start the operation later cannot operate, indicating an operation state in blinking.

In this case, please set all the indoor units to the same operation mode.

• There might be a case that the indoor unit, which is operating in “Auto” mode. Cannot change over to the operating mode “Cool”/“Heat” and becomes a state of standby.

• When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. about 15 minutes) to blow out the warm air.

• In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.

3.3.Temperaturesetting
<Cool,Drying,Heat,andAuto>

Cool Room

AutoSet temp.

Mode Temp. Fan

Fri

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

Operation mode

Room temperature (Refer to the Installation Manual.)

Press the [F2] button to decrease the preset temperature, and press the [F3] button to increase.

• Refer to the table on 3.1 for the settable temperature range for different operation modes.

• Preset temperature range cannot be set for Fan/Ventilation operation.

• Preset temperature will be displayed either in Centigrade in 0.5- or

1-degree increments, or in Fahrenheit, depending on the indoor unit model and the display mode setting on the remote controller.

Cool mode 15 minutes (switches from heating to cooling)

Set temperature +2.0 °C, +4 °F

Set temperature

Set temperature -2.0 °C, -4 °F

15 minutes (switches from cooling to heating)

Press the [ON/OFF] button.

The ON/OFF lamp will light up in green, and the operation will start.

When “LED lighting” is set to “No”, the ON/OFF lamp will not light up.

* Refer to the installation manual of wired remote controller.

Press the [ON/OFF] button again.

The ON/OFF lamp will come off, and the operation will stop.

ON

OFF

ON

OFF

Cool Room

AutoSet temp.

Mode Temp. Fan

Fri

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

VG79Y607H01_IM.indb 7 21-Nov-22 16:14:22

3. Operation

3.4. Fan speed setting

MENU

ON

OFFRETURN SELECT

HOLD

Cool Room

AutoSet temp.

Mode Temp. Fan

Fri

F1 F2 F3 F4

Press the [F4] button to go through the fan speeds in the following order.

Auto

• The available fan speeds depend on the models of connected indoor units.

Notes:

● The number of available fan speeds depends on the type of unit connected.

● Inthefollowingcases,theactualfanspeedgeneratedbytheunit
willdifferfromthespeedshowntheremotecontrollerdisplay.
1.Whilethedisplayisin“Standby”or“Defrost”states.
2.Whenthetemperatureoftheheatexchangerislowintheheat-
ingmode.
(e.g.immediatelyafterheatingoperationstarts)

3. In HEAT mode, when room temperature is higher than the tem-perature setting.

4. In COOL mode, when room temperature is lower than the tem-perature setting.

5. When the unit is in Drying mode.

<Exiting the Main menu screen>

MENU

ON

OFFRETURN SELECT

HOLD

Cool Room

AutoSet temp.

Mode Temp. Fan

Fri

F1 F2 F3 F4

If no buttons are touched for 10 minutes, the screen will automatically return to the Main display. Any settings that have not been saved will be lost.

<Display of unsupported functions> Title

Not available Unsupported function

Return: RETURN

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

Press the [RETURN] button to exit the Main menu and return to the Main display.

The message at left will appear if the user selects a function not supported by the corresponding indoor unit model.

Press [F2] to move the cursor left.

Press [F3] to move the cursor right.

3.5.Airflowdirectionsetting
3.5.1NavigatingthroughtheMainmenu
<AccessingtheMainmenu>

Press the [MENU] button on the Main display.

The Main menu will appear.

Main Main menu

Operation

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

<Item selection>

MENU

ON

OFFRETURN SELECT

HOLD

Main Main menu

Initial setting

F1 F2 F3 F4

Cursor

3.5.2Vane·Vent.(Lossnay)
<Accessingthemenu>

Select “Vane·Louver·Vent.

(Lossnay)” from the Operation menu, and press the [SELECT/ HOLD] button.

Select “Operation” from the Main menu (refer to 3.5.1), and press the [SELECT/HOLD] button.

MENU

ON

OFFRETURN SELECT

HOLD

Main Main menu

Operation

F1 F2 F3 F4

MENU

ON

OFFRETURN SELECT

HOLD

Main menu: RETURN Cursor

Operation Vane·Louver·Vent. (Lossnay) High power Comfort

VG79Y607H01_IM.indb 8 21-Nov-22 16:14:23

Outlet No. 2 Outlet No. 3

Outlet No. 1 Outlet No. 4

3. Operation

Remote controller setting The airflow direction of this outlet is controlled by the airflow direc-tion setting of remote controller.

Fixed The airflow direction of this outlet is fixed in particular direction.

* When it is cold because of direct airflow, the airflow direction can be fixed horizontally to avoid direct airflow.

<How to set the fixed up/down air direction> Note:

● This function cannot be set depending on the outdoor unit to be connected.

• For PLA-A▪EA8, only the particular outlet can be fixed to certain direction with the procedures below. Once fixed, only the set outlet is fixed every time air conditioner is turned on. (Other outlets follow UP/ DOWN air direction setting of remote controller.)

■ Explanation of word

• “Refrigerant address No.” and “Unit No.” are the numbers given to each air conditioner.

• “Outlet No.” is the number given to each outlet of air conditioner.

(Refer to the illustration below.)

• “Up/Down air direction” is the direction (angle) to fix.

Notes:

●Duringswingoperation,thedirectionalindicationonthescreen
doesnotchangeinsyncwiththedirectionalvanesontheunit.
● Availabledirectionsdependonthetypeofunitconnected.
● Inthefollowingcases,theactualairdirectionwilldifferfromthe
directionindicatedontheremotecontrollerdisplay.
1.Whilethedisplayisin“STANDBY”or“DEFROST”states.
2.Immediatelyafterstartingheatmode(whilethesystemiswait-
ingforthemodechangetotakeeffect).
3.Inheatmode,whenroomtemperatureishigherthanthetem-

perature setting.

Horizontal airflow

Note:

TheoutletNo.isindicatedbythenumberofgroovesonboth
endsofeachairoutlet.Settheairdirectionwhilecheckingthe
informationshownontheremotecontrollerdisplay.

Air outlet identification marks

<Vent. setting>

Press the [F1] or [F2] button.

Press the button as indicated above to go through the following setting options.

Auto Auto Step 1 Step 2

Step 3 Step 4 Step 5

Swing Swing

Select “Swing” to move the vanes up and down automatically.

When set to “Step 1” through “Step 5”, the vane will be fixed at the selected angle.

Press the [F4] button to go through the ventilation setting options in the order of “Off”, “Low”, and “High”.

* Settable only when LOSSNAY unit is connected.

Off Low High Off Low High

• The fan on some models of indoor units may be interlocked with cer-tain models of ventilation units.

• under the vane setting icon This icon will appear when the vane is set to “Step 5” and the fan oper-ates at low speed during cooling or drying operation (depends on the model).

The icon will go off in an hour, and the vane setting will automatically change.

Fri

Room

Set temp.

Mode Temp. Fan

Cool Auto

<Vane setting>

Fri

Low

Vent.

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

MENU

ON

OFFRETURN SELECT

HOLD

Fri

Off

Vent.Vane

F1 F2 F3 F4

<Returning to the Main menu>

Press the [RETURN] button to go back to the Main menu.

MENU

ON

OFFRETURN SELECT

HOLD

Main menu: RETURN Cursor

Operation Vane·Louver·Vent. (Lossnay) High power Comfort

VG79Y607H01_IM.indb 9 21-Nov-22 16:14:26

3. Operation

■ Manual vane angle (Wired remote controller) 1 Select “Comfort” from the Opera-tion menu, and press the [SELECT/ HOLD] button.

Main menu: RETURN Cursor

Operation Vane·Louver·Vent. (Lossnay) High power Comfort

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

2 Select “Manual vane angle” with the [F1] or [F2] button, and press the [SELECT/HOLD] button.

Setting display: SELECT Cursor

Comfort Manual vane angle 3D i-See sensor

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

F1 F2 F3 F4

Manual vane angle

Input display:

Cur. Address

Ref. address Unit No.

Identify unit Check button

Check

SELECT

MENU

ON

OFFRETURN SELECT

HOLD

3 Move the cursor to “Ref. address” or “Unit No.” with the [F1] button to select.

Select the refrigerant address and the unit number for the units to whose vanes are to be fixed, with the [F2] or [F3] button, and press the [SELECT/HOLD] but-ton.

• Ref. address: Refrigerant address

• Unit No.: 1, 2, 3, 4 Press the [F4] button to confirm the unit.

F1 F2 F3 F4

Manual vane angle

Cur. Angle

Ref. address Unit No.

Vane 4-way /2-way

Cursor Input display:Angle button

MENU

ON

OFFRETURN SELECT

HOLD

Select “Vane” with the [F1] button.

Select “4-way” or “2-way” with the [F2] or [F3] button, and press the [F4] button.

Select: SELECT

Manual vane angle

Outlet Angle

Setting

Manual vane angle

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

4 The current vane setting will ap-pear.

Select the desired outlets from “1”,“2”, “3”, “4”, or “1, 2, 3, 4 (all outlets)” with the [F1] or [F2] but-ton.

Press the [F3] or [F4] button to go through the following options and select the desired setting.

* Draft reduction The airflow direction for this set-ting is more horizontal than the airflow direction for the “Step 1” setting in order to reduce a drafty feeling. The draft reduction can be set for only 1 vane.

Note:

Donotsetthedraftreductioninanenvironmentwithhighhumidity.
Otherwise,condensationmayformanddrip.

■ Vane setting

Step 1 Step 2

Step 3

No setting

Draft reduction* All outlets

Step 5Step 4

Press the [SELECT/HOLD] button to save the settings.

A screen will appear that indicates the setting information is being trans-mitted.

The setting changes will be made to the selected outlet.

The screen will automatically return to the one shown above (step 5) when the transmission is completed.

Make the settings for other outlets, following the same procedures.

If all outlets are selected, will be displayed the next time the unit goes into operation.

Navigating through the screens

• To go back to the Main menu ................ [MENU] button

• To return to the previous screen .......... [RETURN] button

VG79Y607H01_IM.indb 10 21-Nov-22 16:14:27

3. Operation

1 First, confirm by setting “Ref.

address” to 0 and “Unit No.” to 1.

• Move the cursor to “Ref. address” or “Unit No.” with the [F1] button to select.

• Select the refrigerant address and the unit number for the units to whose vanes are to be fixed, with the [F2] or [F3] button, and press the [SELECT/HOLD] button.

• Ref. address: Refrigerant address

• Unit No.: 1, 2, 3, 4 Press the [F4] button to confirm the unit.

2 Change the “Unit No.” in order and check each unit.

• Press the [F1] button to select “Unit No.”.

Press the [F2] or [F3] button to change the “Unit No.” to the unit that you want to check, and then press the [F4] button.

• After pressing the [F4] button, wait approximately 15 seconds, and then check the current state of the air conditioner.

→ The vane is pointing downward.

→ This air conditioner is displayed on the remote controller.

→ All outlets are closed. → Press the [RETURN] button and continue the operation from the beginning.

→ The messages shown to the left are displayed. → The target device does not exist at this refrig-erant address.

• Press the [RETURN] button to return to the initial screen.

3 Change the “Ref. address” to the next number.

• Refer to step 1 to change the “Ref. address” and continue with the confirmation.

3.6. 3D i-see Sensor setting Note:

This function cannot be set depending on the outdoor unit to be connected.

3.6.1 3D i-see Sensor setting 1 Select “Operation” from the Main menu, and press the [SELECT/ HOLD] button.

F1 F2 F3 F4

Main Main menu

Operation

MENU

ON

OFFRETURN SELECT

HOLD

2 Select “Comfort” from the Operation menu, and press the [SELECT/HOLD] button.

Main menu: RETURN Cursor

Operation Vane·Louver·Vent. (Lossnay) High power Comfort

F1 F2 F3 F4

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

Manual vane angle

Input display:

Cur. Address Check

SELECT

MENU

ON

OFFRETURN SELECT

HOLD

Ref. address Unit No.

Identify unit Check button

■ Confirmation procedure (wired remote controller)

F1 F2 F3 F4

Manual vane angle

RETURN

MENU

ON

OFFRETURN SELECT

HOLD

Return:

Ref. address Unit No.

Function setting for unit with vane fully open.

F1 F2 F3 F4

Manual vane angle

Return:

No communication Check Unit state.

RETURN

3 Select “3D i-See sensor” with the [F1] or [F2] button, and press the [SELECT/HOLD] button.

Setting display: SELECT Cursor

Comfort Manual vane angle 3D i-See sensor

F1 F2 F3 F4

MENU

ON

OFFRETURN SELECT

HOLD

4 Select the desired menu with the [F1] or [F2] button, and press the [SELECT/HOLD] button.

• Air distribution Select the airflow direction control method when the airflow direction is set to “Auto”.

• Energy saving option Operates the energy-save mode according to whether persons are detected in the room by the 3D i-see Sensor.

• Seasonal airflow When the thermostat turns off, the fan and the vanes operate accord-ing to the control settings.

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

Setting display: SELECT Cursor

3D i-See sensor Air distribution Energy saving option Seasonal airflow

3.6.2 Air distribution

1 Move the cursor to “Ref. address” or “Unit No.” with the [F1] button to select.

Select the refrigerant address and the unit number for the units to whose vanes are to be fixed, with the [F2] or [F3] button, and press the [SELECT/HOLD] button.

• Ref. address: Refrigerant address

• Unit No.: 1, 2, 3, 4 Press the [F4] button to confirm the unit.

The vane of only the target indoor unit is pointing downward.

Air distribution

Input display:

Cur. Address Check

Ref. address Unit No.

Identify unit Check button

F1 F2 F3 F4

SELECT

MENU

ON

OFFRETURN SELECT

HOLD

2 Select the menu with the [F4] but-ton.

Default → Area → Direct/Indirect → Default…

Default: The vanes move the same as during normal operation.

“Area”*: The vanes move to the down airflow direction toward areas with a high floor temperature during cooling mode and toward areas with a low floor temperature during heating mode. Otherwise, the vanes move to the horizontal airflow direction.

“Direct/Indirect”*: The vanes automatically move relative to the areas where persons are detected.

The vanes operate as indicated in the following table.

* In order to enable this function, the airflow direction must be set to “Auto”.

Air distribution

Select:

Cur.

Ref. address Unit No.

Auto vane

Direct/Indirect setting

All

Direct/Indirect

F1 F2 F3 F4

SELECT

MENU

ON

OFFRETURN SELECT

HOLD

Vane setting Direct Indirect

Cooling horizontal → swing keep horizontal Heating keep downward downward → horizontal

VG79Y607H01_IM.indb 11 21-Nov-22 16:14:28

3. Operation

3 When Direct/Indirect is selected, set each air outlet.

Select the air outlet with the [F1] or [F2] button, and change the setting with the [F4] button.

After changing the settings for all of the air outlets, press the [SELECT/ HOLD] button to save the settings.

* In order to enable this function, the airflow direction must be set to “Auto”.MENU

ON

OFFRETURN SELECT

HOLD

Direct/Indirect setting

: Direct : Indirect : Indirect : Direct

Select: SELECT Outlet Angle

F1 F2 F3 F4

3.6.3 Energy saving option

1 Select the desired menu with the

[F1] or [F2] button.

No occupancy energy save If there are no persons in the room for 60 minutes or more, energy-saving operation equal to 2 °C, 4 °F is performed.

Room occupancy energy save If the occupancy rate decreases to approximately 30% of the maximum occupancy rate, energy-saving operation equal to 1 °C, 2 °F is performed.

No occupancy Auto-OFF If there are no persons in the room for the set amount of time (60–180 minutes), the operation is automatically stopped.

Energy saving option

Cursor Setting display: SELECT

No occupancy energy save Room occupancy energy save No occupancy Auto-OFF

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

2 When No occupancy energy save or Room occupancy energy save is selected.

Select the setting with the [F4] but-ton.

OFF → Cooling only → Heating only → Cooling/Heating → OFF…

After changing the setting, press the [SELECT/HOLD] button to save the setting.

Energy saving option

Select: SELECT

No occupancy energy save

Cooling/Heating

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

OFF: The function is disabled.

Cooling only: The function is ena-bled only during cooling mode.

Heating only: The function is ena-bled only during heating mode.

Cooling/Heating: The function is enabled during both cooling mode and heating mode.

Energy saving option

Select: SELECT

Room occupancy energy save

Cooling/Heating

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

3 When No occupancy Auto-OFF is selected.

Set the time with the [F3] or [F4] button.

---: The setting is disabled (the op-eration will not stop automatically).

60–180: The time can be set in 10-minute increments.

Energy saving option

Select: SELECT Time

No occupancy Auto-OFF

120 min.

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

4 The message at left will appear if the operation was stopped automatically by the No occupancy Auto-OFF setting.

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

18:47 Thu

Shut down by No Occupancy Auto-OFF

31/Dec 12:59

VG79Y607H01_IM.indb 12 21-Nov-22 16:14:28

4. Timer

■ Timer functions are different by each remote controller.

■ For details on how to operate the remote controller, refer to the appropriate operation manual included with each remote controller.

Notes:

Anypersonatthefollowingplacescannotbedetected.
●Alongthewallonwhichtheairconditionerisinstalled
●Directlyundertheairconditioner
●Whereanyobstacle,suchasfurniture,isbetweenthepersonand
theairconditioner
Apersonmaynotbedetectedinthefollowingsituations.
●Roomtemperatureishigh.
●Apersonwearsheavyclothesandhis/herskinisnotexposed.
●Aheatingelementofwhichtemperaturechangessignificantlyis

present.

● Some heat sources, such as a small child or pet, may not be sensed.

●Aheatsourcedoesnotmoveforalongtime.
The3Di-seeSensoroperatesonceapproximatelyevery3minutes
tomeasurethefloortemperatureanddetectpersonsintheroom.
●Theintermittentoperatingsoundisanormalsoundproduced
whenthe3Di-seeSensorismoving.
●WhenMARemoteControllerisusedtocontrolmultiplerefriger-
antsystems,NooccupancyAuto-OFFcannotbeused.

3.7. Ventilation

For LOSSNAY combination

■ The following 2 patterns of operation is available.

• Run the ventilator together with indoor unit.

• Run the ventilator independently.

Notes:(forwirelessremotecontroller)
●Runningtheventilatorindependentlyisnotavailable.
●Noindicationontheremotecontroller.

3. Operation

1 Select the setting with the [F4] button.

OFF → Cooling only → Heating only → Cooling/Heating → OFF…

After changing the setting, press the [SELECT/HOLD] button to save the setting.

OFF: The function is disabled.

Cooling only: When the thermostat turns off during cooling mode, the vanes move up and down.

Heating only: When the thermostat turns off during heating mode, the vanes move to the horizontal airflow direction to circulate the air.

Cooling/Heating: The function is enabled during both cooling mode and heating mode.

* In order to enable this function, the airflow direction must be set to “Auto”.

* Only heat pump model enables the function during heating mode.

3.6.4 Seasonal airflow function

When the remote controller cannot be used When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons on the grille.

A DEFROST/STAND BY lamp B Operation lamp C Emergency operation cooling switch D Emergency operation heating switch E Receiver

Starting operation

• To operate the cooling mode, press the button C for more than 2 seconds.

• To operate the heating mode, press the button D for more than 2 seconds.

• Lighting of the Operation lamp B means the start of operation.

Notes:

Details of emergency mode are as shown below.

Details of EMERGENCY MODE are as shown below.

Operation mode COOL HEAT Set temperature 24°C, 75°F 24°C, 75°F

Fan speed High High Airflow direction Horizontal Downward

Stopping operation

• To stop operation, press the button C or the button D for more than

2 seconds.

5. Emergency Operation for Wireless Remote-controller

E

C B

B A

Seasonal airflow

Select: SELECT

Seasonal airflow

Cooling/Heating

MENU

ON

OFFRETURN SELECT

HOLD

Seasonal airflow

Select: SELECT

Seasonal airflow

Cooling/Heating

VG79Y607H01_IM.indb 13 21-Nov-22 16:14:29

6. Care and Cleaning

When the is displayed on the Main display in the Full mode, the system is centrally controlled and the filter sign cannot be reset.

If two or more indoor units are connected, filter cleaning timing for each unit may be different, depending on the filter type.

The icon will appear when the filter on the main unit is due for cleaning.

When the filter sign is reset, the cumulative operation time of all units will be reset.

The icon is scheduled to appear after a certain duration of operation, based on the premise that the indoor units are installed in a space with ordinary air quality. Depending on the air quality, the filter may require more frequent cleaning.

The cumulative time at which filter needs cleaning depends on the model.

• This indication is not available for wireless remote controller.

■ Filter information

Cool Room

AutoSet temp.

Mode Temp. Fan

Fri

Main Main menu

Maintenance

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

Main menu: RETURN Cursor

Maintenance menu Error information Filter information Cleaning

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

Main menu: MENU Reset

Filter information

Press Reset button after filter cleaning.

Please clean the filter.

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4

OKCancel

Filter information

Reset filter sign?

Main menu: MENU

Filter information

Filter sign reset

MENU

ON

OFFRETURN SELECT

HOLD

F1 F2 F3 F4 will appear on the Main display in the Full mode when it is time to clean the filters.

Wash,clean,orreplacethefilters
whenthissignappears.
RefertotheindoorunitInstruc-
tionsManualfordetails.

Select “Maintenance” from the Main menu, and press the [SELECT/ HOLD] button.

Select “Filter information” from the Maintenance menu, and press the [SELECT/HOLD] button.

Press the [F4] button to reset filter sign.

Refer to the indoor unit Instructions Manual for how to clean the filter.

Select “OK” with the [F4] button.

A confirmation screen will appear.

Navigating through the screens

• To go back to the Main menu ....................... [MENU] button

• To return to the previous screen .