This is a Request for Quote (RFQ) bid specification document issued by the Soldiers' Home in Chelsea, a Massachusetts state facility, for preventive maintenance services on domestic water booster and pressure-reducing valve systems. The solicitation requires vendors to provide scheduled preventive maintenance for cold-water pressure-reducing/zone-valve assemblies and an Armstrong triplex variable-frequency-drive domestic-water booster system serving the Community Living Center. The scope includes inspection, cleaning, exercising, testing, adjustment, and documentation of four primary service items: a Watts 4-inch cold-water zone valve assembly, a Watts 3/4-inch low-flow bypass pressure-reducing valve, a Watts 2-1/2-inch mid-flow pressure-reducing valve, and the Armstrong triplex VFD booster system with hydrotank. The RFQ was issued on November 23, 2026, with questions due by November 30, 2026, and bids due on December 4, 2026. The contract term runs from December 7, 2027, through December 31, 2027.
Bidders must provide line-item pricing for each preventive maintenance service and submit documentation including labor rates (regular-time, overtime, and emergency/after-hours), parts/material markup percentages, and any applicable travel or service charges. The solicitation requires vendors to be regularly engaged in servicing commercial domestic-water booster systems and VFD pump systems of similar complexity, with properly trained and qualified technicians who comply with applicable Commonwealth of Massachusetts safety requirements and licensing requirements. Prevailing wage documentation, signed service slips, and supporting documentation must accompany invoices submitted to chelseasohoinvoices@mass.gov. No set-aside provisions are identified in this specification, and no incumbent contractor information is provided.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLDIERS' HOME IN CHELSEA | REQUEST FOR QUOTE
Bid Specification - Domestic Water Booster & Zone Valve PM | Page 1
REQUEST FOR QUOTE
Preventive Maintenance - Domestic Water Booster System & Pressure-Reducing /
Zone Valves
Soldiers' Home in Chelsea
100 Summit Avenue, Chelsea, Massachusetts 02150
Bid Number BD-27-1368-CHE01-CHE01- 135642_________________________
Issue Date __November 23, 2026___________
Questions Due __November 30, 2026___________
Bid Due Date / Time __December 4, 2026___________
Contract Term December 7, 2027-December 31, 2027__________________________
This specification is written on a vendor-neutral basis so qualified firms can quote the same preventive-maintenance scope. The successful vendor shall furnish all labor, supervision, routine service tools, test instruments, and documentation necessary to complete the work described below.
1. Scope of Work Provide scheduled preventive maintenance for the domestic cold-water pressure-reducing / zone-valve assemblies and the Armstrong triplex variable-frequency-drive (VFD) domestic-water booster system serving the Community
Living Center at the Soldiers' Home in Chelsea. Work shall include inspection, cleaning, exercising, testing, adjustment, recording of operating data, and written reporting.
2. Existing Equipment / Service Items Service Item Equipment /
Description Existing Size / Type Reference Setting /
Data
CLCCOLDZONEVALVE Cold-water zone valve assembly
Watts 4 in. zone valve with PRV/CRD
Existing service record:
80 PSI inlet; 75 PSI outlet / setpoint
CLCCOLDLOWFLOWZNVLV Low-flow bypass pressure-reducing valve
Watts 3/4 in. direct-acting PRV
Existing service record:
80 PSI inlet/outlet; set to
80 PSI
CLCCOLDMIDFLOWZNVLV Mid-flow pressure-reducing valve
Watts 2-1/2 in. direct-acting PRV
Existing service record:
80 PSI inlet; 77 PSI outlet
2021126019 Domestic-water booster package
Armstrong triplex VFD booster with hydrotank
3 pumps; approximately 480 V, 3-phase system
Note: Manufacturer names, model references, and prior readings are provided to identify existing equipment and establish the maintenance scope; they are not intended to restrict competition.
3. Zone Valve / PRV Preventive Maintenance
• Check and record all available pressure gauges before and after service.
• Inspect and clean strainers.
• Disassemble as required and clean the zone-valve / PRV body.
• Inspect and clean control-restriction devices (CRDs), pilots, and related control components where applicable.
Bid Specification - Domestic Water Booster & Zone Valve PM | Page 2
• Inspect diaphragms, fasteners, seals, trim, and internal components for wear, looseness, damage, or deterioration.
• Exercise isolation valves associated with the serviced assembly were safe and practical.
• Reassemble, place equipment back in service, and adjust pressure settings to the facility-approved operating setpoint.
• Verify stable operation and check for leakage after service.
• Identify any parts or rebuild work required. No non-routine repair or replacement shall be performed without prior written authorization.
• Record inlet pressure, outlet pressure, final setpoint, deficiencies found, corrective action performed, and recommendations.
4. Booster Pump Preventive Maintenance
• Check and, if necessary, adjust controller clock/date settings where applicable.
• Clean external motor surfaces and clean ventilation fan areas on VFD equipment.
• Check pump shutoff / operating pressure using available test points and verify proper pump performance.
• Check and record system pressure, suction pressure, and other available pressure readings.
• Verify proper pump rotation and inspect for water leakage, seal leakage, unusual noise, and vibration.
• Inspect/clean strainers, PRVs, CRDs, check valves, and orifice elbows, where installed and applicable.
• Test alarms and panel indicator lights where applicable.
• Check system sequencing, lead/lag operation, and flow-sensing devices.
• Check hydrotank / accumulator precharge and operation. Drain/isolate as necessary to obtain an accurate precharge reading.
• Exercise pump isolation valves.
• Record hour-meter readings for each pump.
• Run each pump in manual mode as appropriate and document seal leakage / condition.
• Check pump shaft runout on vertical turbine pumps only, if applicable.
• Measure and record phase-to-phase voltage and current draw for each pump/motor while operating. Note any imbalance or readings outside manufacturer limits.
• Lubricate equipment in accordance with manufacturer recommendations where applicable.
• Return the complete booster system to normal automatic operation after testing.
5. Operating Data to Be Documented Item Existing Reference Reading Vendor PM Requirement
System pressure 80 PSIG Record actual
Suction pressure 32 PSIG Record actual min/max if available
Hydrotank precharge 70 PSI Record as-found and final
Low system pressure setting 54 PSIG Verify / record
High system pressure setting 95 PSIG Verify / record
Low suction pressure setting 5 PSIG Verify / record
Pump 1 hour meter Prior record: 3942 Record current
Pump 2 hour meter Prior record: 3997 Record current
Pump 3 hour meter Prior record: 3991 Record current
Motor voltage Prior readings approx. 488-492 V phase-to-phase
Record each phase pair
Motor current Prior readings approx. 6.1-8.2 A Record each phase
Prior readings are historical references only. The bidder is responsible for verifying actual operating conditions at the time of service.
Bid Specification - Domestic Water Booster & Zone Valve PM | Page 3
6. Service Report / Deliverables
• A completed preventive-maintenance checklist for each service item.
• All pressure, voltage, amperage, hour-meter, precharge, setpoint, and other readings taken during service.
• Technician's description of work performed and condition of equipment.
• A written deficiency list identifying items requiring repair, rebuild, or replacement, with separate pricing when requested.
• Confirmation that serviced equipment was returned to normal operating condition.
• Technician name, service date, arrival/departure time, and facility representative acknowledgment.
7. Vendor Requirements
• Vendor shall be regularly engaged in service of commercial domestic-water booster systems, pressure-reducing valves, control valves, and VFD pump systems of similar size and complexity.
• Technicians shall be properly trained and qualified for the equipment being serviced and shall comply with all applicable safety requirements, lockout/tagout procedures, and facility rules.
• Vendor shall provide proof of required insurance and any licenses or certifications required by the
Commonwealth of Massachusetts for work included in its proposal.
• Test instruments used for electrical and pressure measurements shall be appropriate for the service and maintained in suitable condition.
• Vendor shall coordinate shutdowns or interruptions with the facility in advance. Domestic-water service shall not be interrupted without facility authorization.
• Bid shall clearly identify any exclusions, assumptions, travel charges, minimum charges, or work not included in the quoted preventive-maintenance price.
• Invoice Documentation: Applicable prevailing wage documentation, signed service slips, and any additional supporting documentation must be submitted with each invoice to the CHE Invoice Mailbox at chelseasohoinvoices@mass.gov. Incomplete invoice submissions may result in payment processing delays.
8. Pricing Schedule Line Description Qty. Bid Price
1 PM - Watts 4 in. cold-water zone valve assembly
1 $____________
2 PM - Watts 3/4 in. low-flow bypass PRV
1 $____________
3 PM - Watts 2-1/2 in. mid-flow PRV
1 $____________
4 PM - Armstrong triplex VFD booster system with hydrotank
1 $____________
5 Required PM documentation / reports
1 lot $____________
TOTAL PREVENTIVE
MAINTENANCE BID
9. Labor and Markup Rates Rate / Charge Bidder Entry
Regular-time labor rate ____________________________
Overtime labor rate ____________________________
Emergency / after-hours labor rate ____________________________ mailto:chelseasohoinvoices@mass.gov
Bid Specification - Domestic Water Booster & Zone Valve PM | Page 4
Parts/material markup (%) ____________________________
Travel / service charge, if any ____________________________
10. Bidder Information and Certification Company Name
Address
Contact Person
Telephone / Email
Authorized Signature
Printed Name / Title
Date
Bidder certification: The undersigned has reviewed this scope and proposes to furnish the specified preventive-maintenance services for the prices stated, subject only to clearly identified written exceptions.
| 1. Scope of Work |
| 2. Existing Equipment / Service Items |
| 3. Zone Valve / PRV Preventive Maintenance |
| 4. Booster Pump Preventive Maintenance |
| 5. Operating Data to Be Documented |
| 6. Service Report / Deliverables |
| 7. Vendor Requirements |
| 8. Pricing Schedule |
| 9. Labor and Markup Rates |
| 10. Bidder Information and Certification |